Policy Replication

Electric Power Generation, Transmission, and Distribution; Electrical Protective Equipment

Federal Register2014-04-11 · DEPARTMENT OF LABOR; Occupational Safety and Health Administration · Rule · 2013-29579
Final rule.

OSHA last issued rules for the construction of transmission and distribution installations in 1972. Those provisions are now out of date and inconsistent with the more recently promulgated general industry standard covering the operation and maintenance of electric power generation, transmission, and distribution lines and equipment. OSHA is revising the construction standard to make it more consistent with the general industry standard and is making some revisions to both the construction and general industry requirements. The final rules for general industry and construction include new or revised provisions on host employers and contractors, training, job briefings, fall protection, insulation and working position of employees working on or near live parts, minimum approach distances, protection from electric arcs, deenergizing transmission and distribution lines and equipment, protective grounding, operating mechanical equipment near overhead power lines, and working in manholes and vaults. The revised standards will ensure that employers, when appropriate, must meet consistent requirements for work performed under the construction and general industry standards. The final rule also revises the general industry and construction standards for electrical protective equipment. The existing construction standard for the design of electrical protective equipment, which applies only to electric power transmission and distribution work, adopts several national consensus standards by reference. The new standard for electrical protective equipment, which matches the corresponding general industry standard, applies to all construction work and replaces the incorporation of out-of-date consensus standards with a set of performance-oriented requirements that is consistent with the latest revisions of the relevant consensus standards. The final construction rule also includes new requirements for the safe use and care of electrical protective equipment to complement the equipment design provisions. Both the general industry and construction standards for electrical protective equipment will include new requirements for equipment made of materials other than rubber. OSHA is also revising the general industry standard for foot protection. This standard applies to employers performing work on electric power generation, transmission, and distribution installations, as well as employers in other industries. The final rule removes the requirement for employees to wear protective footwear as protection against electric shock.

RIN 1218-AB67 · Docket OSHA-S215-2006-0063

Other documents for the same rulemaking

1986-05-31 Regulatory impact analysisSupporting Exhibit 7-3; PREPARATION OF AN ECONOMIC IMPACT STUDY FOR THE PROPOSED OSHA REGULATION COVERING ELECTRIC POWER GENERATION, TRANSMISSION, AND DISTRIBUTION. TASK ORDER NO. 1 CONTRACT NO. J-9-F-5-0057.
1987-10-23 Regulatory impact analysisSupporting Exhibit 2; OFFICE OF REGULATORY ANALYSIS, OSHA
1990-06-12 Regulatory impact analysisSupporting Exhibit 32; Regulatory Impact and Regulatory Flexibility Analysis of the Electrical Safety-Related Work Practices Standard for General Industry (29 CFR 1910, Subpart S)
2003-02-14 Regulatory impact analysisSupporting Exhibit 2-4; A BRIEF SUMMARY OF OSHAS PRELIMINARY ESTIMATES OF THE ECONOMIC IMPACTS, COSTS, AND BENEFITS OF THE PROPOSED RULE AS A WHOLE. CONTRACT NO. J-9-F-9-0013. TASK ORDER NUMBER 29. OPTION YEAR 3.
2003-02-14 Regulatory impact analysisSupporting Exhibit 3; FINAL REPORT. ANAYTICAL SUPPORT AND DATA GATHERING FOR A PRELIMINARY ECONOMIC ANALYSIS FOR A PROPOSED STANDARD FOR WORK ON ELEC POWER TRANSMISSION AND DISTRIBUTION LINES AND EQUIP (29 CFR 1910.269 AND 29 CFR 1926 - SUBPART V). CONTRACT NO. J-9-F-9-0013
2003-04-07 Regulatory impact analysisSupporting Exhibit 2-3; DRAFT COPY OF OSHAS PRELIMINARY INITIAL REGULATORY FLEXIBILITY ANALYSIS, WHICH INCLUDES THE AGENCYS ANALYSIS OF SOME ALTERNATIVES TO THE PROPOSED RULE.
2005-06-08 Regulatory impact analysisSupporting Exhibit 7-1; REVISED FINAL REPORT - ANALYTICAL SUPPORT AND DATA GATHERING FRO A PRELIMINARY ECONOMIC ANALYSIS FOR PROPOSED STANDARDS FOR WORK ON ELECTRIC POWER GENERATION, TRANSMISSION, AND DISTRIBUTION LINES AND EQUIPMENT (29 CFR 1910.269 AND 29 CFR 1926-SUBPART V)
2005-06-15 Federal RegisterElectric Power Generation, Transmission, and Distribution; Electrical Protective Equipment
2005-10-12 Federal RegisterElectric Power Generation, Transmission, and Distribution; Electrical Protective Equipment; Extension of Comment Period; Change in Date of Public Hearing
2008-10-22 Federal RegisterElectric Power Generation, Transmission, and Distribution; Electrical Protective Equipment; Limited Reopening of Record
2009-09-14 Federal RegisterElectric Power Generation, Transmission, and Distribution; Electrical Protective Equipment; Limited Reopening of Record; Notice of Informal Public Hearing
2014-04-01 Docket documentOffice of Management and Budget. 2003. Circular A-4
2014-09-24 Federal RegisterElectric Power Generation, Transmission, and Distribution; Electrical Protective Equipment; Corrections
2015-10-05 Federal RegisterElectrical Safety-Related Work Practices; Electric Power Generation, Transmission, and Distribution; Electrical Protective Equipment; Corrections

References: 94 extracted, 28 linked to papers

Page 1Download these results: CSV · JSON
Hearon, B.F., Brinkley, J.W., "Fall Arrest and Post-Fall Suspension: Literature Review and Directions for Further Research," AFAMRL-TR-84-021, April 1984.
0088).\115\ That same study showed that subjects suspended in full body harnesses could tolerate suspension for approximately 20 to 30 minutes (id.). --------------------------------------------------------------------------- ---------------------------------------------------------------------------
ASTM F887-04, Standard Specifications for Personal Climbing Equipment
otherNot linked to a paper · Paragraph (b)(2) discussion, Standard Specifications for Personal Climbing Equipment
IEEE Std 1307-2004, Standard for Fall Protection for Utility Work
otherNot linked to a paper · Section on fall protection starting height (Southern Company recommendation)
IEEE Std 516-2003, IEEE Guide for Maintenance Methods on Energized Power Lines
otherNot linked to a paper · Section 1926.957 live-line tools
ASTM F711-02 (2007), Standard Specification for Fiberglass-Reinforced Plastic (FRP) Rod and Tube Used in Live-Line Tools
otherNot linked to a paper · Section 1926.957 live-line tools
ANSI A14.3-2002, American National Standard for Ladders—Fixed—Safety Requirements
otherNot linked to a paper · Section 1926.955 fixed ladders
Worker Deaths by Electrocution: A Summary of NIOSH Surveillance and Investigative Findings, Publication No. 98-131
government reportNot linked to a paper · Discussion of grounding and minimum resistance of employee (fn none; section on mechanical equipment, paragraph (d)(3)(iii))
Vaisman, R., Fonseca, J. R., Andrade, V. H. G., Almeida, M. A., Hattori, H. K., Melo, M. O. B. C., Teivelis, F., Fernandes, J. H. M., Silva, J. T. S., Dias, L. E. N., Esmeraldo, P. C. V., and Samico, R. A. M., "Switching Impulse Strength of Compact Transmission Lines," IEEE Transactions on Power Delivery, Vol. 8, No. 3, July 1993 (Ex. 0555).
0545.1, 0551.1.) American Electric Power argued against adopting minimum approach distances different from the minimum approach differences in OSHA's proposal, relying on calculations they made that were taken from a paper by Vaisman et al.\184\ (Ex.
IEEE Std 516-2009
otherNot linked to a paper · Minimum Approach Distances section
IEEE Paper 91 SM 312-9 PWRD "Test Results of Grounding Un-insulated Aerial Lift Vehicles Near Energized Distribution Lines"
journal articleNot linked to a paper · Mechanical equipment, paragraph (d)(3)(iii) discussion
Assessment of the Benefits of the Proposed Standard on Electric Power Generation, Transmission, and Distribution; Coding Results and Analysis (Ex. 0081)
research reportNot linked to a paper · fn 172
IEC Standard 61472
otherNot linked to a paper · Maximum transient overvoltage discussion
Bonneville Power Administration report on overvoltage testing, Big Eddy-Chemewa 230-kV line (Ex. 0575.1)
research reportNot linked to a paper · Maximum transient overvoltages discussion
Ex. 0175 (Contracts between electric utilities and their contractors) — not a work
otherNot linked to a paper · fn 73
Jones, R. A., Liggett, D. P., Capelli-Schellpfeffer, M., Macalady, T., Saunders, L. F., Downey, R. E., McClung, L. B., Smith, A., Jamil, S., Saporita, V. J., “Staged Tests Increase Awareness of Arc-Flash Hazards in Electrical Equipment,” IEEE Transactions on Industry Applications Society, 36(2): 659-667, March-April 2000.
\289\ described the results of one arcing-fault test as follows: ``the fault blew the door open and progressed up the vertical bus, completely destroying the vertical section of the [motor control center]'' (id.).
Land III, H. B., “The Behavior of Arcing Faults in Low Voltage Switchboards,” 2005 IEEE ESTS, Philadelphia, pp. 133-140, 2005.
A paper by Land \290\ described problems the Navy had in 1979 with arcing faults in switchboards: ``These arcs could completely destroy a switchboard within a matter of seconds'' (id.).
Lee, R. H., “The Other Electrical Hazard: Electric Arc Blast Burns, ” IEEE Transactions on Industry Applications, 1A-18(3):246—251, May/June 1982 (Ex. 0433).
It should be noted that NFPA 70E-2004 Annex D contains three different methods of estimating incident heat energy: (1) a method based on a paper by Lee entitled ``The Other Electrical Hazard: Electric Arc Blast Burns,'' \296\ also known as the ``Lee equation''; (2) a method based on the Doughty, Neal, and Floyd paper, which Table 10 lists separately; and (3) the IEEE 1584 method, which Table 10 also lists separately.\297\ The following discussion refers to the method based on the Lee equation as the NFPA 70E Annex D method.\298\ ---------------------------------------------------------------------------
Doughty, T. E., Neal, T. E., and Floyd II, H. L., “Predicting Incident Energy to Better Manage the Electric Arc Hazard on 600 V Power Distribution Systems,” Record of Conference Papers IEEE IAS 45th Annual Petroleum and Chemical Industry Conference, September 28-30, 1998.
Guide for Performing Arc Flash Hazard Calculations, IEEE Std 1584-2002.
otherNot linked to a paper · Table 10
Stokes, A. D., Sweeting, D. K., “Electric Arcing Burn Hazards,” IEEE Transactions on Industry Applications. Vol. 42. No. 1, January/February 2006, pp. 134-141.
journal articleElectric arcing burn hazards (2004) · fn 309
0452).\309\ That paper notes that the NFPA and IEEE methods use a predominantly radiant model of incident heat energy from an electric arc, in which 90 percent of the heat is radiant heat and in which the entire exposure will be outside the electric arc plasma.
IEEE Std 1584a-2004 (Amendment 1 to IEEE Std 1584-2002)
otherNot linked to a paper · fn 307
Ashford, N.A., 2007. “Workers' Compensation,” in Environmental and Occupational Medicine, Fourth Edition, W.N. Rom & S. Markowitz (Eds.), Lippincott-Raven Publishers, Philadelphia, pp. 1712-1719.
book chapterNot linked to a paper · References, ref. 3
Leigh, J.P., and Marcin, J.P. 2012. “Workers' compensation benefits and shifting costs for occupational injury and illness,” Journal of Occupational and Environmental Medicine, April, 54(4): 445-450.
Magat, W.A, Viscusi, W.K, and Huber, J, 1996. “A Reference Lottery Metric for Valuing Health.” Management Science 42: 1118-1130.
journal articleA Reference Lottery Metric for Valuing Health (1996) · References, ref. 22
National Academy of Social Insurance. 2012. “Workers' Compensation: Benefits, Coverage, and Costs, 2010,” August.
research reportNot linked to a paper · References, ref. 23 · cited link
Neuhauser, F.W., Seabury, S.S., and Mendeloff, J. 2013. “The Impact of Experience Rating on Small Employers: Would Lowering the Threshold for Experience Rating Improve Safety?” Rand Working Papers WR-955.
working paperNot linked to a paper · References, ref. 27 · cited link
Viscusi, W.K., and Aldy, J.E. 2003. “The Value of a Statistical Life: A Critical Review of Market Estimates Throughout the World.” Journal of Risk and Uncertainty, 27(1): 5-76.
Occupational Safety and Health Administration Small Business Advocacy Review Panel. 2003. “Report of the Small Business Advocacy Review Panel on the Draft OSHA Standard for Electric Power Generation, Transmission, and Distribution,” June 17, 2003. Ex. 0019.
government reportNot linked to a paper · References, ref. 29
Urban Institute/Brookings, 2012. “Historical Average Federal Tax Rates for All Households,” Tax Policy Center, October.
datasetNot linked to a paper · References, ref. 52 · cited link
NFPA 70E-2004, Section 110.1, which sets the scope for Article 110, General Requirements for Electrical Safety-Related Work Practices (Ex. 0134).
otherNot linked to a paper · fn 41
ANSI Z133.1-1982[, American National Standard for Tree Care Operations—Pruning, Trimming, Repairing, Maintaining, and Removing Trees, and Cutting Brush—Safety Requirements ]
otherNot linked to a paper · fn 48
Training Requirements in OSHA Standards and Training Guidelines
otherNot linked to a paper · fn 55 · cited link
Leigh and Marcin estimate that the average indemnity benefits for a fatality are $225,919 [21]
otherNot linked to a paper · fn 482
Viscusi and Aldy [53]
otherNot linked to a paper · Wage premiums / Valuation of fatalities section
CONSAD [5]
research reportNot linked to a paper · Profile of Affected Industries
U.S. Census' County Business Patterns data [47]
datasetNot linked to a paper · Profile of Affected Industries
Energy Information Administration (EIA)'s Form EIA-860 Database Annual Electric Generator Report [49]
datasetNot linked to a paper · Profile of Affected Industries
EIA's Form-861 Annual Electric Power Industry Report [50]
datasetNot linked to a paper · Profile of Affected Industries
BLS Occupational Employment Statistics data [34]
datasetNot linked to a paper · Profile of Affected Industries
Census of Fatal Occupational Injuries (CFOI) developed by the Bureau of Labor Statistics
datasetNot linked to a paper · Benefits, Net Benefits, and Cost Effectiveness
Statistics of U.S. Businesses [43]
datasetNot linked to a paper · Profile of Affected Industries
Viscusi and Aldy conducted a metaanalysis of studies in the economics literature
National Safety Council's (NSC) valuation of $1 million per fatality [26]
web pageNot linked to a paper · Benefits, Net Benefits, and Cost Effectiveness
a study of burn injuries (Ex. 0424)
journal articleNot linked to a paper · fn 498
Office of Regulatory Analysis, OSHA. See text.
government reportNot linked to a paper · Costs of Compliance
Doughty, T.E., Neal, T.E., and Floyd II, H.L., "Predicting Incident Energy to Better Manage the Electric Arc Hazard on 600 V Power Distribution Systems," Record of Conference Papers IEEE IAS 45th Annual Petroleum and Chemical Industry Conference, September 28-30, 1998.
Stoll, A. M., and Chianta, M. A., "Method and Rating System for Evaluations of Thermal Protection," Aerospace Medicine, Vol 40, 1969, pp. 1232-1238
Stoll, A. M., and Chianta, M. A., "Heat Transfer through Fabrics as Related to Thermal Injury," Transactions—New York Academy of Sciences, Vol 33(7), Nov. 1971, pp. 649-670.
IEEE Std 516-2009, IEEE Guide for Maintenance Methods on Energized Power Lines
IEEE Std 4-1995, Standard Techniques for High-Voltage Testing
Next →