Policy Replication

Technologies and Costs Document for the Final Long Term 2 Enhanced Surface Water Treatment Rule and Final Stage 2 Disinfectants and Disinfection Byproducts Rule [EPA 815-R-05-013]

Docket document2006-01-04 · EPA · publication · EPA-HQ-OW-2002-0043-0733
RIN 2040-AD37, RIN 2040-AD38, RIN 2040-AD93 · Docket EPA-HQ-OW-2002-0043

Other documents for the same rulemaking

2003-07-09 Docket documentApplication for the Laboratory Quality Assurance Evaluation Program for Analysis of Cryptosporidium under the Safe Drinking Water Act. Microbial Laboratory Guidance Manual for the Long Term 2 Enhanced Surface Water Treatment Rule (LT2 Rule). June 2003
2003-07-09 Docket documentChecklist for the Laboratory Quality Assurance Evaluation Program for Analysis of Cryptosporidium under the Safe Drinking Water Act. Microbial Laboratory Guidance Manual for the Long Term 2 Enhanced Surface Water Treatment Rule (LT2 Rule). June 2003 Draft
2003-07-09 Docket documentAppendix D - EXAMPLE PROCEDURE FOR COLLECTING BULK WATER SAMPLES FOR LABORATORY FILTRA-TION AND CRYPTOSPORIDIUM ANALYSIS. Source Water Monitoring Guidance Manual for Public Water Systems for the Long Term 2 Enhanced Surface Water Treatment Rule (LT2 Rule)
2003-07-09 Docket documentAppendix E - Example Procedure for Field-Filtering Samples for Cryptosporidium Analysis Using the Pall Life Sciences ENVIROCHEK OR ENVIROCHEK HV Filter.
2003-07-09 Docket documentAppendix F - Example Procedure for Field-Filtering Samples for Cryptosporidium Analysis Using IDEXX Filta-Max Filters. Source Water Monitoring Guidance Manual for Public Water Systems for the Long Term 2 Enhanced Surface Water Treatment Rule (LT2 Rule).
2003-07-09 Docket documentUltraviolet Disinfection Guidance Manual. Part 5 of 6.
2003-07-09 Docket documentUltraviolet Disinfection Guidance Manual. Part 6 of 6.
2003-07-09 Docket documentUltraviolet Disinfection Guidance Manual. Part 2 of 6.
2003-07-09 Docket documentUltraviolet Disinfection Guidance Manual. Part 1 of 6.
2003-07-09 Docket documentUltraviolet Disinfection Guidance Manual. Part 3 of 6.
2003-07-09 Docket documentUltraviolet Disinfection Guidance Manual. Part 4 of 6.
2003-07-15 Docket documentReverse Osmosis Water Purification Unit: Efficacy of Cartridge Filters for Removal of Bacteria and Protozoan Cysts when RO Elements are Bypassed.
2003-07-15 Docket documentCryptosporidium: Risk for Infants and Children.
2003-07-15 Docket documentU.S. EPA Water Supply Performance Evaluation Study #41 Low-Level Turbidity.
2003-07-15 Docket documentFinal Draft: Technologies and Costs for the Microbial Recommendationa of the M/DBP Advisory Committee, October 10, 1997.
2003-07-15 Docket documentFinal Report of the Small Business Advocacy Review Panel on Stage 2 Disinfectants and Disinfection Byproducts Rule (Stage 2 DBPR) and Long-Term 2 Enhanced Surface Water Treatment Rule (LT2ESWTR).
2003-07-15 Docket documentDesign, Implementation, and Results fo USEPA's 70-Utility ICR Laboratory Spiking Program.
2003-07-18 Docket documentBromate in Commercial Bleach Products (The Chlorine Institute)
2003-07-18 Docket documentThe Ground Water Supply Survey, Summary of Volatile Organic Contaminant Occurrence Data, January 1983.
2003-07-18 Docket documentBromate MCL Impacts on Ozone Feasibility. Technical Work Group Approach and Preliminary Results
2003-07-18 Docket documentCalifornia Drinking Water: NDMA-Related Activities (California Dept. of Health Services)
2003-07-21 Docket documentGuidelines for Carcinogen Risk Assessment, NCEA-F-0644, July 1999 Review Draft.
2003-07-23 Docket documentOMB 83-I form for ICR No. 2097.01- New Collection
2003-08-05 Regulatory impact analysisEconomic Analysis for the Long Term 2 Enhanced Surface Water Treatment Rule Proposal. File 2 of 5.
2003-08-05 Regulatory impact analysisAppendices to the Economic Analysis for the Long Term 2 Enhanced Surface Water Treatment Rule Proposal. File 4 of 5.
2003-08-05 Regulatory impact analysisEconomic Analysis for the Long Term 2 Enhanced Surface Water Treatment Rule Proposal. File 3 of 5.
2003-08-05 Regulatory impact analysisEconomic Analysis for the Long Term 2 Enhanced Surface Water Treatment Rule Proposal. File 1 of 5.
2003-08-11 Regulatory impact analysisEconomic Analysis for the Proposed Stage 2 DBPR. (Chapters)
2003-08-11 Regulatory impact analysisEconomic Analysis for the Proposed Stage 2 DBPR. (Appendices H-M)
2003-08-11 Regulatory impact analysisEconomic Analysis for the Proposed Stage 2 DBPR. (Appendices A-G)
2003-08-11 Federal RegisterNational Primary Drinking Water Regulations: Long Term 2 Enhanced Surface Water Treatment Rule
2003-08-11 Docket documentGuidelines for Carcinogen Risk Assessment, Published on September 24, 1986, Federal Register 51 (185) : 33992-34003.
2003-08-11 Docket documentMinutes of the Chloroform Risk Assessment Review Subcommittee Meeting, October 27-28, 1999.
2003-08-11 Docket documentStage 2 Occurrence and Exposure Assessment for Disinfectants and Disinfection Byproducts. Proposal Draft.
2003-08-11 Docket documentGuidelines for Development Toxicity Risk Assessment, Published on December 5, 1991, Federal Register 56(234): 63798-63826.
2003-08-11 Docket documentEstimated Per Capita Water Ingestion in the United States, Based on Data Collected by the United States Department of Agriculture's 1994-96 Continuing Survey of Food Intakes by Individuals.
2003-08-18 Docket documentChemical Name - Microsoft Excel Spreadsheet.
2003-08-18 Federal RegisterNational Primary Drinking Water Regulations: Stage 2 Disinfectants and Disinfection Byproducts Rule; National Primary and Secondary Drinking Water Regulations: Approval of Analytical Methods for Chemical Contaminants
2003-09-22 Federal RegisterStakeholder Meetings Concerning the Long-Term 2 Enhanced Surface Water Treatment Rule and Stage 2 Disinfectants and Disinfection Byproducts Rule Proposals; Notice of Public Meetings
2003-10-08 Federal RegisterNational Primary Drinking Water Regulations: Long Term 2 Enhanced Surface Water Treatment Rule; Extension of Comment Period
2003-10-08 Federal RegisterNational Primary Drinking Water Regulations: Stage 2 Disinfectants and Disinfection Byproducts Rule; National Primary and Secondary Drinking Water Regulations: Approval of Analytical Methods for Chemical Contaminants; Extension of Comment Period
2004-12-07 Docket documentToxicological Profile for N-Nitrosodimethylamine
2004-12-07 Docket documentToxicological Profile for 1,3-Dinitrobenzene
2004-12-28 Docket documentDraft Toxicological Profile for Polybrominated Biphenyls and Polybrominated Diphenyl Ethers
2004-12-28 Docket documentPublic Health Protection Threatened by Inadequate Resourses for State Drinking Water Programs: An Analysis of State Drinking Water Programs Resources, Needs, and Barriers
2004-12-28 Docket documentDraft Groundwater Information Sheet: N-Nitrosodimethylamine (NDMA)
2004-12-28 Docket documentMethod 521: Determination of Nitrosoamines in Drinking Water by Solid Phase Extraction and Capillary Column Chromatography with Large Volume Injection and Chemical Ionization Tandum Mass Spectrometery (MS/MS) Version 1.0 EPA/600/R-05/054
2004-12-28 Docket documentMethod 535: Measurement of Chloroacetanilide and Other Acetamide Herbicide Degradates in Drinking Water by Solid Phase Extraction and Liquid Chromatography/Tandem Mass Spectrometery (LC/MS/MS) Version 1.0 EPA/600/R-05/053
2004-12-28 Docket documentToxilogical Profile for RDX
2004-12-28 Docket documentToxicological Profile for 2,4,6-Trinitrotoluene
2004-12-30 Docket documentMethod 314.0: Determination of Perchlorate in Drinking Water Using Ion Chromatography, Revision 1.0
2005-01-01 Regulatory impact analysisEconomic Analysis for the Final Long Term 2 Enhanced Surface Water Treatment Rule
2005-01-01 Regulatory impact analysisAppendices to the Economic Analysis for the Final Long Term 2 Enhanced Surface Water Treatment Rule Volume II (H - U)
2005-01-01 Regulatory impact analysisAppendices to the Economic Analysis for the Final Long Term 2 Enhanced Surface Water Treatment Rule Volume I (A -G)
2005-01-01 Regulatory impact analysisEconomic Analysis for the Final Stage 2 Disinfectants and Disinfection Byproducts Rule
2005-01-04 Docket documentScience Policy Council Handbook, Peer Review [EPA 100-B-00-001]
2005-04-14 Docket documentStatistical Design and Sample Selection for the Unregulated Contaminant Monitoring Regulation (1999) UCMR
2005-04-14 Docket document2002 Edition of the Drinking Water Standards and Health Advisories
2005-04-26 Docket documentEstimating Potency Scores: An Exercise
2005-04-26 Docket document2004 Edition of the Drinking Water Standards and Health Advisories

References

Page 1Download these results: CSV · JSON
GAC if used as a filter cap is not likely to result in additional removal over what would be expected from conventional treatment. If it is used as a secondary filter in series with conventional filtration, additional removal can be obtained. The efficacy of secondary filters in removing pathogens is discussed in full in Section 2.2.8.1. 2.3.1.2 DBP Precursor Removal In many circumstances, GAC is an effective process for the removal of NOM from drinking water sources. The removal will depend on a number of factors which are more fully discussed in the following section. It is important to note that, GAC will reduce TOC levels but may not significantly lower bromide. This can cause the bromide-to-TOC ratio to increase and can cause a net shift in speciation of DBPs to the more brominated compounds. The bromide-to-TOC ratio will continually change through the adsorption process, so the concentration of brominated DBPs may spike and then fall. LT2ESWTR T&C Document 2-35 December 2005 2.3.1.3 Factors Affecting Performance The removal of NOM by GAC adsorption depends on a large number of factors including the following: Molecular size, polarity, and concentration of NOM entering the GAC process Water quality characteristics such as pH and ionic strength
research reportNot linked to a paper · refsec
GAC characteristics such as pore size distribution and surface chemistry Operational characteristics such as EBCT and GAC usage rate Treatment processes used prior to the GAC process Configuration of GAC contactors This section briefly describes the impacts of these factors as seen in several GAC studies. Constituents of NOM are adsorbed within the GAC bed in a manner proportional to their adsorption potential. Weakly adsorbing components of NOM may irreversibly preload the GAC at the downstream end of the bed and may, therefore, reduce the capacity of the bed for stronger adsorbing components at the end of the bed. The impacts of pH on adsorption of NOM and humic extracts have been well documented in equilibrium studies using powdered activated carbon (Weber et al. 1983, Randtke and Jepsen 1982, McCreary and Snoeyink 1980, Summers 1986). All of these studies showed increased removal of TOC with decreased pH levels. Unfortunately, some of the work has been done with different initial TOC concentrations, and the increased performance attributed to low pH may be because of the lower initial
research reportNot linked to a paper · refsec
EBCT is increased from 2.8 to 15.2 minutes. Summers et al. (1997) evaluated EBCTs of 10 and 20 minutes for a number of water sources and concluded that EBCT had a definite effect in prolonging the bed life of a GAC contactor. However, the carbon usage rate is relatively unaffected by EBCTs at the ranges evaluated. They also noted that the balance between EBCT and the frequency of GAC replacement or reactivation is primarily a choice between larger capital investment (i.e., longer EBCTs) LT2ESWTR T&C Document 2-36 December 2005 and greater operational complexities (i.e., more frequent reactivation). Another study indicated that GAC usage rate decreased with an increase in EBCT from 7.5 to 30 minutes. However, a further increase in
research reportNot linked to a paper · refsec
EBCT from 30 to 60 minutes did not influence the GAC usage rate (McGuire et al. 1989).
research reportNot linked to a paper · refsec
GAC systems may require some kind of pretreatment to prevent build-up of solids in the GAC bed, to minimize the organic loading on the GAC, and to improve cost effectiveness. Build-up of solids, which can cause poor filter performance, could be caused by suspended solids in the raw water or by precipitation of calcium carbonate, iron, and manganese on the GAC. Suspended solids typically cause problems in surface water systems, while carbonate scaling, iron, and manganese precipitation may occur in both surface and ground waters. When the GAC bed life is long, clogging may also be caused by biological growths. Pretreatment methods include coagulation, filtration, or softening ahead of the GAC system. Conventional coagulation, clarification, and filtration processes may be optimized for the removal of organic material to reduce natural organic loading to the GAC bed. The impacts of coagulation on NOM adsorption have also been well documented in batch experiments studying adsorption equilibria (Weber et al. 1983, Randtke and Jepsen 1981, Lee et al. 1981, El-Rehaili and Weber 1987, Harrington and DiGiano 1989). Coagulation processes, as a pretreatment to
research reportNot linked to a paper · refsec
Giardia, Cryptosporidium, and viruses. Historically, NF processes have not been used as a primary means of disinfection, since, in large part, they have been used to treat ground water or have been coupled with pretreatment processes such as MF or UF. When only disinfection is required, MF and UF processes are typically used instead of NF, since they are less costly and can achieve the required level of pathogenic rejection (Mallevialle et al. 1996). Because of this, relatively few studies documenting microbial removal with NF membranes have been conducted in comparison to MF and UF processes. Because NF and RO processes represent systems that are very similar in terms of disinfection capabilities, available studies documenting microbial removal with RO as well as NF membranes are presented in Exhibit 2.17. LT2ESWTR T&C Document 2-38 December 2005 Exhibit 2.17: NF Studies Documenting Microbial Removal Giardia Log Removal Crypto Log Removal MS2 Virus Log Removal Gagliardo et al. (1999)
research reportNot linked to a paper · refsec
ESPA Gagliardo et al. (1998) Acumem4040 FilmTec BW30 FilmTec BW30 4.2 to 5.0 4.1 to 5.9 3.7 to 5.7 2.1 to 3.3 2.9 to 4.3 Reference Process Gagliardo et al. (1999) Gagliardo et al. (1999) Seyde et al. (1999) Colvin et al. (1999) Colvin et al. (1999) Trussel et al. (1998) Trussel et al. (1998) (Pilot) (bench) (bench) pretreat) pretreat) Membrane FilmTec BW30 Hydranautics 4040 Fluid Systems
research reportNot linked to a paper · refsec
TFLC/M48 20HR Fluid Systems TFCL/ULP Trussel et al. (1998) pretreat) Trussel et al. (1998) pretreat) Gagliardo et al. (1997)
research reportNot linked to a paper · refsec
RO (pilot) TFC >5.7 >5.7 3.0 to 4.0 Gagliardo et al. (1997)
government reportNot linked to a paper · refsec
UV-254 absorbance, microorganisms, and particle counts (Spangenberg et al. 1999). Vacuum testing entails taking the membrane off-line. This has the disadvantage of being unable to provide on-line integrity monitoring. Should a system become compromised, it would not be realized until the module is taken off-line and tested. Effluent water quality monitoring does provide real-time results. However, the parameters being monitored must be sensitive enough to provide an alert if the system is compromised. Sensitivity of various parameters will depend on the influent level of that particular parameter along with the amount of removal accomplished by the membrane. The parameter acting as a surrogate for membrane integrity must be removed to a significant degree such that a noticeable increase in effluent concentration would be seen if the membrane system were compromised. LT2ESWTR T&C Document 2-39 December 2005
research reportNot linked to a paper · refsec
NF processes are also capable of reducing biodegradable organic carbon (BDOC) (Escobar and Randall 1999). Since BDOC serves as substrate for microorganisms in the distribution system, reducing
research reportNot linked to a paper · refsec
BDOC can reduce the potential for regrowth in a distribution system, disinfectant doses, and DBPs. A recent full-scale study was performed to document the microbiological and disinfection benefits derived from implementing NF where conventional treatment had previously been practiced (Laurent et al. 1999). The results of this study showed significant decreases in chlorine residual fluctuations, microbiological counts, DOC, and BDOC in treated water and in the distribution system. In effect, this created greater water quality stability in all areas of the distribution system, particularly in areas with high residence times. In addition, the finished water chlorine dose required was lowered from about 1 mg/L to 0.2 mg/L by the use of NF. 2.3.2.2 DBP Precursor Removal Membrane processes can remove DBP precursors through filtration and adsorption of organics. Membranes remove NOM through filtration (i.e., sieving) when NOM molecules are larger than a given membrane pore size, causing them to be rejected. Size, however, is only one factor that influences NOM rejection. Shape of the NOM molecules and membrane pores, along with chemical characteristics of the
research reportNot linked to a paper · refsec
NOM molecules and membrane also play important roles in the permeation of NOM across a membrane (Mallevialle et al. 1996). Membranes may also remove NOM through adsorption of organics directly on the membrane surface. The level of adsorption to the membrane surface depends on the chemical characteristics, particularly charge and hydrophobicity, of both the membrane material and the NOM.
research reportNot linked to a paper · refsec
Unfortunately, organic adsorption is generally undesirable since it has proven to be a primary cause of irreversible fouling of membranes, thereby shortening membrane life. Without pretreatment, NF processes remove NOM to varying degrees. NOM removals for NF and RO processes are typically on the order of 50 to 99 percent. NOM removal depends on many factors, including membrane MWCO and hydrophobicity, characteristics of the NOM, and membrane system operating parameters such as recovery and operating pressure. Results from several studies on NOM removal by NF processes are provided in Exhibit 2.18. LT2ESWTR T&C Document 2-40 December 2005 Exhibit 2.18: NOM Removal Through NF Processes Reference Design Criteria Conclusions of Study Taylor et al. (1987 and 1989) Operating pressure: 98-141 Flux: 8.9-16.4 gpd/sf Recovery: 50-79%
research reportNot linked to a paper · refsec
NOM removal. TDS1 and hardness rejection are increased by increased operating pressure. Conlon and McClellan (1989) Operating pressure: 90-100 Recovery: 75%
research reportNot linked to a paper · refsec
NOM removal greater than 90% for 200 MWCO. Allgeier and Summers (1995) Operating pressure: 95 psi Flux: 15-24 gpd/sf Recovery: 30-87% 66-94% TOC removal for 200 MWCO.
research reportNot linked to a paper · refsec
TOC removal decreased by up to 15% as recovery approached 90%. Lozier et al. (1997) Operating pressure: 70 psi Flux: 10 gpd/sf Recovery: 85% 69-98% TOC removal using MF pre-treated water. Chellam et al. (1997) Operating pressure: 70 psi Flux: 10 gpd/sf Recovery: 85% 90-95% TOC removal with 200 MWCO on MF and UF pretreated water. 95-99% SDS THM precursor removal. 96-99% SDS HAA6 precursor removal. Mulford et al. (1999) Operating pressure: 100 psi Flux: 15 gpd/sf Recovery: 82% 96% DOC removal with 200 MWCO. Fu et al. (1995) Operating pressure: 80 psi Flux: 15-20 gpd/sf Recovery: 75-90% 85-97% TOC removal with 100 to 500 MWCO. Yoon et al. (1999) Not reported 60-90% TOC removal with 200 to 8,000 MWCO. Slightly higher NOM removal is achieved at pilotscale than at bench-scale. Legube et al. (1995) Not reported 79-91% DOC removal. 91-95% TOXFP reduction. 93-94% THMFP reduction.
research reportNot linked to a paper · refsec
DBPs, so its removal can be beneficial. NF membranes are capable of significant bromide removal. Several studies documenting the use of NF processes for bromide removal are summarized in Exhibit 2.19. LT2ESWTR T&C Document 2-41 December 2005 Exhibit 2.19: Bromide Removal Through NF Processes Reference Conclusions of Study Amy and Siddiqui (1999) 38-41% bromide removal with 150 to 300
research reportNot linked to a paper · refsec
MWCO. Mulford et al. (1999) 50-63% bromide removal with 200 MWCO. Allgeier and Summers (1995) 40-61% bromide removal with 200 MWCO. Fu et al. (1995) 24-38% bromide removal with 100 to 500
research reportNot linked to a paper · refsec
MWCO. Prados-Ramirez et al. (1993) 63% bromide removal. Conlon and McClellan; Taylor et al. (1989) 60-70% chloride removal, with bromide removal expected to be nearly identical. As shown by the data in Exhibit 2.19, NF is capable of high percentage bromide removal.
research reportNot linked to a paper · refsec
Overall, however, bromide removal using NF would probably not be cost effective if used only for that purpose. If the process were incorporated into a treatment train and used for other contaminant removal, membrane removal of bromide may become cost effective (Amy and Siddiqui 1999). It is important to note that, if bromide is not removed sufficiently but TOC levels are reduced, the bromide-to-TOC ratio will increase considerably and will cause a net shift in speciation of DBPs to the more brominated compounds. In the worst case, such a scenario could cause a net increase in the absolute level of brominated DBPs (i.e., bromoform) after chlorination (Amy and Siddiqui 1999). 2.3.2.3 Factors Affecting Performance
research reportNot linked to a paper · refsec
NF is gaining popularity as a DBP precursor removal process, since production costs are comparable with competing processes (Mallevialle et al.1996). Due to the small pore size associated with
research reportNot linked to a paper · refsec
MWCO membranes (i.e., MWCO near and above 10,000), however, will not be as effective for NOM reduction. Commercial NF (as well as MF and UF) membranes are available in many types of material (e.g., cellulose acetate and polysulphone) and in various configurations (e.g., spiral wound and hollow fiber). The chemistry of the membrane material, particularly surface charge and hydrophobicity, can play an important role in rejection properties, since membranes can remove contaminants through adsorption on the membrane surface as well as through sieving across the membrane pores. These factors must be taken into consideration to accommodate source water characteristics and removal requirements. LT2ESWTR T&C Document 2-42 December 2005 Source water quality can also dictate pretreatment requirements. The small pore size of NF and
research reportNot linked to a paper · refsec
BLS numerical values were re-based to 1967 base year.
government reportNot linked to a paper · refsec
ENR BCI value for other years are available at www.enr.com Energy and labor are required to operate most technologies. Exhibit 4.4 displays costs used for energy and labor in this document. Chemicals are also required for some technologies. Exhibit 4.5 displays costs for chemicals required to operate the technologies costed in this document. LT2ESWTR T&C Document December 2005 Exhibit 4.4: Unit and General Cost Assumptions Unit Cost* $0.076/kWh Electricity Diesel Fuel1 $1.48/gallon Natural Gas $0.009/scf Building Energy Use 102.6 kWh/ft2/yr Note - variable labor rates are used, based on the system size
research reportNot linked to a paper · refsec
Energy Information Administration, 2003. EPA is aware that DOE has updated its 2003 average national cost of electricity per kilowatt hour per year from $0.076kWhr/yr to $0.074kWhr/yr. However, EPA continues to use the $0.076kWhr/yr value in order to maintain consistency with Stage 2 DBPR and LT2ESWTR analyses. Includes public street and highway lighting, other sales to public authorities, sales to railroads and railways, sales for irrigation, and interdepartmental sales. * Where kWh = kilowatt hour; scf = standard cubic feet; hr = hour; ft = feet; and yr = year. Exhibit 4.5: Chemical Costs Chemical Cost Units
research reportNot linked to a paper · refsec
Aboytes, Ramon; Di Giovanni, George D.; Abrams, Felicia A.; Rheinecker, Corey; McElroy, Wyndi;Shaw, Nancy; LeChevallier, Mark W. 2004. “Detection of Infectious Cryptosporidium in Filtered Drinking Water” J. AWWA, 95:9:88-98
journal articleNot linked to a paper · refsec
Adham, Samer S., Snoeyink, V. J., Clark, M. M. and C. Anselme. 1993. “Predicting and Verifying Organics Removal by PAC in Pilot-scale UF Systems.” J. AWWA, 85:12:58.
research reportNot linked to a paper · refsec
Adham, Samer S., Snoeyink, V. J., Clark, M. M. and Bersillon, Jean-Luc. 1991. “Predicting and Verifying Organics Removal by PAC in an Ultrafiltration System.” J. AWWA, 83:12:81.
research reportNot linked to a paper · refsec
Allgeier, S.A. and R.S. Summers. 1995. "Evaluating Nanofiltration for DBP Control with the RBSMT," J. AWWA, 86:3:87-99.
journal articleNot linked to a paper · refsec
Amy, G.L. and M.S. Siddiqui. 1999. Strategies to Control Bromate and Bromide. Report No. 90751,
research reportNot linked to a paper · refsec
AWWARF, Denver, CO. Anselme, C. and Charles, P. 1990. “The Use of Powdered Activated Carbon for the Removal of Specific Pollutants in Ultrafiltration processes.” Laboratoire Central, Lyonnaise des Eaux, Le Pecq, France.
research reportNot linked to a paper · refsec
APHA-AWWA-WEF. 1998. Standard methods for the examination of water and wastewater, 20th ed.
research reportNot linked to a paper · refsec
Washington, DC. Arora, H., M.W. LeChevallier, and K.L. Dixon. 1997. “DBP Occurrence Survey.” J. AWWA, 89:6:60-68.
journal articleNot linked to a paper · refsec
AWWA. 1969. Water Treatment Plant Design. First Edition, American Water Works Association, Inc.
research reportNot linked to a paper · refsec
AWWA. 1999. Water Quality and Treatment. Fifth Edition, McGraw-Hill, New York, NY.
research reportNot linked to a paper · refsec
AWWA and ASCE. 1998. Water Treatment Plant Design. Third Edition, McGraw-Hill, New York, NY.
research reportNot linked to a paper · refsec
AWWSC. 1998. Evaluation of Chlorine Dioxide for Inactivation of Cryptosporidium and Byproduct Control. AWWSC, Voorhees, NJ.
research reportNot linked to a paper · refsec
Babcock, D. B. and Singer, P. C. 1979. “Chlorination and Coagulation of Humic and Fulvic Acids.” J.
research reportNot linked to a paper · refsec
AWWA, 71:3:149. LT2ESWTR T&C Document December 2005
research reportNot linked to a paper · refsec
Battigelli, D.A., M.D. Sobsey and D.C. Lobe. 1993. “The Inactivation of Hepatitis A Virus and Other Model Viruses by UV Irradiation.” Wat. Sci. Tech., 27:3-4:339-342.
journal articleNot linked to a paper · refsec
Benedek, A., Bancsi, J. J., Malaiyandi, M. and Lancaster, E. A. 1979. “The Effect of Ozone on the Biological Degradation and Activated Carbon Adsorption of Natural and Synthetic Organics in Water. Part II. Adsorption.” Ozone Sci. Eng., 1:4:347.
research reportNot linked to a paper · refsec
Bergman R. A. 1996. “Cost of Membrane Softening in Florida”, J. AWWA, 88:5:32.
research reportNot linked to a paper · refsec
Bolton, J. R. 1999. Ultraviolet Applications Handbook. Bolton Photosciences, Inc., Ayr, Ontario, Canada.
journal articleNot linked to a paper · refsec
Bouwer, E. J. and Crowe, P. B. 1988. “Biological Processes in Drinking Water Treatment.” J. AWWA, 80:9:82.
research reportNot linked to a paper · refsec
Bukhari, Z.; Hargy, T.H.; Bolton, J.R., Dussert B., and Clancy J.L. 1998. “Inactivation of Cryptosporidium Parvum Oocysts Using Medium-Pressure Ultraviolet Light.” Proceedings, 1998 Annual AWWA Conference, Dallas, TX.
journal articleNot linked to a paper · refsec
Bukhari, Z., T.M. Hargy, J.R. Bolton, B. Dussert and J.L. Clancy. 1999) “Medium-Pressure UV Light for Oocyst Inactivation.” J. AWWA, 91:3:86-94.
journal articleNot linked to a paper · refsec
Cairns, B. 1999. “Ultraviolet Water Disinfection.” USEPA Workshop on UV Disinfection of Drinking
research reportNot linked to a paper · refsec
Water, April 28-29, 1999, Arlington, VA. Camel, V., and Bermond, A. 1999. “The Use of Ozone and Associated Oxidation Processes in Drinking Water Treatment.” Water Research, 32:11:3208-3222.
journal articleNot linked to a paper · refsec
Campbell, A. T., Robertson, L. J., and Smith, H. V. 1995b. “Inactivation of Oocysts of Cryptosporidium parvum by Ultraviolet Irradiation.” Wat. Res., 29:2583.
research reportNot linked to a paper · refsec
Next →