Federal Register. Final Rule. U.S. Environmental Protection Agency. 1999. National Primary and Secondary Drinking Water Regulations: Analytical Methods for chemical and Microbiological Contaminants and Revisions to Laboratory Certification Requirements; Final Rule Wednesday, December 1, 1999, Volume 64, Number 230, Page 67449-67467,[W-00-12-II-A-2-2]
Other documents for the same rulemaking (all, by stage)
References: 31 extracted, 0 linked to papers
EPA proposed approving the use of updated versions of previously approved analytical methods, the withdrawal of older versions of certain EPA methods, minor technical corrections or clarifications, and amendments to the regulations. The direct final rule, in the absence of adverse public comment, would have been final on January 4, 1999. Because adverse comments were received, EPA withdrew the entire September 1998 rule on December 31, 1998 (63 FR 72200) and deferred final action in order to respond to those comments.
Therefore, the pH adjustment step was removed and the method was reissued and proposed as EPA Method 549.2. The pH retest step and other data are in the administrative record of the July 31, 1998 (63 FR National Primary and Secondary Drinking W... to Laboratory Certification Requirementhttp://www.epa.gov/fedrgstr/EPA-WATER/1999/December/Day-01/w30901.htm 41134) rule. Use of EPA Method 549.2 does not require re-certification or learning the use of a new method. EPA Method 549.2 is EPA Method 549.1 without the pH adjustment step. Requiring a step (pH adjustment) to be omitted from the current method does not impose a hardship on analytical laboratories or the regulated community. As no positive effect is associated with the pH adjustment to 10.5, and there is the possibility of a negative effect, the Agency is withdrawing EPA Method 549.1.
3. MI-Agar Medium for Coliform Determinations In the July 31, 1998 rule, EPA proposed to approve the use of MI Agar for use with the Total Coliform Rule and Surface Water Treatment Rule. The Agency had proposed that the results from MI Agar can be read following incubation of media for 16-24 hours. Two commenters suggested that the MI Agar procedure should be approved as a 24 hour procedure since results in the comparison study were read at 24 hours. EPA data demonstrates that blue E. coli and fluorescent total coliform colonies appear in as few as 9 hours, which would be detected by the laboratory in 16-24 hours, depending upon the time of day the sample was filtered.
However, because the appearance time for the blue E. coli colonies exceeded the standard 8-hour working day and because EPA planned to compare the MI Agar procedure with one using M-Endo medium, a 24-hour method, EPA used the 24-hour incubation time for the studies. Thus, the Agency is approving the method as a 24-hour test (although the test may be recorded as positive if this result shows up earlier than 24 hours). The test is approved for detecting total coliforms and E. coli under the Total Coliform Rule and for enumerating total coliforms under the Surface Water Treatment Rule. B. Responses to Significant Comments Received on the September 3, 1998 (63 FR 47115) Notice 1. Quality Control Improvements for EPA Methods Four commenters on the September 1998 rule noted that, although many Supplement III methods contain tightened analyte recovery control limits of 30%, the data presented in some of these methods do not support the change. Commenters provided data or other information to support their argument for the following analytes: 2,4DB, Aciflurofen, DCPA, Dinoseb, pentachlorophenol and Picloram in EPA Method 515.1, Rev. 4.1; hexachlorocyclopentadiene (HCP) in EPA Method 508.1, Rev. 2.0; and DDT in EPA Method 508, Rev.3.1. The commenters recommended either (1) retaining the current limits of 3 standard deviations or method limits, whichever are narrower for these three methods or (2) setting the recovery control limits on an analyteby-analyte basis.
APHA 1992. Eighteenth edition of Standard Methods for the Examination of Water and Wastewater, 1992, American Public Health
APHA 1995. Nineteenth edition of Standard Methods for the Examination of Water and Wastewater, 1995, American Public Health
ASTM 1994. Annual Book of ASTM Standards, 1994, Vol. 11.01 and 11.02, American Society for Testing and Materials, 100 Barr Harbor
Drive, West Conshohocken, PA 19428. ASTM 1996. Annual Book of ASTM Standards, 1996, Vol. 11.01 and 11.02, American Society for Testing and Materials, 100 Barr Harbor
Drive, West Conshohocken, PA 19428. AWWA 1996. ""Standard Methods—A Closer Look'1, Posavec, Steve, in
Opflow, Vol. 22, No. 2, February 1996, American Water Works
Association, 6666 West Quincy Avenue, Denver, CO 80235. Brenner 1993. Brenner, K.P., et al., ""New medium for the simultaneous detection of total coliform and Escherichia coli in water 1 ', Appl. Environ. Microbiol. 59:3534-3544. Brenner 1996a. Brenner, K.P., et al., ""Comparison of the recoveries of Escherichia coli and total coliform from drinking water by the MI Agar method'', Appl. Environ. Microbiol. 62:203-208. Brenner 1996b. Brenner, K.P., et al., ""Interlaboratory evaluation of MI Agar and the U.S. Environmental Protection Agency—approved membrane filter method for the recovery of total coliform and Escherichia coli from drinking water' 1 , J. Microbiol. Methods 27:111119.
EPA 1987. ""Development of Preservation Techniques and Establishment of Maximum Holding Times: Inorganic Constituents of the National Pollutant Discharge Elimination System and Safe Drinking Water Act 1 ', EPA/600/S4-86/043, March 1987.
EPA 1990a. ""Methods for the Determination of Organic Compounds in Drinking Water—Supplement I'', July 1990, NTIS PB91-146027.
EPA 1991. ""Methods for the Determination of Organic Compounds in P.23 National Primary and Secondary Drinking W... to Laboratory Certification Requiremen_sttp://www.epa.gov/fedrgstr/EPA-WATER/1999/December/Day-01/w30901.htm Drinking Water'', December 1988, revised July 1991, NTIS PB91-231480.
EPA 1992. ""Methods for the Determination of Organic Compounds in Drinking Water—Supplement II, ' • August 1992, NTIS PB92-207703.
EPA 1993. ""Methods for the Determination of Inorganic Substances in Environmental Samples'', August 1993, NTIS PB94-120821.
EPA 1994. ""Methods for the Determination of Metals in Environmental Samples—Supplement I'', May 1994, NTIS PB95-125472.
EPA 1994b. Technical Notes on Drinking Water Methods, EPA/600/R-94/ 173, October 1994, NTIS PB95-104766.
EPA 1995. ""Methods for the Determination of Organic Compounds in Drinking Water—Supplement III, '' EPA/600/R-95/131, August 1995, NTIS PB95-261616.
EPA 1996. EPA Methods 515.3, ""Determination of Chlorinated Acids in Drinking Water by Liquid-liquid Extraction, Derivatization And Gas Chromatography With Electron Capture Detection,'' Revision 1.0, EPA/ 815/B-99/001, July 1996. Available from U.S. Environmental Protection
EPA 1997a. EPA Methods 549.2 ""Determination of Diquat And Paraquat in Drinking Water by Liquid-solid Extraction And High Performance Liquid Chromatography With Ultraviolet Detection'1, Revision 1.0, EPA/ 815/B-99/002, June 1997. Available from U.S. Environmental Protection
EPA 1997b. Manual for the Certification of Laboratories Analyzing Drinking Water, Fourth Edition, Office of Water Resource Center (RC4100), 401 M. Street SW, Washington, D.C. 20460, EPA/81/B-97/001, March 1997.
NY 1996. Suffolk County Water Authority 1996. Data Package pertaining to EPA Method 508.1 and the use of a NP detector. Suffolk County Water Authority Laboratory, 260 Motor Parkway, P.O. Box 18043,
Hauppauge, New York 11788-8843. Palintest 1999. Method 1001: Lead in Drinking Water by Differential Pulse Anodic Stripping Voltammetry, August 1999. Palintest, LTD, 21 Kenton Lands Road, P.O. Box 18395, Erlanger, KY 41018.
USGS 1989. Methods 1-3720-85, 1-3300-85, 1-1030-85, 1-1601-85, I2598-85, 1-1700-85 and 1-2700-85 in Techniques of Water Resources Investigations of the U.S. Geological Survey, Book 5, Chapter A-1, 3rd ed., 1989, U.S. Geological Survey (USGS) Information Services, Box 25286, Federal Center, Denver, CO 80225-0425.
USGS 1993. Method 1-2601-90 in Methods of Analysis by the U.S. Geological Survey National Water Quality Laboratory—Determination of Inorganic and Organic Constituents in Water and Fluvial Sediments, Open File Report 93-125, 1993, U.S. Geological Survey (USGS) Information
Services, Box 25286, Federal Center, Denver, CO 80225-0425. Williams 1979. Williams, T. J, et al., ""An Evaluation of the Need for Preserving Potable Water Samples for Nitrate Testing'1, JAWWA, March 1979, pp. 157-160. List of Subjects 40 CFR Part 141 Environmental protection, Chemicals, Incorporation by reference,
Indian-lands, Water supply. Dated: November 22, 1999.
Carol M. Browner, Administrator. P.24 National Primary and Secondary Drinking W... to Laboratory Certification Requirementbttp://www.epa.gov/fedrgstr/EPA-WATER/1999/December/Day-01/w30901.htm For the reasons set out in the preamble, title 40, chapter I of Code of Federal Regulations, are amended as follows: [[Page 67461]]
Street, SW, Washington, D.C. 20460 (Telephone: 202-260-3027); or at the Office of Federal Register, 800 North Capitol Street, NW, Suite 700, Washington, D.C. 20408. \1\ Methods 9221 A, B; 9222 A, B, C; 9221 D and 9223 are contained in Standard Methods for the Examination of Water and Wastewater, 18th edition (1992) and 19th edition (1995) American Public Health
Association, 1015 Fifteenth Street NW, Washington, D.C. 20005; either edition may be used. P.25 National Primary and Secondary Drinking W... to Laboratory Certification Requiremenlhttp://www.epa.gov/fedrgstr/EPA-WATER/1999/December/Day-01/w30901.htm \2\ The time from sample collection to initiation of analysis may not exceed 30 hours. Systems are encouraged but not required to hold samples below 10 deg.C during transit. \3\ Lactose broth, as commercially available, may be used in lieu of lauryl tryptose broth, if the system conducts at least 25 parallel tests between this medium and lauryl tryptose broth using the water normally tested, and this comparison demonstrates that the falsepositive rate and false-negative rate for total coliform, using lactose broth, is less than 10 percent. \4\ If inverted tubes are used to detect gas production, the media should cover these tubes at least one-half to two-thirds after the sample is added. \5\ No requirement exists to run the completed phase on 10 percent of all total coliform-positive confirmed tubes. \6\ MI agar also may be used. Preparation and use of MI agar is set forth in the article, ""New medium for the simultaneous detection of total coliform and Escherichia coli in water'1 by Brenner, K.P., et al., 1993, Appl. Environ. Microbiol. 59:3534-3544. Also available from the Office of Water Resource Center (RC-4100), 401 M. Street SW,