The J.P Pulliam Generating Station in Wisconsin uses dual barrier nets (0.64 centimeters stretch mesh) to permit net rotation for cleaning. Nets are used from April to December or when water temperatures go above 4 degrees Celsius. Impingement has been reduced by as much as 90 percent. Operating costs run about $5,000 per year, and nets are replaced every two years at $2,500 per net (EPRI, 1985). The Chalk Point Station in Maryland realized operational costs of $5,000-10,000 per year with the nets being replaced every two years (EPRI, 1985). However, crab impingement has been reduced by 84 percent and overall impingrment liability has been reduced from $2 million to $140,000 (EPRI, 1999). The Ludington Storage Plant (Michigan) provides water from Lake Michigan to a number of power plant facilities. The plant has a 2.5-mile long barrier net that has successfully reduced impingement and entrainment. The overall net effectiveness for target species (five salmonids, yellow perch, rainbow smelt, alewife, and chub) has been over 80 percent since 1991 and 96 percent since 1995. The net is deployed from mid-April to mid-October, with storms and icing preventing use during the remainder ofthe year (EPRI, 1999).
DESIGN CONSIDERATIONS: The most important factors to consider in the design of a net barrier are the site-specific velocities and the potential for clogging with debris (ASCE, 1982). The size of the mesh must permit effective operations, without excessive clogging. Designs at the Bowline Point Station in New York have 0.15 and 0.2 inch openings in the mesh nets, while the J.P. Pulliam Plant in Wisconsin has 0.25 inch openings (ASCE, 1982).
LIMITATIONS: Net barriers are not effective for the • protection of the early life stages of fish or zooplankton (ASCE. 1982). A-35 P.98
REFERENCES: ASCE. Design of Water Intake Structures for Fish Prntectinn (1982). American Society of Civil Engineers Electric Power Research Institute (EPRI). Fish Protection at Cooling Water Tntakes: Staftis Report. 1999.
Lawler, Matusky, and Skelly Engineers. 1977 Hudson River Aquatic Fcningy Snidies at the Rowline Pnint Generating Stations Prepared for Orange and Rockland Utilities, Inc. Pearl River, NY. 1978. A-36 P.99 Fish Diversion or Avoidance Systems FactSheetNo.il: Aquatic Filter Barrier Systems
Gunderboom, Inc., has a patented full-water-depth filter curtain comprised of polyethylene or polypropylene fabric that is suspended by flotation billets at the surface of the water and anchored to the substrate below. The curtain fabric is manufactured as a matting of minute unwoven fibers with an apparent opening size of 20 microns. The Gunderboom Marine/Aquatic Life Exclusion System (MLES)™ also employs an automated "air burst"™ technology to periodically shake the material and pass air bubbles through the curtain system to clean it of sediment buildup and release any other material back in to the water column. Gunderboom Marine/Aquatic Life Exclusion Svstem (Gunderboom, Inc., 1999)
TESTING FACILITIES AND/OR FACILITIES USING THE TECHNOLOGY: Gunderboom MLES ™ have been tested and are currently installed on a seasonal basis at Unit 3 ofthe Lovett Station in New York. Prototype testing ofthe Gunderboom system began in 1994 as a means of lowering ichthyoplankton entrainment at Unit 3. This was the first use ofthe technology at a cooling water intake structure. The Gunderboom tested was a single layer fabric. Material clogging resulted in loss of filtration capacity and boom submergence within 12 hours of deployment. Ichthyoplankton monitoring while the boom was intact indicated an 80 percent reduction in entrainable organisms (Lawler, Matusky, and Skelly Engineers, 1996). A Gunderboom MLES ™ was effectively deployed at the Lovett Station for 43 days in June and July of 1998 using an Air-Burst cleaning system and newly designed deadweight anchoring system. The cleaning system coupled with a perforated material proved effective at limiting sediment on the boom, however it required an intensive operational schedule (Lawler, Matuskv, and Skelly Engineers, 1998). A-37 A 1999 study was performed on the Gunderboom MLES ™ at the Lovett Station in New York to qualitatively determine the characteristics ofthe fabric with respect to the impingement of ichthyoplankton at various flow regimes. Conclusions were that the viability of striped bass eggs and larvae were not affected (Lawler, Matusky, and
Skelly Engineers, 1999). Ichthyoplankton sampling at Unit 3 (with Gunderboom MLES ™ deployed) and Unit 4 (without Gunderboom) in May through August 2000 showed an overall effectiveness of approximately 80 percent. For juvenile fish, the density at Unit 3 was 58 percent lower. For post yolk-sac larvae, densities were 76 percent lower. For yolk-sac larvae, densities were 87 percent lower (Lawler, Matusky & Skelly Engineers 2000).
DESIGN CONSIDERATIONS: The most important parameters in the design of a Gunderboom ® Exclusion System include the following (Gunderboom, Inc. 1999): Marine/Aquatic Life Size of booms designed for 3-5 gpm per square foot of submerged fabric. Flows greater than 10-12 gallons per minute. Flow-through velocity is approximately 0.02 ft/s. Performance monitoring and regular maintenance.
REFERENCES: Lawler, Matusky & Skelly Engineers, "Lovett Generating Station Gunderboom Evaluation Program 1995" Prepared for Orange and Rockland Utilities, Inc. Pearl River, New York, June 1996.
Lawler, Matusky & Skelly Engineers, "Lovett Generating Station Gunderboom System Evaluation Program -1998" Prepared for Orange and Rockland Utilities, Inc. Pearl River, New York, December 1998.
Lawler, Matusky & Skelly Engineers, " Lovett Gunderboom Fabric Ichthyoplankton Bench Scale Testing" Southern Energy Lovett. New York, November 1999.
Lawler, Matusky & Skelly Engineers, "Lovett 2000 Report" Prepared for Orange and Rockland
Utilities, Inc. Pearl River, New York, 2000. A-39 Fish Diversion or Avoidance Systems Fact Sheet No. 12: Sound Barriers
DESCRIPTION: Sound barriers are non-contact barriers that rely on mechanicaLor electronic equipment that generates various sound patterns to elicit avoidance responses in fish. Acoustic barriers are used to deter fish from entering industrial water intakes and power plant turbines. Historically, the most widely-used acoustical barrier is a pneumatic air gun or "popper." The pneumatic air gun is a modified seismic device which produces high-amplitude, low-frequency sounds to exclude fish. Closely related devices include "fishdrones" and "fishpulsers" (also called "hammers")- The fishdrone produces a wider range of sound frequencies and amplitudes than the popper. The fishpulser produces a repetitive sharp hammering sound of low-frequency and high-amplitude. Both instruments have ahd limited effectiveness in the field (EPRI, 1995;
EPRI, 1989; Hanson, et al., 1977; EPA, 1976; Taft, et al., 1988; ASCE, 1992). Researchers have generally been unable to demonstrate or apply acoustic barriers as fish deterrents, even though fish studies showed that fish respond to sound, because the response varies as a function of fish species, age, and size as well as environmental factors at specific locations. Fish may also acclimate to the sound patterns used (EPA, 1976; Taft et al., 1988;
EPRI, 1995; Ray at al., 1976; Hadderingh, 1979; Hanson et al., 1977; ASCE, 1982). Since about 1989, the application of highly refined sound generation equipment originally developed for military use (e.g., sonar in submarines) has greatly advanced acoustic barrier technology. Ibis technology has the ability to generate a wide array of frequencies, patterns, and volumes, which are monitored and controlled by computer. Video and computer monitoring provide immediate feedback on the effectiveness ofan experimental sound pattern at a given location. In a particular environment, background sounds can be accounted for, target fish species or fish populations can quickly be characterized, and the most effective sound pattern can be selected (Menezes, at al., 1991; Sonalysts, Inc.).
TESTING FACILITIES AND/OR FACILITIES WITH TECHNOLOGY IN USE: No fishpulsers and pneumatic air guns are currently in use at power plant water intakes. Research facilities that have completed studies or have on-going testing involving fishpulsers or pneumatic air guns include the Ludington Storage Plant on Lake Michigan; Nova Scotia Power; the Hells Gate Hydroelectric Station on the Black River; the Annapolis Generating Station on the Bay of Fundy; Ontario Hydro's Pickering Nuclear Generating station; the Roseton Generating Station in New York; the Seton Hydroelectric Station in British Columbia; the Surry Power Plant in Virginia; the Indian Point Nuclear Generating Station Unit 3 in New York; and the U.S. Army Corps of Engineers on the Savannah River (EPRI, 1985; EPRI, 1989;
EPRI, 1988; and Taft, et al., 1998). Updated acoustic technology developed by Sonalysts, Inc. has been applied at the James A. Fitzpatrick Nuclear Power Plant in New York on Lake Ontario; the Vernon Hydroelectric nlant on tbe Connecticut River (New England Power Comnanv. 1993: Menezes. et al.. 1991: A-40 personal communication with Sonalysts, Inc., by SAIC, 1993); and in a quarry in Verplank, New York (Dunning, et al., 1993).
REFERENCES: A-42 ASCE. Design of Water Intake Structures for Fish Protection. American Society of Civil Engineers. New York, NY. 1982. pp. 69-73.
Chow, W., Isbwar P. Murarka, Robert W. Brocksen. Electric Power Research Institute, Entrainment and Impingement in Power Plant Cooling Systems Tune 1981.
Avoid High Frequency Sound. 1991 Electric Power Research Institute (EPRI). Fish Protection at Cooling Water Intakes- Status Report 1999.
EPRI. Field Testing of Behavioral Barriers for Fish Exclusion at Cooling Water Tntake SytemsOntario Hydro Pickering Nuclear Generating Station Electric Power Research Institute. March 1989a.
River, for Electric Power Research Institute. EPRI GS-6293. March 1989.
EPRI. Field Testing of Behavioral Barriers for Fish Exclusion at Cooling Water Tntake SystemsCentral Hudson Gas and Electric CoMany Roseton Generating Statoni Electric Power Research Institute. September 1988.
EPRI. Tntake Research Facilities Manual 1985. Prepared by Lawler, Matusky & Skelly Enginem, Pearl River, for Electric Power Research Institute. EPRI CS-3976. May 1985.
Hadderingh, R. H. "Fish Intake Mortality at Power Stations: The Problem and Its Remedy." Netherlands HyHrohiological Rnlletin ; 13(2-3), 83-93, 1979.
Hanson, C. H., J.R. White, and H.W. Li. "Entrapment and Impingement of Fishes by Power Plant Cooling Water Intakes: An Overview." from Fisheries Review, MFR Paper 1266. October 1977.
McKinley, R.S. and P.H. Patrick. "Use of Behavioral Stimuli to Divert Sockeye Salmon Smolts at the Seton Hydro-Electric Station, British Columbia." In the Electric Power Research Institute Proceedings Fish Protection at Steam and Hydroelectric Power Plants. March 1988.
Menezes, Stephen W. Dolat, Gary W. T'iller, and Peter J. Dolan. Sonalysts, Inc. Waterford, Connecticut. The Electronic FishStartle System. 1991. New EnglancLPower Company. Effect of Ensonification on Juvenile American Shad Movement and Behavior at Vernon Hydroelectric Station, 1992. March 1993.
Patrick, P.H., R.S. McKinley, and W.C. Micheletti. "Field Testing of Behavioral Barriers for Cooling Water Intake Structures-Test Site 1-Pickering Nuclear Generating Station, 1985/96.* In the Electric Power Research Institute Proceedings Fish Protection at Steam and Hydroelectri Power Plants March 1988. A-43 Personal Communication, September 17, 1993, letter and enclosure from MJ. Curtin (Sonalysts, Inc.) to D. Benelmouffok (SAIC).
Ray, S.S., R.L. Snipes, and D. A Tomljanovich. *A State-of-the-Art Report on Intake Technologies.TVA PRS-16 and EPA 6OOn-76-020. October 1976.
Taft, E. P., and J.K. Downing. -Comparative Assessment of Fish Protection Alternatives fbr Fossil and Hydroelectric Facilities.' In the Electric Power Research Institute Proceedingsp Fish Protection at Steam and Hydroelectric Power Plants March 1998.
Taft, E.P, J. K. Downing, and C. W. Sullivan. "Laboratory and Field Evaluations of Fish Protection Systems for Use at Hydroelectric Plants Study Update." In the Electric Power Research Institute's Proceedings: Fish Protection at Steam and Hydroelectric Power Plants March 1988. U.S. EPA. Develnpment Document for Best Technology Available for the Location D Constmction and Capacity of Cooling Water Tntake Stmctures fbr Minimizing Adverse Environmental Impact U.S. Environmental Protection Agency, Effluent Guidelines Division, Office of Water and Hazardous Materials. April 1976.
Uziel, Mary S., "Entrainment and Impingement at Cooling Water Intakes." Journal WPCF, Vol 52, No.6. June 1980.
ADDITIONAL REFERENCES: Blaxter, J.H'.S., and D.E. Hoss. "Startle Response in Herring: the Effect of Sound Stimulus Frequency, Size of Fish and Selective Interference with the Acoustical-lateralis System. " Journal ofthe Marine Biolo/ical Association ofthe United Kingdom 61-971-879 1981.
Blaxter, U.S., J.A.B. Gray, and E.J. Denton. "Sound and Startle Response in Herring Shoals." J Mar Riol Ass U K 61851-869 1981
Burdic, W.S. Underwater Acoustic System Analysis F.nglewood Cliffs, New Jersey: PrenticeHall. 1984.
Burner, C.J., and H.L. Moore. "Attempts to Guide Small Fish with Underwater Sound. "U.S. Fish and Wildlife Service. Special Scientific Report: Fisheries No 403. 1962. p. 29.
CH. Hocutt. "Behavioral Barriers and Guidance Systems." In Power Plants: Effects on Fish and Shellfish Rebavior C H Hocutt, J.R. Stauffer, Jr., J. Edinger, L. Hall, Jr., and R. Morgan, U (Editors). Academic Press. New York, NY. 1980. pp. 183-205. Empire State Electric Energy Research Corporation. 'Alternative Fish Protective Techniques: Pneumatic Guns and Rope. Nets." EP-83-12. March 1984. A-44
Illinois. 1988. Frizzell, L.A., *Biological Effects of Acoustic Cavitation." In Ultrasound Tts Chemical, Physical and Biological Effects. K.S. Suslick (Editor). VCH Publishers, Inc. New York. 1988. pp. 297-319.
Haymes, G.T., and P.H. Patrick. "Exclusion of Adult Alewife (Alosa pseuoharengus), Using Low-Frequency Sound for Application of Water Intakes.' Can, J. Fish Aamatics Srd 43:855862. 1986.
FM Tonmal September 1987. Micheletti, Coal Combustion Systems Division. wFish Protection at Cooling Water Intake Systems."
EPRI Tonmal September 1997. Patrick, P.H., R.S. McKinley, A. E. Christie, and J.G. Holsapple. "Fish Protection: Sonic Deterrents.' In the EPRI Proceeding: Fish Protection at Steam and Hydroelectric Power Plants March 1988.
Ross, Q.E., D. J. Dunning, R. Thorne, J. Menezes, G. W. Tiller, and J. K. Watson. Response of Alewives to High Frequency Sound at a Power Plant Tntake on Lake Ontario. 1993
Schwarz, A.L., and G.L. Greer. "Responses, of Pacific Herring, Clnltea harengns Rallasi, to Some Underwater Sounds." Can T Fish Agnatic Sri 41-119^-1197 1984.
Smith, E.J., and J.K. Andersen. "Attempts to Alleviate Fish Losses from Allegheny Reservoir, Pennsylvania and New York, Using Acoustic." North American Tonmal of Fisheries Management vol 4(3), 1994. pp. 300-307.
Thorne, R.E. "Assessment of Population Density by Hydroacoustics." In Tonmal of Biological Oceanography Vol. 2. 1983. pp. 252-262. A-45 Industry Profile: Oil and Gas Extraction Industry § 316(b) TDD Chapter 6 for New Facilities Chapter 6: Industry Profile: Oil and Gas Extraction Industry
EPA-821-B-00-013, December 2000. U.S. EPA, Economic Analysis of Final Effluent Limitations Guidelines and Standards for Synthetic-Based Drilling Fluids and other Non-Aqueous Drilling Fluids in the Oil and Gas Extraction Point Source Category,
EPA-821-B-00-012, December 2000. U.S. Departmentof Interior, Minerals Management Service, Liberty Development and Production Plan Draft Environmental Impact Statement, OCS EIS/EA, MMS 2001-001, January 2001.