Damage Case Compendium, Volume III: Rejected Damage Cases - DCN SE04462
Other documents for the same rulemaking
References: 248 extracted, 0 linked to papers
EIP (2010a) counters that sulfate, boron, and strontium concentrations all generally correspond with the lead and arsenic exceedances. Under the SD DENR permit, boron, sulfate and strontium are designated as ash monitoring parameters, indicating CCR is a significant source of the pollution.200, 201 198 EarthJustice comment to the proposed CCR Rule’s docket (EPA-HQ-RCRA-2009-0640-6314) address the same 2007-2009 groundwater monitoring records cited by EIP (2010a). BSP’s groundwater monitoring program consists of 25 wells, 17 of which are screened at shallow depths and 8 of which are screened at intermediate depths. Many wells are nested together to provide an indication of vertical contaminant transport.
EIP (2010a) claims that exceedances have been measured in down gradient groundwater for arsenic at more than 13 times the federal MCL at 0.1322 mg/L, boron up to 34 times the federal Lifetime Health Advisory Level at 204 mg/L, lead up to 7 times the federal Action Level at 0.1086 mg/L, strontium up to 1.5 times the federal Lifetime Health Advisory at 6.03 mg/L, chloride up to 13 times the federal Secondary MCL (SMCL) at 3,330 mg/L, and sulfate up to 112 times the state standard and 224 times the federal SMCL at 56,000 mg/L. 199 In its comment to the proposed CCR Rule’s docket (http://www.uswag.org/pdf/2010/CCR%20Comments/SDDENR112010.pdf), SD DENR challenges EIP’s (2010a) assertion that
BC-3, and BC-4) generally correspond to those with the highest concentrations of boron, lead, sulfate, and chloride. This is the basis for the Utility’s argument (Barr, 2010) that the residual brine of the predecessor leaking brine pond is the source of the high levels of both the metals (boron, manganese, and strontium) and the major ions (chloride, hardness, potassium, sodium, and sulfate). To test the hypothesis that evaporation alone can result in significant exceedances of the area’s natural lake waters, we used Carter and Thompson’s (1999) concentration level of ‘conservative’ parameters (i.e., constituents that would remain in solution until very high concentration levels are caused due to evaporation: sodium, potassium, chloride, and sulfate) measured in Lake Traverse as a proxy for the composition of Big Stone Lake’s water - BSP’s cooling water source. The compositions of interest are sodium: 46 mg/L, potassium: 12 mg/L, sulfate: 370 mg/L, chloride: 16 mg/L, arsenic: 8 µg/L, and boron: 180 µg/L. (Composition data for Big Stone Lake are rather scarce and incomplete, and do not include data for arsenic or boron: http://watersgeo.epa.gov/mwm/?layer=LEGACY_WBD&feature=07020001&extraLayers=null). By evaporating the water of Lake Traverse to the maximum level of sodium concentration recorded in 2009 in BSP’s Holding Pond: 526 mg/L (11.4 times the baseline level), it is possible to elevate the concentration of arsenic to 91 µg/L (9.1 times the
EIP (2010a) also indicates that for a number of reasons, current monitoring is insufficient and cannot define the extent of contamination. For example, the Cooling Pond is located along the northern property line with no wells along that side. The Evaporation Pond is located along the northern and eastern property lines, with no wells along those property lines. Although there may be off-site contamination, groundwater is not being monitored along much of the perimeter of the BSP’s site.202
III. CCR Rejected Damage Cases December 2014 and a nest of three wells, S-4, S-5, and S-6, south towards the Whetstone River. These wells were installed in August 1990. However, after the wells were installed, rather than conduct enhanced monitoring to determine the source and extent of contamination, the BSP continued to monitor the groundwater under the normal detection-monitoring program. No new off-site (beyond the BSP property line) wells have ever been installed, no existing off-site wells have been sampled, and no surface water samples have been collected to-date.
USWAG does not consider this site to qualify as a damage case.205 Evaluation:206 “Not a damage case. Although there are exceedances of primary EPA MCLs, EPA Lifetime Health Advisories, and EPA SMCLs in onsite groundwater, the exceedances generally occur near the brine ponds and are possibly related to the water softening and treatment process: CCRs cannot be directly implicated as a source of the contamination. There are no administrative rulings or court decisions associated with the site.” Rationale for Rejection: Considering that the old Brine Pond, the leakage of which resulted in the 1988 groundwater exceedances, contains solely non-contact, evaporation-concentrated water, recent (at least 2007-09) groundwater impact detected in the BC and S monitoring wells cannot be attributed to CCR. Due to inadequate spatial distribution of the current monitoring well network around the ash landfill and its runoff pond (the H wells) it is impossible to ascertain whether CCRs are directly implicated as the source of the recent contamination. References
Appendix C, Case #31. ICF, October 2010. SD DENR (No date): South Dakota Department of Environment and Natural Resources (SD DENR). Website link for Waste Management Program – Coal Ash. Accessed Online March 2013. http://denr.sd.gov/coalash.aspx Barr (2010): 2009 Annual Water Monitoring Report, South Dakota Department of Environment and Natural Resources, Solid Waste Permit 06-18A, Big Stone Plant, Big Stone City, South Dakota. Prepared by Barr, 4700 West 77th Street, Minneapolis, MN 55435-4803, April 2010. Accessed Online March 2013. http://denr.sd.gov/des/wm/coalash/2009bsamr0410.pdf U.S.
DOE EIS (2009): U.S. Department of Energy, Western Area Power Administration, Final Environmental Impact Statement Volume I: Big Stone II Power Plant and Transmission Project,
USWAG’s comment to the 2011 NODA docket (EPA-HQ-RCRA-2011-0392-0211), November 14, 2011: “This case does not meet the criteria for a damage case because the allegations are only for on‐site groundwater. The information provided for the site does not contain any documented evidence of off‐site groundwater monitoring data or off‐site groundwater monitoring data showing exceedances of specified health‐based criteria. Allegations focus on potential impacts to nearby drinking water wells; there are no data from the off‐site wells to indicate off‐site impacts.”
ICF (2010). III. CCR Rejected Damage Cases December 2014
DOE/EIS-0377, prepared for Western Area Power Administration and U.S. Army Corps of Engineers, June 2009. Accessed Online March 2013. http://energy.gov/sites/prod/files/EIS-0377-FEIS-01-2009.pdf U.S.
DOE SDEIS (2007): U.S. Department of Energy, Western Area Power Administration, Big Stone II Power Plant and Transmission Project Supplemental Draft Environmental Impact Statement 0377, 2007. Accessed Online March 2013. http://energy.gov/sites/prod/files/EIS-0377-DEIS-2007.pdf Hansen (1990): Water Resources of Codington and Grant Counties, South Dakota. U.S. Geological Survey Water-Resources Investigations Report 89-4147. Hansen, D. S., in cooperation with the South Dakota Geological Survey, East Dakota Water Development District, and Codington and Grant Counties.
Huron, South Dakota, 1990. Accessed Online March 2013. http://pubs.usgs.gov/wri/1989/4147/report.pdf Cobban and Merewether (1983): the Stratigraphy and Paleontology of Mid-Cretaceous Rocks in Minnesota and Contiguous Areas, William A. Cobban and E. A. Merewether, Geological Survey Professional Paper 1253, 1983. Accessed Online March 2013. http://pubs.usgs.gov/pp/1253/report.pdf Gilbertson (1996): Investigation of Groundwater Resources in Portions of Roberts County, South Dakota,
III. CCR Rejected Damage Cases December 2014 fly ash mixture (Poz-O-Tec), along with small volumes of bottom ash and sludge from coal pile runoff treatment ponds, in a 22-acres stretch of an abandoned strip coal-mine 12 miles east from the plant.208 Part of the landfill is underlain by acid-producing spoils from the strip mining of coal. Impact: In the 1988 Report, EPA found concentrations of cadmium exceeding the MCL by as much as 20 times in downgradient groundwater; the highest concentration was found in a well closest to the landfill. There were no upgradient exceedances of cadmium. Arsenic was repeatedly detected at levels three to five times the PDWS in pond liquors, but appeared to be attenuated by soils at the site. Secondary drinking water standards (for pH, manganese, sulfate, and iron) were exceeded at the site in both the upgradient and downgradient groundwater. EPA concluded that coal combustion wastes have been a source of contamination at the site, but also concluded that exceedances for many contaminants were probably due to concurrent contamination from acid mine drainage. Resolution: According to EPRI (2010), there is no information on mitigation and/or remedial actions, Current site status and existing monitoring well network.
EPRI (2010) claims that there are no receptors between the site and the Youghiogheny River. Basis for Consideration as a Potential Damage Case: While levels of cadmium exceed the primary
EPA (2007): Coal Combustion Waste Damage Case Assessments, July 2007, Case #30, docket ID EPAHQ-RCRA-2006-0796-0015 (including a reference to (i) a Memorandum from SAIC to Dennis Ruddy regarding Rationale and Conclusions Regarding Commenter-Identified Fossil Fuel Combustion Waste Damage Cases, April 20, 2000, and (ii) Compendium of nineteen alleged coal combustion wastes damage cases, May 3, 2007). http://www.regulations.gov/#!documentDetail;D=EPA-HQ-RCRA-2006-0796-0015
Arthur D. Little, Inc. (1985): Full-scale Field Evaluation of Waste Disposal from Coal-fired Electric Generating Plants. Volume 1. Prepared for Environmental Protection Agency, Research Triangle Park, North Carolina. Little (Arthur D.), Inc., Cambridge, Massachusetts. June 1985. PB85-228054. Energy said the Elrama closing is driven by economic conditions, including the high price of coal and lower electricity demand: http://gantdaily.com/2012/02/29/genon-looking-to-cut-generating-capacity-shawville-plant-inthe-crosshairs/, http://www.post-gazette.com/stories/local/region/off-switch-hit-for-power-plants-220452/#ixzz2M8mzTHej, and http://www.cleanair.org/sites/default/files/Elrama%20TV%20(63-00014)%20Comments%201.14.13.pdf Whereas the specific mine site is not identified in the accessible resources, according to the Compendium of nineteen alleged coal combustion wastes damage cases (May 3, 2007), the mine drains into the Youghiogheny River. According to http://www.environmentalintegrity.org/news_reports/documents/LabelleNoticeLetter20130313.pdf, Ash Volume Reports submitted annually by Mac Canestrale Contracting indicate that the LaBelle reclaimed strip mine received 97,370 tons of ash from the Elrama plant in 2010, and 18,344 tons - in 2011.
RTC (1988, Page 5-32), citing Arthur D.
Little (1985). See also Exhibits 5-10 and 5-11 for concentration levels observed at the site’s groundwater monitoring wells.
III. CCR Rejected Damage Cases December 2014 http://nepis.epa.gov/Exe/ZyNET.exe/500020AK.TXT?ZyActionD=ZyDocument&Client=EPA&Index=1 986+Thru+1990&Docs=&Query=&Time=&EndTime=&SearchMethod=1&TocRestrict=n&Toc=&TocE ntry=&QField=&QFieldYear=&QFieldMonth=&QFieldDay=&IntQFieldOp=0&ExtQFieldOp=0&XmlQ uery=&File=D%3A%5Czyfiles%5CIndex%20Data%5C86thru90%5CTxt%5C00000018%5C500020AK. txt&User=ANONYMOUS&Password=anonymous&SortMethod=h%7C&MaximumDocuments=1&FuzzyDegree=0&ImageQuality=r75g8/r75g8/x150y150g16/i425&Display=p %7Cf&DefSeekPage=x&SearchBack=ZyActionL&Back=ZyActionS&BackDesc=Results%20page&Ma ximumPages=1&ZyEntry=1&SeekPage=x&ZyPURL
RTC (1988): Report to Congress on Wastes from the Combustion of Coal by Electric Utility Power Plants (EPA530-SW-88-002), US EPA, February, 1988. Accessed Online December 2014. http://www.epa.gov/osw/nonhaz/industrial/special/fossil/coal-rtc.pdf
EPA (2007, Table 1). http://www.epa.gov/epaoswer/other/fossil/volume_2.pdf For present pond locations, see O’Brien & Gere (2010), Figures 1-3. According to Dominion Power (2009), there are also three old/closed VPDES treatment ponds (Ash Pond A, B and C). According to O’Brien & Gere (2010), Figures 1-3, Ponds A and B occupy each an area of about seven acres.
EPA (2007). III. CCR Rejected Damage Cases December 2014 wastes in damages.”221 DVP and USWAG cite the same rationale for rejecting this as a CCR damage case.222 References
EPA (2007): 2007 Coal Combustion Waste Damage Case Assessments, July 2007, Case #4, docket ID
EPA-HQ-RCRA-2006-0796-0015 (including a reference to a Memorandum from SAIC to Dennis Ruddy regarding Rationale and Conclusions Regarding Commenter-Identified Fossil Fuel Combustion Waste Damage Cases, April 20, 2000.) http://www.regulations.gov/#!documentDetail;D=EPA-HQ-RCRA-2006-0796-0015
Appendix A, Case #4. ICF, 10/2010. Technical Background Document to the RTC (1999): Technical Background Document for the Report to Congress on Remaining Wastes from Fossil Fuel Combustion: Potential Damage Cases. March 15, 1999. Accessed Online February 2013. http://www.epa.gov/osw/nonhaz/industrial/special/fossil/ffc2_397.pdf O’Brien & Gere (2010): Dam Safety Assessment of CCW Impoundments, Possum Point Power Station,
Report, United States Environmental Protection Agency, Washington, DC, September 8, 2010. Accessed Online February 2013. http://www.epa.gov/wastes/nonhaz/industrial/special/fossil/surveys2/dom-possum-final.pdf Dominion Power (2009): Response to a request for information pursuant to Section 104(e) of the Comprehensive Environmental Response, Compensation, and Liability Act (“CERCLA”), Virginia Electric and Power Company, Possum Point Power Station, March 23, 2009. Accessed Online February 2013. http://www.epa.gov/waste/nonhaz/industrial/special/fossil/surveys/dominion-va.pdf
EPRI (2010): Evaluation of Coal Combustion Product Damage Cases, Volume 2: Site Information. EPRI 1020554, Final Report, September 2010. Accessed Online August 2012. http://www.epri.com/search/Pages/results.aspx?sq=1&k=Evaluation%20of%20Coal%20Combustion%20 Product%20Damage%20Cases R15. Mitchell Generating Station, American Electric Power,223 Moundsville, Marshall
ICF (2010), Appendix A, P. 4. (i) DVP, in their comment to the 2011 NODA, EPA-HQ-RCRA-2011-0392-0254: “The EPA subsequently identified the likely source of this contamination to be oil ash and other low volume wastes and not coal fly or bottom ash. As the Possum Point findings are a result of oil ash contamination rather than coal ash, this case is not relevant to the scope of the NODA.”(ii) USWAG, in their comment to the 2007 NODA, EPA-HQ-RCRA-20060796-0432, Appendix C. d/b/a Ohio Power Company.
III. CCR Rejected Damage Cases December 2014 Background and Description: Mitchell Generating Station manages CCRs in two ponds and a landfill:224 the fly ash pond is unlined, and there is no information as to whether the bottom ash pond and the landfill have a liner. The Plant’s impoundments have been accepting fly ash and bottom ash slurries from two power plants (in 2008, about 40 percent of the total waste came from AEP Mitchell and AEP Kammer) and the reminder, ‘unspecified coal mining wastes,’ from the Consol McElroy Mine. 225, 226 The Conner Run fly ash impoundment has been receiving fly ash from the AEP since 1971. This impoundment discharges effluent to Conner Run, a tributary of Fish Creek that discharges to the Ohio River.227 Conner Run has a site-specific variance from the statewide numeric criteria for selenium and iron.228 In addition to ash pond effluent, seepage through ash pond retention dikes also entered Fish Creek and the Ohio River. 229, 230 Impact: According to EIP (2010), the Mitchell Plant holds CWA NPDES permit # WV0005304. Outlet 004 discharges effluent from the impoundment to Conner Run. The outfall has a 0.062 mg/L max daily limit for selenium based on the site specific variance. The Mitchell Plant exceeded the selenium limit at Outlet 004 in August, 2005, in August-September, 2006 and in 2007, every month from May through
December, with values between 0.063 to 0.254 mg/L and an average of 0.118 mg/L. 231 Average selenium concentrations in 14 water samples taken downstream of the discharge in Conner Run from November 2005 through April 2007 were 0.0478 mg/L (WVDEP, 2009b). This is more than twice as high as the state‘s water quality standard for protection of aquatic life from acutely toxic selenium concentrations (0.020 mg/L) and nearly 10 times higher than the state‘s standard for protection of aquatic life from concentrations of selenium that engender chronic toxic effects (0.005 mg/L, the same as EPA‘s
EPA (2009). The Conner Run fly ash impoundment was commissioned in 1971; it has a capacity of 13,500 acrefeet, covers 71 acres, and holds 48 million cubic yards of fly ash. The bottom ash pond was commissioned in 1975, has a capacity of 262 acre-feet, and covers 17.5 acres. According to (WVDEP, 2009), the capacity of this pond is 464 acre-feet. According to WVDEP (2009), the bottom ash pond is roughly parallel to the Ohio River. Heavier sludge material is pumped into the upper reservoir of the dam and water flows from the upper reservoir into the lower section after settling. The lower section has three small dikes across it that are approximately perpendicular to the river that appear to have been installed to increase retention- time in the reservoir. The bottom ash that remains in the upper section of the impoundment is removed by a bulldozer and end loader. The water leaves the lower portion of the reservoir through an overflow structure and is carried to a third settling pond (‘the clear water pond’) before being released into an outfall structure to the Ohio River.
WVDEP (2009a). The Consol McElroy Mine is an underground coal mine and refuse impoundment owned by McElroy Mining, that supplies coal to the Mitchell plant. According to EIP (2010), the start date is ‘prior to 1990’. Except that site-specific numeric criteria shall apply to the stretch of Conners Run from its mouth to the discharge from Conner Run impoundment, which shall not have the Water Use Category A and may contain selenium not to exceed 62 µg/L; and iron not to exceed 3.5 mg/L as a monthly average and 7 mg/L as a daily maximum. West Virginia’s statewide selenium numeric criteria for the protection of aquatic life are 5µg/L chronic and 20µg/L acute; and State regulations require that site specific numeric criteria be fully protective of designated and existing uses.
Ibid, and references therein. According to Lemly (2010), whereas the power plant began discharging ash effluent in 1971, no biological monitoring was conducted until 2005-2007. No biological effects studies have been done. Discharge of ash pond effluent continued unabated in 2010. This specific daily limit for selenium discharge is corroborated by a WVDEP regulator responding to the 2007
NODA: ‘The permit reissued in 2005 contains a max daily limit of 0.062 mg/L for selenium. It would appear that they (AEP Mitchell) have been violating this effluent limit.” Alleged DCs NODA Comments Overview, an EPA Draft Document, October 7, 2008, case #11, with Industry’s rebuttal and State’s feedback.
III. CCR Rejected Damage Cases December 2014 Despite the waiver’s requirement, EIP (2010) claims there is substantial evidence that aquatic life uses of Conner Run are being seriously degraded due to selenium discharges associated with the Mitchell Plant, with two, post-2005 instances of an average fish tissue concentration of selenium of 24.4ppm and 31.5ppm.232, 233 According to WVDEP,234 statistical analyses have been conducted on groundwater monitoring wells MWH1, MWU3, MWL3. Statistical Significant Increases (SSI) were found on MWH1 for temperature, SO4, zinc, and sodium. No other SSIs were found. Exceedances have been reported for arsenic at MWH1, MWU3, and MWL3, and an exceedance for antimony was reported at MWL3.
EIP (2010) claims that groundwater monitoring showed moderate exceedences of the arsenic groundwater criterion downgradient from the impoundment in several months in 2005 and 2006. In summary, Incidences of surface water discharges above the site variance concentrations allowed in the permit have occurred since at least 2005. Violations of numeric water quality criteria in Conner Run have been documented continuously from late 2005 through the spring of 2007. Fish tissue test results indicate exceedances of safe levels of selenium in fish occurring at least in 2006. Groundwater data indicate exceedances dating from at least 2005.235
Recently, AEP acknowledged (i) high selenium levels in fish while citing extenuating circumstances;236 (ii) occasional selenium effluent limit exceedances in Outfall 004 in 2005-2007; and (iii) exceedances of arsenic in groundwater down-gradient from the Conner Run impoundment on four occasions in 2005, and on two – in 2006. 237 Remediation/Resolution: The selenium variance for Conner Run, raising it from the USEPA national criterion value of 5µg/L to a permissible level of 62µg/L, was not approved by EPA, nor was it based on a site-specific standard development process that included supporting biological studies.238 These levels exceed EPA’s proposed selenium fish tissue criterion of 7.9ppm for the protection of aquatic life by 3 and 4 fold, respectively. They also greatly exceed threshold values of 4ppm established by A. Dennis Lemly, a fisheries selenium expert at the USDA Forest Service. In addition, fish containing 31.5ppm selenium should trigger a West Virginia human fish consumption advisory restricting consumption to just one meal a month. Lemly has estimated the monetary value of the damage as $18,666.
EIP (2010). American Electric Power comment to the 2011 NODA: EPA-HQ-RCRA-2011-0392-0202: “WV DEP has not adopted any fish tissue criterion for selenium. The only applicable selenium regulatory limitation at the Mitchell Plant fly ash pond impoundment is the existing maximum effluent limitation of 62µg/L. This site-specific criterion is based on laboratory toxicity studies conducted by Ohio Power Company. Neither WV DEP nor any other party has provided evidence indicating that the aquatic life use of Conner Run is or previously was/ impaired…. there is considerable evidence indicating that fish residing in fly ash impoundment receiving streams do not suffer adverse population-level impacts despite having relatively high levels of selenium in their tissues (Reash et al. 1988, Reash et al. 1999; Lohner et al. 2001, Reash et al. 2006). The most likely explanation of these fish not exhibiting adverse effects is long-term adaptation and the presence of other trace metals that are believed to antagonize the potential toxic effects of selenium.” American Electric Power comment to the 2011 NODA, ibid.
III. CCR Rejected Damage Cases December 2014 The WVDEP has classified Conner Run as a fly ash influenced stream.239 Concentrations of selenium in muscle tissue of sport fish exceed West Virginia’s consumption restriction advisory levels (10 ppm dry weight, or 2.5 ppm wet weight). However, no advisory has been issued.240 Rationale for Rejection: A recent reevaluation of CCR damage cases241 determined that this is Not a Damage Case:”The site is reported to co-manage CCR and unspecified ‘coal mining wastes’; therefore the claim does not specifically implicate CCRs as a cause of damage to human health or the environment.” The observation of a large, co-managed fraction of the waste originating in a nearby mine is noted by West Virginia’s regulator242 and adopted by USWAG as one of the arguments for rejecting this site as a damage case.243 References
EIP (2010): Out of Control: Mounting Damages from Coal Ash Waste Sites; Environmental Integrity
Project, EarthJustice; February 24, 2010, Case #31. http://www.environmentalintegrity.org/news_reports/news_02_24_10.php Alleged DCs NODA Comments Overview, an EPA Draft Document, October 7, 2008, case #11, with Industry’s rebuttal and State’s feedback.
EPA (2009): Coal Combustion Waste Surveys, American Electric Power, Mitchell generating Station. Accessed Online February 2013. http://www.epa.gov/waste/nonhaz/industrial/special/fossil/surveys/survey-mitchell.pdf
WVDEP (2009a): Fly Ash Dam/Landfill Condition Evaluation, West Virginia Department of Environmental Protection, Division of Water and Waste Management, Environmental Enforcement, November 2009. Accessed Online February 2013. http://www.dep.wv.gov/WWE/ee/ds/Documents/Status_WV_Fly_Ash_Dams_Landfills_Nov609.pdf Lemly (2010): A White Paper on Environmental Damage from Coal Combustion Waste: The Cost of Poisoned Fish and Wildlife, A. Dennis Lemly, EPA Docket comment EPA–HQ–RCRA–2009–06406313, Appendix I, December 15, 2010. Accessed Online February 2013. http://prairierivers.org/wp-content/uploads/2012/03/Lemly-2010-Environmental-Damage-from-CCW.pdf
WVDEP (2009b): Selenium bioaccumulation among selected stream and lake fishes in West Virginia. West Virginia Department of Environmental Protection, 2009. WVDEP, Charleston, WV. Accessed Online February 2013. http://www.dep.wv.gov/WWE/watershed/wqmonitoring/Documents/Selenium/Se_Fish_Tissue_Summary _Paper_final_Feb09.pdf
WVDEP (2009b): “Average water column concentrations of selenium in streams ranged from <1.0 ppb (μg/L) at the reference site, Ash Fork (Fig. 1), to 49.7 ppb at Conner Run, which is influenced by upstream fly ash deposition.” Lemly (2010) and references therein: Average fish tissue selenium concentration in Conner Run is 25.99µg/L, predominantly as selenite (Se+4, IV) form, the valance state selenium which is reported to be more bioaccumulative.
ICF (2010, Appendix B, #31, p. 62).
WVDEP (2009a), citing from Mitchell’s 2008 Annual report.