Energy Conservation Program: Test Procedures for Manufactured Housing
Federal Register2016-11-09 · DEPARTMENT OF ENERGY · Proposed Rule · 2016-26008
Notice of proposed rulemaking.
The U.S. Department of Energy (DOE) is publishing a proposed rule to establish test procedures for manufactured housing (MH). This test procedure would support standards DOE is directed to establish by the Energy Independence and Security Act of 2007. DOE proposes to establish test procedures applicable to manufactured homes for determining compliance with the following metrics that were included in a June 17, 2016, notice of proposed rulemaking: The R-value of insulation; the U-factor of windows, skylights, and doors; the solar heat gain coefficient of fenestration; U-factor alternatives to R-value requirements; the air leakage rate of air distribution systems; and mechanical ventilation fan efficacy. DOE will accept comments regarding this proposed rule.
Original sourceXML (143 KB)PDF (354 KB)
Other documents for the same rulemaking
References: 4 extracted, 1 linked to papers
Page 1Download these results: CSV · JSON
Conner, C.C., Taylor, Z.T., Pacific Northwest Laboratory, published February 1, 1992 (Battelle Method). "Overall U-Values and Heating/Cooling Loads-Manufactured Home."
Hammon, R.W. and Modera, M.P. "Improving the Energy Efficiency of Air Distribution Systems in New California Homes." Proceedings of the 1996 ACEEE Summer Study on Energy Efficiency in Buildings. Vol. 2. 1996.
conference paperNot linked to a paper · fn 16
"Field Test Best Practices—Duct Pressurization Testing." National Renewable Energy Laboratory Building Research. https://buildingsfieldtest.nrel.gov/duct_pressurization_testing.
Energy Star Ventilation Fans Key Product Criteria. https://www.energystar.gov/products/heating_cooling/fans_ventilating/key_product_criteria.