EPA. 1999d. Guidance Manual for Compliance with the Interim Enhanced Surface Water Treatment Rule: Turbidity Provisions. EPA Document Number: EPA 815-R-99-010. 214 pp. Also available at the Water Resource Center and NTIS (PB99-111429). Cover page and table of contents are on the WWW at www.epa.gov/safewater/mdbp/pdf/turbidity/cover_tu.pdf [W-99-10-I-B-82]
Other documents for the same rulemaking (all, by stage)
References: 154 extracted, 0 linked to papers
Hudson, H.E. Jr. 1981. Water Clarification Processes, Practical Design and Evaluation. Van Nostrand Reinhold Environmental Engineering Series, Litton Educational Publishing, Inc.
Kawumara, S. L991. Integrated Design of Water Treatment Facilities. John Wiley & Sons, Inc. April 1999 10-23
THIS PAGE INTENTIONALLY LEFT BLANK EPA Guidance Manual Turbidity Provisions 10-24 April 1999 P.71
However, particles larger than the wavelength of the incident light, form a spectral pattern that results in greater light scattering in the forward direction (away from the incident light) than in the other directions. This scattering pattern and intensity of the light beam April 1999 11-1
EPA Guidance Manual Turbidity Provisions 11-2 April 1999 P.73
Therefore, if a polychromatic light source is used, the spectral output of the light source has a direct bearing on the type and design of photodetector selected for an instrument. The specification of the photodector is not nearly as critical when a monochromatic light source is used. In general, with the polychromatic tungsten filament lamp as a light source, the photomultiplier tube and the vacuum photodiode are more sensitive to the shorter wavelength light in the source, making them more sensitive to the detection of smaller particles. Conversely, the silicon photodiode is more sensitive to longer wavelengths in the light source, making it more suited for sensing larger particles. The sensitivity of the cadmium sulfide photoconductor is between the sensitivity of the photomultiplier tube and the silicon photodiode. 11.3 Turbidimeter Design Configurations Several instrument design standards have been developed by various organizations to attempt to standardize instrument designs and achieve test results that are accurate and repeatable. These standards govern the design of the various turbidimeter configurations available today, which include the single beam design, modulated four beam design, surface scatter design, and transmittance design. Only the single beam design, ratio design, and modulated four beam design are approved by EPA. April 1999 11 -3
EPA Method 180.1 lists the following design requirements for turbidimeters: "Light Source: Tungsten-filament lamp operated at a color temperature between 2200 and 3000 degree K. Distance traversed by incident light and scattered light within the sample tube not to exceed 10 cm. Angle of light acceptance by detector: Centered at 90 degrees to the incident light path and not to exceed +/- 30 degrees from 90 degrees. The detector, and filter system if used, shall have a spectral property between 400 and 600 nm (Standard Methods, 1995)."
EPA Guidance Manual Turbidity Provisions 11-4 April 1999 P.75
71. BASIC TURBIDIMETER DESIGN AND CONCEPTS The wavelength , X, of the incident radiation shall be 860 nm; The spectral bandwidth , AA., of the incident radiation shall be less than or equal to 60 nm; There shall be no divergence from parallelism of the incident radiation and any convergence shall not exceed 2.5 degrees; The measuring angle (tolerance on deviation of the optical axis) shall be o +/2.5 degrees The aperture angle, Q.Q, should be between 10 and 20 degrees in the water sample (ISO, 1990)."
ISO 7027 requires the use of monochromatic light sources such as tungsten lamps fitted with monochromators and filters, diodes, or lasers. However, the standard recognizes that many older instruments have polychromatic light sources, and allows their use for water treatment monitoring and control, but not for comparison to readings from other turbidimeters. The tighter definition ofthe light source in ISO 7027 eliminates many ofthe variables inherent to the polychromatic sources used in the other standards. However, ISO 7027 does not eliminate the effects of light source decay or electronic gains and drifts inherent in monochromatic sources such as LEDs (Lex, 1994). ISO 7027 is not accepted by
EPA for turbidity analysis for compliance with the IESWTR. 11.3.2 Single Beam Design The single beam design configuration, shown in Figure 11-3, is the most basic turbidimeter design using only one light source and one photodetector located at 90 degrees from the incident light. The single beam design is the oldest of the modern nephelometers and typically is used with a polychromatic tungsten filament lamp. The design is still in wide used today and yields accurate results for turbidity under 40 NTU, provided that samples have little natural color. In fact, many on-line instruments in use today still utilize the single beam design. The single beam design does, however, have limited accuracy at higher turbidities. As turbidity increases and the amount of scattered light Glass increases, multiple scattering can Sample Cell ,- Lamp occur when light strikes more than one particle as it reacts with Transmitted -*- Light the sample fluid. The resulting 90° Scattered scattered light intensity reaching Light ^Aperture Lens the 90 degree detector can - Detector diminish as the instrument effectively "goes blind." For Source: Sadar, 1996. this reason, a single beam design conforming strictly to EPA 180.1 Figure 11-3. Basic Nephelometer does not typically demonstrate April 1999 11-5
LIOHT DETECTOR Source: Sadar, 1996. Figure 11-4. Ratio Turbidimeter turbidity ofthe sample. A typical ratio mathematical algorithm is as follows (Standard
Methods, 1995): T= W (d0 * I, + d, * Ifs + d2 * Ibs + d3 * I90) Where: T = Turbidity in NTU d0, di, di, d3 = Calibration Coefficients I90 = 90 Degree Detector Current I, = Transmitted Detector Current IfS = Forward Scatter Detector Current Ibs = Back Scatter Detector Current The use of multiple photodetectors and the ratio algorithm gives the instrument much better performance with colored samples. The transmitted light and the 90-degree scattered light are affected almost equally by the color of the sample because they travel
EPA Guidance Manual Turbidity Provisions 11-6 April 1999 P.77
Hach Corporation. 1995. Excellence in Turbidity Measurement. Hach Corporation. International Organization for Standards (ISO). 1990. International Standard ISO 7027- Water Quality - Determination or Turbidity. ISO.
King, K. 1991. Four-Beam Turbidimeters for Low NTU Waters. Great Lakes Instruments.
Lex, D. 1994. Turbidity Technology Turns on the High Beams. Intech Engineer's Notebook. 41(6):36
Sadar, M.J. 1996. Understanding Turbidity Science. Technical Information Series Booklet No. 11. Hach Company.
Standard Methods. 1995. Standard Methods for the Examination of Water and
Wastewater, nineteenth edition. America Public Health Association, AWWA, Water Environment Federation. Franson, M.H., A.D. Eaton, L.S. Clesceri, and A.E. Greenberg (editors). American Public Health Association, AWWA, and Water Environment Federation. Port City Press, Baltimore, MD. April 1999 11-11
THIS PAGE INTENTIONALLY LEFT BLANK EPA Guidance Manual Turbidity Provisions 11-12 April 1999 P.83
EPA Guidance Manual Turbidity Provisions April 1999 P.85
EPA Guidance Manual Turbidity Provisions April 1999 P.87
EPA Guidance Manual Turbidity Provisions April 1999 P.89
EPA Guidance Manual Turbidity Provisions April 1999 P.91
Mathematically, pH is the logarithm (base 10) ofthe reciprocal ofthe hydrogen ion concentration, [H+]. pH = Log (1/H+) The pH may range from 0 to 14, where 0 is most acid, 14 most basic, and 7 neutral. Natural waters usually have a pH between 6.5 and 8.5. plug flow. A type of flow that occurs in tanks, basins or reactors when a slug of water moves through a tank without ever dispersing or mixing with the rest of the water flowing through the tank. polymer. A chemical formed by the union of many monomers (a molecule of low April 1999
EPA Guidance Manual Turbidity Provisions A-10 April 1999 P.93
METHODS FOR THE EXAMINATION OF WATER AND WASTEWATER. transient water system. A non-community water system that does not serve 25 of the same nonresident persons per day for more than six months per year. Also called a transient non-community water system (TNCWS). tube settler. A device that uses bundles of small bore (2 to 3 inches or 50 to 75 mm) tubes installed on an incline as an aid to sedimentation. The tubes may come in a variety of shapes including circular and rectangular. As water rises within the tubes, settling solids fall to the tube surface. As the sludge (from the settled solids) in the tube gains weight, it moves down the tubes and settles to the bottom of the basin for removal by conventional sludge collection means. Tube settlers are sometimes installed in April 1999 A-11
Caiabrese, E.J., CE. Gilbert, and H. Pastides, editors. 1988. Safe Drinking Water Act
California State University. 1988. Water Treatment Plant Operation. School of
Dzurik, A.A., Rowman, and Littlefield. 1990. Water Resources Planning. Savage, MD.
EPA Guidance Manual Turbidity Provisions A-12 April 1999 P.95
APPENDIX A. LIST OF DEFINITIONS USEPA. 1991a. Code of Federal Regulations, Title 40, Chapter I, Section 141.2. July 1.
EPA Guidance Manual Turbidity Provisions A-14 April 1999 P.97
NEPHELOMETRY METHOD 180.1 DETERMINATION OF TURBIDITY BY NEPHELOMETRY Edited by James W. O'Dell Inorganic Chemistry Branch Chemistry Research Division Revision 2.0 August 1993
EPA Guidance Manual Turbidity Provisions April 1999 P.99
APPENDIX B. DETERMINA TION OF TURBIDITY used to determine if method analytes or other interferences are present in the laboratory environment, the reagents, or the apparatus. April 1999
EPA Guidance Manual Turbidity Provisions April 1999
CAUTION - - CARCINOGEN 7.2.2 Dissolve 10.00 g hexamethylenetetramine (CASRN 100-97-0) in reagent water and dilute to 100 mL in a volumetric flask. In a 100 mL volumetric flask, mix 5.0 mL of each solution (7.2.1 + 7.2.2). Allow to stand 24 hours at 25 + 3°C, then dilute to the mark with reagent water. Primary calibration standards: Mix and dilute 10.00 mL of stock standard suspension (7.2) to 100 mL with reagent water. The turbidity of this suspension is defined as 40 NTU. For other values, mix and dilute portions of this suspension as required. 7.3.1 April 1999 A new stock standard suspension (7.2) should be prepared each month. Primary calibration standards (7.3) should be prepared daily by dilution of the stock standard suspension. Formazin in commercially prepared primary concentrated stock standard suspension (SSS) may be diluted and used as required. Dilute turbidity standards should be prepared daily.
QCS). 9.2.2 EPA Guidance Manual Turbidity Provisions Linear Calibration Range (LCR) - - The LCR must be determined initially and verified every 6 months or whenever a significant change in instmment response is observed or expected. The initial demonstration of linearity must use sufficient standards to insure that the resulting curve is linear. The verification of linearity must use a minimum of a blank and three standards. If any verification data exceeds the initial values by + 10%, linearity must be reestablished. If any portion of the range is shown to be nonlinear, April 1999
METHOD PERFORMANCE 14.0 April 1999 13.1 In a single laboratory (EMSL-Cincinnati), using surface water samples at levels of 26, 41, 75 and 180 NTU, the standard deviations were ± 0.60, ± 0.94, ± 1.2 and + 4.7 units, respectively. 13.2 The interlaboratory precision and accuracy data in Table 1 were developed using a reagent water matrix. Values are in NTU.
REFERENCES American Society for Testing and Materials (ASTM). 1993. Annual Book of ASTM Standards, Volume 11.01. Water (1), Standard D1889-88A, p. 359. West Conshohocken, PA,
Standard Methods. 1992. Standard Methods for the Examination of Water and Wastewater. Eighteenth Edition, pp. 2-9, Method 2130B.
ATL' HACH. CC. R.D. VANOUS & J.M. HEER. 1985. Understanding Turbidity Measurement. Hach Co.. Technical Information Ser.. Booklet 11. Loveland. Colo.
KATZ. E.L. 1986. The stability of turbidity in raw water and its relationship to chlorine demand. J. Amer. Water Works Assoc. 78:72.
MCCOY. W.F. & B.H. OLSON. 1986. Relationship among turbidity, particle counts and bacteriological quality within water distribution lines. Water Res. 20:1023. 0.05
BUCKLIN. K.E.. G.A. MCFETERS & A. AMIRTHARAJAH. 1991. Pene- When comparing water treatment efficiencies, do not estimate turbidity more closely than specified above. Uncertainties and discrepancies in turbidity measurements make it unlikely that results can be duplicated to greater precision than specified. 6. Reference tration of coliform through municipal drinking water filters. Water Res. 25:1013.
HERNANDEZ. E.. R.A. BAKER & P.C. CRANDALL. 1991. Model for evaluating turbidity in cloudy beverages. J. Food Sci. 56:747.
HART, V.S.. C.E. JOHNSON & R.D. LETTERMAN. 1992. An analysis of low-level turbidity measurements. J. Amer. Water Works Assoc. 84(12):40.
LECHEVALLIER. MW. & W.D. NORTON. 1992. Examining relationship 1. U.S. ENVIRONMENTAL PROTECTION AGENCY. 1993. Methods for Determination of Inorganic Substances in Environmental Samples. between particle counts and Giardia, Cryptosporidium, and turbidity. J. Amer. Water Works Assoc. 84(12):54. 2150 ODOR* 2150 A. Introduction 1. Discussion