3 - Oil and Other Hazardous Substances Pollution Control
Other documents for the same rulemaking (all, by stage)
References: 14 extracted, 0 linked to papers
ENVIRONMENTAL CONSERVATION (c) No later than December 30, 2007, the owner or operator shall ensure that measures for controlling corrosion in flow lines are undertaken, including, at a minimum, (1) a corrosion monitoring and control program consistent with Chapter VIII of Pipeline Transportation Systems for Liquid Hydrocarbons and Other Liquids (ASME B31.42002) adopted by reference in (b)(1) of this section; (2) unless a more stringent requirement is set out in this section, external corrosion control of buried or submerged flow lines consistent with NACE International’s Standard Recommended Practice-Control of External Corrosion on Underground or Submerged
Metallic Piping Systems, 2002 Edition (NACE, RP0169-2002), adopted by reference; (3) external corrosion control of aboveground flow lines by the application of a protective coating, by the use of corrosion-resistant alloys or by another method approved by the department, unless the operator demonstrates by test, investigation, or experience appropriate to the environment of the flow line segment, that the anticipated extent of corrosion will not affect the flow line’s fitness for service; and (4) a program designed to minimize internal corrosion, including, as appropriate, one or more of the following: (A) removal of foreign material by scraping or pigging; (B) treatment of residual water or dehydration; (C) injection of inhibitors, biocides, or other chemical agents; (D) removal of dissolved gases by chemical or mechanical means; (E) gas blanketing; (F) continuous internal coating or lining; or (G) another method approved by the department; and (d) No later than December 30, 2007, the operator shall (1) completely contain the entire circumference of the flow line and provide the interstitial space with a leak detection system approved by the department; or (2) have in place a preventative maintenance program that ensures the continued operational reliability of any flow line system component affecting quality, safety, and pollution prevention; the owner or operator shall ensure that the program, Register 240, January 2022
Code, Inspection, Repair, Alteration, and Rerating of In-service Piping Systems, Second Edition (API 570), adopted by reference in (d)(2) of this section; (3) “removed from service” means not in regular use for the service intended and not included in a regular maintenance and inspection program in accordance with (c) and (d) of this section. (4) “submerged” means located below the surface of waters of the state. (Eff.12/30/2006, Register 180; am 3/23/2017, Register 221) Authority:
Street NW, Washington, DC 20005-4070; phone (202) 682-8000; fax (303) 397-2740; website: http://www.api-ec.api.org. 18 AAC 75.055. Leak detection, monitoring, and operating requirements for crude oil transmission pipelines. (a) A crude oil transmission pipeline must be equipped with a leak detection system capable of promptly detecting a leak, including (1) if technically feasible, the continuous capability to detect a daily discharge equal to not more than one percent of daily throughput; (2) flow verification through an accounting method, at least once every 24 hours; (3) for a remote pipeline not otherwise directly accessible, weekly aerial surveillance, unless precluded by safety or weather conditions. (b) The owner or operator of a crude oil transmission pipeline shall ensure that the incoming flow of oil can be completely stopped within one hour after detection of a discharge. (c) If aboveground oil storage tanks are present at the crude oil transmission pipeline facility, the owner or operator shall meet the applicable requirements of 18 AAC 75.065, 18 AAC 75.066 and 18 AAC 75.075. (d) For facility oil piping connected to or associated with the main crude oil transmission pipeline, the owner or operator shall meet the requirements of 18 AAC 75.080. (Eff. 5/14/92, Register 122; am 12/30/2006, Register 180) Register 240, January 2022 Authority:
AS 46.04.070 18 AAC 75.065. Field-constructed aboveground oil storage tank requirements. (a) Unless the owner or operator must comply with a more stringent requirement set out in this section, the owner or operator of an oil terminal, crude oil pipeline, exploration, or production facility shall maintain and inspect each field-constructed aboveground oil storage tank consistent with the requirements, as appropriate of American Petroleum Institute’s (API) (1) Tank Inspection, Repair, Alteration, and Reconstruction, Fifth Edition, November 2014, Addendum 1, April 2018, and Addendum 2, May 2020 (API 653), adopted by reference; or (2) Installation, Operation, Maintenance, Inspection, and Repair of Tanks in Production Service, Sixth Edition, March 2020 (API STD 12R1) adopted by reference. (b) Inspection intervals for a field-constructed aboveground oil storage tank (1) may be reduced by the department 30 years; bolted; (A) for a field-constructed aboveground oil storage tanks older than (B) for a field-constructed aboveground oil storage tank that is riveted or (C) for a field-constructed aboveground oil storage tanks with a demonstrated structural, corrosion, or foundation problems; or (D) after a significant seismic event; (2) may be extended if a request to extend an initial internal tank inspection interval beyond 10 years is submitted to the department for review and is approved; the request must document that it is based on Table 6.1 of Tank Inspection, Repair,
Alteration, and Reconstruction (API 653), adopted by reference in (a) of this section; and (3) may be based upon risk-based inspection, as specified in Section 6.4.2.2.2 of Tank Inspection, Repair, Alteration, and Reconstruction, (API 653), adopted by reference in (a) of this section; the assessment must be signed by a registered engineer, and the inspection interval may not exceed 30 years. (c) An onshore elevated field-constructed aboveground oil storage tank whose configuration allows external inspection of more than 50 percent of the tank bottom is not required to undergo an internal inspection if Register 240, January 2022
Alteration, and Reconstruction, (API 653), adopted by reference in (a) of this section. (f) A field-constructed aboveground oil storage tanks served by an internal steam heating systems must be designed to control leakage through defective heating coils. Condensate lines must be monitored, passed through an oil separating device, or passed through a retention system. (g) An internal lining system installed and used to control corrosion or to meet the requirements of (h) of this section, must be installed in accordance with American Petroleum Institute’s (API). (1) Lining of Aboveground Petroleum Tank Bottoms, First Edition, 1991, (API
RP 652) adopted by reference, for internal lining systems installed before December 30, 2008;
Tanks, Fourth Edition, September 2014 (API RP 651), adopted by reference, with the exception that these requirements do not apply to elevated tanks, a cathodic protection system must be Register 240, January 2022
ENVIRONMENTAL CONSERVATION (i) designed by a corrosion expert; (ii) installed under the supervision of a corrosion expert; (iii) installed, operated, and maintained in accordance with Application of Cathodic Protection to Control External Corrosion of Carbon Steel On-Grade Storage Tank Bottoms (NACE SP0193-2016), adopted by reference in (h) of this section; a corrosion expert or qualified cathodic protection tester shall perform a cathodic protection survey specified under that standard; or (B) a corrosion control system approved by the department as an alternate to the cathodic protection system described in (A) of this paragraph, unless determined not necessary by an evaluation conducted by a corrosion expert consistent with Chapter 5 of the American Petroleum Institute’s (API) Cathodic Protection of Aboveground Petroleum Storage Tanks, Fourth Edition, September 2014 (API RP 651), adopted by reference in (A) of this paragraph. (Eff. 5/14/92, Register 122; am 5/26/2004, Register 170; am 12/30/2006, Register 180; am 3/23/2017, Register 221; am 11/18/2021, Register 240) Authority:
Washington, DC 20005-4070; phone (202) 682-8000; fax (303) 397-2740; website: http://www.api.org ; NACE International Headquarters, 15835 Park Ten Place, Houston, Texas 77084; phone (281) 228-6200; fax (281) 228-6300; website: http://www.nace.org. As of Register 209 (April 2014), and acting under AS 44.62.125(b)(6), the regulations attorney made technical revisions to 18 AAC 75.065(d) and (i). 18 AAC 75.066. Shop-fabricated aboveground oil storage tanks. (a) The owner or operator of a shop-fabricated aboveground oil storage tank placed in service: this section; (1) on or before December 30, 2008 shall meet the requirements of (f) - (h) of (2) after December 30, 2008 and before May 17, 2022 shall meet the requirements of (b) – (h) of this section; or section. (3) on or after May 17, 2022 shall meet the requirements of (c) – (i) of this Register 240, January 2022
Distribution Piping Systems, 2003 Edition (ASME B31.8-2003), adopted by reference; (4) another equivalent standard approved by the department. (d) The owner or operator shall ensure that buried metallic facility oil piping placed in service between May 14, 1992 and December 30, 2008, is protected from corrosion by installing protective coating and cathodic protection appropriate for local soil conditions and is of all welded construction with no clamped, threaded, or similar connections for lines larger than a one inch nominal pipe size. (e) The owner or operator shall ensure that buried facility oil piping placed in service after December 30, 2008 (1) is of all welded construction with no clamped, threaded, or similar connections for lines larger than one inch nominal pipe size; and department, is (2) unless constructed of a corrosion-resistant material approved by the Register 240, January 2022
ENVIRONMENTAL CONSERVATION (A) protected from corrosion by installing protective coating; and (B) cathodically protected in accordance with (f) of this section. (f) The owner or operator shall ensure that, after December 30, 2008, cathodic protection systems installed on facility oil piping are (1) consistent with NACE International’s, Standard Recommended PracticeControl of External Corrosion on Underground or Submerged Metallic Piping Systems, 2002 Edition (NACE RP0169-2002), adopted by reference; (2) designed by a corrosion expert; and (3) installed under the supervision of a corrosion expert; (g) The owner or operator shall ensure that, if a piping segment of a buried facility oil piping installation is exposed for any reason, the segment is carefully examined, for damaged coating or corroded piping in accordance with Section 9.2.6 of Piping Inspection Code,
Inspection, Repair, Alteration, and Rerating of In-service Piping Systems (API 570), adopted by reference in (j) of this section, if active corrosion is found during that examination, of this section. (1) the owner or operator shall implement actions for control of future corrosion; (2) significant repairs or replacements must meet the requirements of (c) and (e) (h) An owner or operator or a buried facility oil piping installation of metallic construction without cathodic protection shall ensure that the piping (1) is electrically inspected by a corrosion expert for active corrosion at least once every three years, but with intervals between inspections not exceeding 39 months; and (2) in areas in which active corrosion is found, cathodically protected in accordance with (d) or (f) of this section, as appropriate; (i) The owner or operator shall ensure that aboveground facility oil piping is supported consistent with the requirements of Paragraph 321 of Process Piping, (ASME B31.3-2004), adopted by reference in (c) of this section. (j) After December 30, 2007, unless the owner or operator must comply with a more stringent requirement set out in this section, the owner or operator shall ensure that all facility oil piping is maintained and inspected under Register 240, January 2022