US EPA. 1999b. Technologies and Costs for the Removal of Arsenic from Drinking Water. Prepared by International Consultants, Inc. and Malcolm Pirnie, Inc. under contract 68-C-C6–0039 with EPA OGWDW. April 1999. 392 pages [W-99-16-III-B-140]
Other documents for the same rulemaking (all, by stage)
References: 138 extracted, 0 linked to papers
TDS/As Ratio: NR 2,800 Hathaway and Rubel (1987)
Fox (1989) Ionac ASB-1 Dowex 11 Bed Volume: 0.014 cu ft Flowrate: NR
TDS/As Ratio: 9200:1 400-500 (projected if oxidation to As(V)is preformed) Clifford and (1985) • A-300E (bench-scale) . A-300E (full-scale) Bed Volume: 0.0018 cu ft Flowrate: 0.035 gpm
NR = Not Reported 2.4.6 Secondary Effects Chloride-formresinsare often used in arsenic removal. Chloride ions are displaced from the column as contaminants (arsenic) are sorbed onto the column. As a result, the potential exists for increases in the chloride concentration of the product water. Increases in chlorides can greatly increase the corrosivity of the product water. Chlorides increase the corrosion potential of iron and as a result increase the potential for red water problems (EPA, 1995). Corrosion problems are 2-23 worsened when high chloride levels are intermittent. In situations where chlorides pose a problem, demineralization, blending, or alternate treatment techniques may be required.
Second, spent brine can be treated by precipitation. Clifford and Lin (1995) have shown that arsenic levels can be substantially reduced using iron and aluminum coagulants as well as lime. Much greater than the stoichiometric amounts (up to 20 times as much), however, are needed in actual practice to reduce arsenic to low levels. In addition, pH adjustment may be necessary to ensure optimum coagulation conditions. Reductions from 90 mg As(V)/L to less than 1.5 mg As(V)/L have been seen using iron and aluminum metal salts (Clifford and Lin, 1995). Both coagulant types seem to work well, however, iron precipitates tend to settle better due to their weight. Dried sludge from brine reduced to 1.5 mg As(V)/L using precipitation passed an EP toxicity test with only 1.5 mg/L As(V) in the leachate. In this situation, dried sludge could have been disposed of in a landfill. Reuse of decontaminated regenerant has yet to be evaluated, however, the possibility of reuse does exist. 2-25 2.4.10
EBCT A few studies have been performed to test the effect of EBCT on IX performance. Clifford and Lin (1986) reduced EBCT from 5 to 1.4 in a Hanford, CA study and found no significant reduction in arsenic removal performance. In a recent AWWARF study, four IX columns were run with EBCTs varying between 2.5 and 15 minutes. Data from this study show that the shorter the
EBCT, the more BVs can be treated before breakthrough. The disadvantage to shorter EBCT, however, is increasedregenerationfrequency.Based on these data, shorter EBCTs may be preferred to reduce capital costs (AWWARF, 1998). 2.4.11 Typical Design Parameters Through extensive research, Clifford and others (1998) assembled typical operating parameters and suggested options for ion exchange processes. Although many design parameters should be tailored to the specific treatment situation, Table 2-2 gives typical values and options.
MEMBRANE PROCESSES 2.5.1 Introduction Membranes are a selective barrier, allowing some constituents to pass and blocking the passage of others. The movement of constituents across a membrane requires a driving force (Le. a potential difference between sides of the membrane). Membrane processes are often classified by the type of driving force, including pressure, concentration, electrical potential and temperature. The processes discussed here include only pressure-driven and electrical potential-driven types. Pressure-driven membrane processes are often classified by pore size into four categories: microfiltration (MF), ultrafiltration (UF), nanofiltration (NF), and reverse osmosis (RO). Typical pore size classification ranges are given in Figure 2-1. High-pressure processes (Le., NF and RO) have a relatively small pore size compared to low-pressure processes (Le., MF and UF). Typical pressure ranges for these processes are given in Table 2-3. NF and RO primarily remove constituents through chemical diffusion (Aptel and Buckley, 1996). MF and UF primarily remove constituents through physical sieving. An advantage of high-pressure processes is that they tend to remove a broader range of constituents than low-pressure processes. However, the drawback to broader removal is the increase in energy required for high-pressure processes.
AWWARF (1998) performed bench-scale tests on two low-MWCO UF membranes. Single element testing was performed on Desai GM and FV UF membranes for a spiked, deionized water. Flat sheet testing was also performed on Desai GM, FV, and PM UF membranes for spiked, deionized water. Since the samples were spiked, no particulate or colloidal arsenic was present. Results of this study are given in Table 2-5.
Fox, 1989 Fox and Sorg, 1987 Eugene, OR 3-5 gpd 67% recovery 195 psi below MDL
Fox, 1989 Fox and Sorg, 1987 Fairbanks, AL low-pressure (< 100 psi)
Fox, 1989 Fox and Sorg. 1987 San Ysidro, NM Pilot (hollow fiber, cellulose acetate) 50% recovery pH adjustment to 6.3 antiscalent addition 93-99% Clifford and Lin, 1991 San Ysidro, NM Pilot (hollow fiber, polyamide) 50% recovery pH adjustment to 6.3 antiscalent addition Clifford and Lin, 1991 San Ysidro, NM 10-15% recovery
Fox, 1989 Fox and Sorg, 1987 Tarrytown, NY Pilot (FilmTec BW30, Hydranautics NCM1, Fluid Systems TCFL) 15 gfd 10% recovery below MDL
Malcolm Pirnie, 1992 Tarrytown, NY Rogers, 1989 B Charlotte | Harbor, FL (several membrane As(V) 96-99% As(m) 46-84%
Cincinnati, OH As(IH) 73% Fox and Sorg, 1987
Hudson, NH USEPA. 1982 NA: Not Available 2-37
MWCO Source Water Speciation As Rejection 1 Single Element DK2540F Deionized DK2540F Lake Water DK2540F Deionized DK2540F Lake Water Flat Sheet DK2540F Deionized These results indicate very high rejection for As(V) but very low rejection for As(III) at neutral pH. Again, this points to the fact that oxidation conditions would be desirable and that surface charge/electrostatic repulsion probably plays a role in arsenic rejection. Also, flat sheet testing produced arejectionrate comparable, and slightly conservative, to the single element rejection rate. Several RO pilot-scale tests were also performed (AWWARF, 1998). Two tests were performed on high- and low-DOC groundwaters. Another set of tests was performed on spiked, finished surface water. The resultsfromthese pilot tests are summarized in Table 2-11. Table 2-11 shows substantial rejection for both the low- and high-DOC waters. Rejection was only slightly higher with the high DOC water. As with UF and NF,fluxand recovery changes did not seem to affect arsenicrejection.Results for the four membranes tested on spiked finished water also showed substantial removal. For all membranes during this test, As(V) exceeded 95 percent, however, As(III) rejection averaged only 74 percent. 2-38 P.68
ENR Materials Prices 2189.24 BLS numerical values were re-based to 1967 base year (see Section 3.2.5) Table 3-8 Unit and General Cost Assumptions Electricity1 $0.08/kWh Diesel Fuel1 $1.25/gallon Natural Gas1 $0.006/scf Labor2 Large systems: Small systems: Very small systems: Building Energy Use 102.6 kWh/sq ft/yr Housing Costs $125/S4ft Energy Information Administration. Technical Design Panel (EPA, 1998a) $40/hr S28/hr 8 hrs/wk P.85
Brandhuber (1998). "Arsenic Rejection by Nanofiltration and Ultrafiltration Membranes: Arsenic Forms vs. Membrane Properties," AWWA Inorganic Contaminants
Workshop, San Antonio, TX, February 23-24, 1998.
Aptel, P. and C A Buckley (1996). "Categories of Membrane Operations," Chapter in Water Treatment Membrane Processes, McGraw Hill, 1996. American Water Works Research
Foundation, Lyonnaise des Eaux, Water Research Commision of South Africa, 1996.
AWWA (1990). Water Quahty and Treatment - A Handbook of Community Water Svstems. McGraw-HiU Publishing Company, New York.
AWWA (1997). Arsenic Regulation. USEPA, Office of Ground Water and Drinking Water, October 1997.
AWWARF (1996) - Water Treatment Membrane Processes, McGraw-HiU Publishing Company, New York.
AWWARF (1998). Arsenic Treatability Options and Evaluation of Residuals Management Issues,
Amy, G.L., M. Edwards, M. Benjamin, K. Carlson, J. Chwirka, P. Brandhuber, L. McNeiU and F. Vagliasindi, Draft Report, April 1998.
Bellack, E. (1971). "Arsenic Removal from Potable Water," J. AWWA, 63:7:454-458.
Bennett (1996). "Sorption and Filtration of Metals Using Iron-Oxide Coated Sand," Water Research, 30:11:2609.
Bennett (1998). "Sorption of Arsenic by Various Adsorbents," AWWA Inorganic Contaminants Workshop, San Antonio, TX, February 23-24, 1998. Cadmus Group, Inc. (1998). Cost Evaluation of Small System Compliance Options - Point-of-Use and Point-of-Entrv Treatment Units, Prepared for USEPA Office of Ground Water and Drinking Water.
CH2M HiU (1998). Telephone conversation with Joseph Chwirka, CH2M HiU, Albuquerque, New Mexico.
Ruiz (1994). "Removal of Arsenic by Enhanced Coagulation and Membrane Technology," Proceedings AWWA Annual Conference, New York.
Edwards (1998). "Raw Water Quahty and Arsenic Treatment," Submitted for Pubhcation in J. AWWA.
Edwards (1996). "Speciation of As in US Waters," Poster Session AWWA Annual
Yang (1994). "Arsenic Species in Groundwaters ofthe Blackfoot Disease Area, Taiwan," Environmental Science and Technology, 28:5:877.
Beuhler (1994). "Enhanced Coagulation for Arsenic Removal," J. AWWA, 9:79-90.
Chow (1983). "As (III) and As (V) Separation by Chloride-Form Ion Exchange Resins," Proceedings AWWA WQTC, Norfolk, Virginia.
Lin (1985). Arsenic (UI) and Arsenic (V) Removal From Drinking Water in San
Lin (1986). Arsenic Removal From Groundwater in Hanford, California - A Preliminary Report, University of Houston, Department of Civil/Environmental Engineering. Cited in: AWWA (1990). Water Quality and Treatment - A Handbook of Community Water
Clifford, D. (1994). "Computer Prediction of Arsenic Ion Exhange," J. AWWA, 86:4:10.
Lin (1995). "Ion Exchange, Activated Alumina, and Membrane Processes for Arsenic Removal from Groundwater," Proceedings of the 45* Annual Environmental Engineering Conference, University of Kansas, February 1995.
Tripp (1998). "Arsenic Removal by Ion Exchange With and Without Brine Reuse," AWWA Inorganic Contaminants Workshop, San Antonio, TX, February 2324, 1998. Culp/Wesner/Culp (1979). Estimating Water Treatment Costs, Volume 2: Cost Curves Apphcable to 1 to 200 mgd Treatment Plants, CWC Engineering, San Clemente, California. Culp/Wesner/Culp (1984). Estimation of SmaU System Water Treatment Costs, CWC Engineering Software (for USEPA), San Clemente, California. Culp/Wesner/Culp (1994). WATERCO$T Model - A Computer Program for Estimating Water and Wastewater Treatment Costs (Version 2.0), CWC Engineering Software, San Clemente, California.
Tikkanen (1994). "Nationwide and California Arsenic Occurrence Studies," Published in Arsenic Exposure and Health, Chapman and Hall Publishing Company, pp. 31-40. P.87
DPRA, Inc. (1993a). Smah Water System Byproducts Treatment and Disposal Cost Document, Prepared for USEPA Office of Ground Water and Drinking Water.
DPRA, Inc. (1993b). Water System Byproducts Treatment and Disposal Cost Document, Prepared for USEPA Office of Ground Water and Drinking Water.
Hildebrandt (1998). "Granular Ferric Hydroxide - A New Adsorbent for the Removal of Arsemc from Natural Water," J. Water SRT - Aqua, 47:1:30-35.
Edwards, M.A. (1994). 'Chemistry of Arsenic Removal During Coagulation and Fe-Mn Oxidation," J. AWWA, September 1994, pp. 64-77.
Taylor II (1998). "Considerations in Arsenic Analysis and Speciation," J. AWWA, 90:3:103.
Hayes (1980). "Removal of Arsenic from Contaminated Drinking Water by Chitosan/Chitin Mixture," Water Research, 14:1307.
EPA (1989). SAB Review of Arsenic Issues Relating to the Phase II of Proposed Regulations from the ODW. EPA SAB-EHC-89-038.