Tuesday, November 20, 2001 P.27 Morgantown, WV. Interim Release - May 1996. Response to Public Comment: CWA Section 316(b) New Facility Rule-Final Author ID: 316bNFR.039 Page 612 of 2970
Tuesday, November 20, 2001 P.28 Comment ID 316bNFR.039.042 Author Name Robert S. Kripowicz
EEA - Estimation of Unit Costs Fish Spray Pumps Table A-26 provides two equations for estimating the capital costs of fish spray pumps, which differ in whether a third-order term is present. The book, Plant Design and Economics for Chemical Engineers (Peters & Timmerhaus, 1968) indicates that a power law representation ofthe capital cost of centrifugal pumps would be more appropriate. Figure 4 {see attachment 316bNFR039_Figures} provides correlation of capital cost data for centrifugal pumps (horizontal, split-case, single-stage) taken from page 522 of the U .S. Army Corp of Engineer's Unit Price Book 2000, Volume I. We suggest that EPA consider this already-published costing equation.
Tuesday, November 20, 2001 P.29 Comment ID Subject Matter Code 316bNFR.039.043 21.1 Facility-incurred Costs as a Result of Compliance with Proposed Rule Author Name Robert S. Kripowicz
Organization U.S. Dept. of Energy Cooling Tower Installation Costs Page AppA-16 of the report notes that "Based on discussions with industry representatives, EPA estimated installation costs as 80 percent of cooling tower equipment cost." It is unclear why alternative sources of cost data, such as the U.S. Army Corps of Engineers' Unit Price Book 2000 were not applied. The assumption that installation is 80 percent of equipment cost may not be valid and may lead to excessively high capital costs. Table 5 <listed below> provides capital cost data for centrifugal-type, packaged unit cooling towers based upon the above-cited reference. Table 5- Capital Cost of Centrifugal-Type Cooling Towers, Packaged Units Heat Rejection (tons) Ton-Btu/hr Range (<deg>F) Flow (gpm) Capital Cost ($) 1,000 12,000 12,000 12,000 12,000 12,000 12,000 12,000 12,000 12,000 12,000 12,000 12,000 1200 1800 2400 4800 7200 9600 12000 14400 16800 19200 21600 24000 6800 8900 10600 16500 22900 27200 34900
Tuesday, November 20, 2001 P.93 Burns, J.M. Micheletti, W.C. Comparison of Wet and Dry Cooling Systems for Combined Cycle Power Plants. November 4, 2000
Hensley, J.C. Undated. Cooling Tower Fundamentals. 2nd Edition. The Mariey Cooling Tower Company (Mission, Kansas) 1985.
Kaplan, Charles. Memo to Martha Segall. April 18, 2000. Subject: Flow Reduction. (Water Docket #1-1073-TC) Response to Public Comment: CWA Section 316(b) New Facility Rule-Final Author ID: 316bNFR.068 Page 1535 of 2970
Tuesday, November 20, 2001 P.94 Comment ID Subject Matter Code 316bNFR.068.331 Author Name Terry M. Hogan & David E. Bailey Organization Utility Water Act Group c/o Hunton & Williams 21.1 Facility-incurred Costs as a Result of Compliance with Proposed Rule
Tuesday, November 20, 2001 P.95 significantly more complicated than the winter operation of a wet cooling tower. As a result, the costs of dry cooling systems are significantly greater. During extremely cold periods, operators of dry cooling towers must run the turbine at a higher backpressure than they would normally to prevent the tubes from freezing. Operating this way leads to inefficient plant use. To avoid such measures, dry towers would require special winterization measures and would probably involve a more complex
Nuclear. 1972. Entergy Nuclear Generation Company (Entergy). 2001. Condenser Performance Analysis Additional Data; Pilgrim Nuclear Power Station. Submitted by J.F. Alexander, to Nicholas Prodany,
EPA Region 1. February 26, 2001. Taylor, Stu. Bechtel. Telephone contact with John Sunda. SAIC. May 11, 2001.
Fleming, Robert. 2001. Personal communications between Robert Fleming, The Mariey Cooling Tower Co., and Faysal Bekdash, SAIC.
Hess, Dale. Graham Corporation. "Condenser Cost Study" June, 25, 2001. Response to Public Comment: CWA Section 316(b) New Facility Rule-Final Author ID: 316bNFR.501 Page 2100 of 2970
Tuesday, November 20, 2001 Comment ID 316bNFR.501.025 Author Name Robert S. Kripowicz
Tuesday, November 20, 2001 In terms of S02, given the requirement for BACT and the "cap" on S02 emissions, DOE recommends that EPA assume 95 percent or greater S02 capture. EPA will still need to specify the coal-sulfur content in order to estimate increases in emissions. DOE recommends that the Agency assume the use of coal commonly used by existing scrubbed plants from nearby regions. Regarding primary particulate emissions, DOE recommends that EPA estimate increases in emissions based on the plant having a state-of-the-art electrostatic precipitator (ESP) or fabric filter installed.
DOE recommends that the September 1998 AP-42 collection efficiencies for ESPs (99.2 percent) and baghouses (99.8 percent) are appropriate to use in estimating potential increases in particulate emissions. From an emissions standpoint, mercury is a special case with its own set of issues and questions. EPA needs to elaborate on how it will handle mercury. Since there still remains significant uncertainty about how well mercury is removed from combustion flue gas, DOE recommends that the Agency not use existing emissions factors. EPA has just recently completed a mercury Information Collection Request (ICR) in which they have collected data on mercury emissions from power plants, both pulverized coal and IGCC facilities. Does EPA intend to use this data in estimating increases in mercury emissions from power plants? If the power plant is equipped with a wet scrubber, will the