Occurrence Assessment for the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules EPA Document No. 815-R-00-019 [W-99-10-II-B-49]
Other documents for the same rulemaking (all, by stage)
References: 1,178 extracted, 0 linked to papers
January, 2001 5-73 P.12 Occurrence Assessmentfor the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules
January, 2001 5-74 P.13 Occurrence Assessment for the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules hydroxide, ferric carbonate, or manganese dioxide. Further sedimentation orfiltrationprocessesthenremove the precipitates (AWWA/ASCE 1998).
EE&T (1999) reported that only one study, by Wang et al. (1973), addressed the impacts of FBR on inorganic finished water quality. Cornwell and Lee (1993) studied the effects of filter backwash on the concentrations of inorganics in water treatment process streams. The ranges of inorganics, including manganese, iron, aluminum, copper, and arsenic, in filter backwash and related process streams were reviewed by EE&T (1999) and are summarized in Table 5-16. Table 5-15. Summary of Cryptosporidium and Giardia Occurrence in Process Streams Pathogen Cryptosporidium
January, 2001 Total Concentration Range (oocysts or cysts/1 OOL) Number Samples Untreated spent filter backwash
ND-750 n>50 Cornwell and Lee 1993b; Karanis etal. 1995; Karanis etal. 1998 Untreated sediment basin sludge 2,642 Cornwell and Lee 1993b Thickener supernatant 82-420 Cornwell and Lee 1993b Sludge drying bed decant and overflow <210 Cornwell and Lee 1993b Process Stream Comments References Three of five studies reported oocysts >15,000/ 100L Cornwell and Lee 1993b; LeChevallier etal. 199 Id; States et al. 1995; LeChevallier et al. 1998; Rose 1989, as cited in EE&T 1999 5-75 P.14 Occurrence Assessment for the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Total Concentration Range (oocysts or cysts/1 OOL) Number Samples Untreated spent filter backwash
ND-374 n>50 Cornwell and Lee 1993b; Karanis etal. 1995 Untreated sediment basin sludge 5,284 Cornwell and Lee 1993b Thickener supernatant
ND-71 Cornwell and Lee 1993b Cornwell and Lee 1993b Pathogen Giardia Process Stream Sludge drying bed decant and overflow Comments References Two of five sources reported cysts > 10,000/ 100L Cornwell and Lee 1993b; LeChevallier etal. 199 Id; States et al. 1995; LeChevallier et al. 1998; Rose 1989, as cited in EE&T 1999
ND = None detected or below method detection Source: EE&T 1999. Manganese Concentrations of total manganese detected in untreated sedimentation basin sludge range from 0.34 to 865 mg/L; dissolved manganese ranges from 1.2 to 7.28 mg/L (EE&T 1999). Hoehn et al. (1987) collected sludge samplesfroma mechanically cleaned basin at the Lee Hall plant on three occasions (March,
AWWSC 1998 GAC transport water from a filter absorber 25.8108.0
AWWSC 1998 Untreated spent filter backwash O.001 0.85 n>50 LeChevallier et al. 1998 and
AWWSC 1998 Treated spent filter backwash AWWSC 1998 0.0045 15.44 n=234 Cornwell et al. 1992, Schmitt and Hall 1975, Cornwell 1986, Wortel and Koppers 1989, Koppers et al. 1985, and AWWSC 1998 Sedimentation basin sludgetreated supernatant Dissolved Pump packing water Untreated sedimentation basin sludge
AWWSC 1998 Table 5-16. Summary Inorganic Contaminant Occurrence in Process Streams (continued) Inorganic Contaminant Arsenic (continued) Copper Concentration Range (mg/L) Total Number Samples Thickener supernatant <0.001
AWWSC 1998 Lagoon decant <0.001 AWWSC 1998 Mechanical dewatering device <0.05-0.70
AWWSC 1998 Reverse osmosis membrane concentrate O.005-17.4 n=14 Snoeyink et al. 1984 Sludge drying bed decant and underflow 0.06-19.5 Pump packing water 0.001
AWWSC 1998 GAC transport water from a filter absorber <0.001-0.050
AWWSC 1998 Process Stream Untreated spent filter backwash Dissolved Comments References n=13 Wortel and Koppers 1989 <0.1 Treated spent filter backwash <0.01 Wang and Yang 1975 and
AWWSC 1998 Untreated sedimentation basin sludge <0.01-18.53 n=235 Cornwell and Vandermeyden 1992, Schmitt and Hall 1995, Cornwell et al. 1981, Wortel and Koppers 1989, Koppers et al. 1985, and AWWSC 1998 Table 5-16. Summary Inorganic Contaminant Occurrence in Process Streams (continued) Inorganic Contaminant Copper (continued) Cone. Range (mg/L) Total Number Samples Sedimentation basin sludge-treated supernatant
AWWSC 1998 Thickener supernatant <0.01 AWWSC 1998 Process Stream Dissolved Comments References Lagoon decant <0.01
AWWSC 1998 Mechanical dewatering device concentrate <0.01 0.340
AWWSC 1998 Sludge drying bed decant and underflow
AWWSC 1998 5.2 - 9.0 AWWSC 1998 <0.01 17.9 n>50 Cornwell and Lee 1993 b, Grubb and Arnold 1997, Klezcewski 1997, LeChevallier et al. 1998, and AWWSC 1998 Untreated spent filter backwash
GAC transport water Manganese Comments Dissolved Reverse osmosis membrane concentrate Mechanical dewatering device concentrate Number Samples 0.150.75 Treated spent filter backwash <0.02 0.92 <0.02 • Untreated sedimentation basin sludge 1.2-7.28 0.34865 n=27 Cornwell and Lee 1993b, Wang and Yang 1975, Klezcewski 1997, and
AWWSC 1998 Cornwell and Lee 1993b, Schmitt and Hall 1975, Cornwell 1986, Cornwell et al. 1981, Such et al. 1988, and
AWWSC 1998 Table 5-16. Summary Inorganic Contaminant Occurrence in Process Streams (continued) Inorganic Contaminant Manganese (continued) Cone. Range (mg/L) Process Stream Comments References Dissolved Total Sedimentation basin sludge-treated supernatant 0.263.08 0.26186.0 Cornwell and Lee 1993b and
AWWSC 1998 0.01 Snoeyink et al. 1984 Reverse osmosis membrane concentrate Number Samples Lagoon decant 0.62 <0.01 0.70 The upper ends of both total and dissolved manganese ranges are high. Cornwell and Lee 1993b and
AWWSC Mechanical dewatering device concentrate 5.2112.2 3.4731.45 n=15 Both total and dissolved manganese concentrations were very high. Cornwell and Lee 1993b, Such etal. 1998, and
AWWSC 1998 Sludge drying bed decant and underflow 0.0512.34 n=17 Pump packing water <0.01
ND = None detected or below detection level Source: EE&T 1999. Vandermeyden and Cornwell 1998 and Wortel and Koppers 1989
January, 2001 5-86 P.25 Occurrence Assessmentfor the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Total Organic Carbon
TOC in Process Streams EE & T (1999) reviewed occurrence data for TOC in water treatment process streams. These data are summarized in Table 5-17. Observed TOC concentrations in untreated spent filter backwash water ranged from 2.9 to 41.9 mg/L. TOC apparently concentrates in settled solids (untreated sedimentation basin sludge contains 8.7 to 245 mg/L TOC). Cornwell and Lee (1993b) sampled several plants for TOC in the waste streams and within the treatment process. Several streams showed elevated TOC levels; however, most ofthe TOC was associated with the solids and readily settled out. TOC levels in some streams were higher than 200 mg/L, which could impact the formation of DBP if the solids are not settled out prior to recycling. Filtered water TOC levels were not affected by recycling at the plants studied.
January, 2001 5-87 P.26 Occurrence Assessmentfor the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Table 5-17. Summary of Total Organic Carbon Occurrence in Process Streams Total Concentration Range (mg/L) Number of Samples Untreated spent filter backwash 2.9-41.9 n>50 Cornwell and Lee 1993b, Ashcroft etal. 1997, Nieminski 1997, LeChevallier etal. 1998, and
AWWSC 1998 Treated spent filter backwash 2.1-9.9 Cornwell and Lee 1993b and Ashcroft etal. 1997 Untreated sedimentation basin sludge 8.7-245 Cornwell and Lee 1993b Sedimentation basin sludge-treated supernatant 5.1-15.1 Cornwell and Lee 1993b Thickener supernatant 2.1-4.4 Cornwell and Lee 1993b Reverse osmosis membrane concentration 27-33 Nelson and DiGiano 1996 5.8-14.3 Process Stream Lagoon decant
January, 2001 5-88 P.27 Occurrence Assessmentfor the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Ashcroft et al. (1997) collected data during upgrades to the Big Cottonwood and Little Cottonwood Water Treatment Plants in Salt Lake City to evaluate the performance ofthe new water recovery facilities with respect to removal of pathogens, TOC, THM, and TTHMFP. The TOC concentration in backwash water was generally higher at the Little Cottonwood plant, which could be attributed to its source water. In this study, TOC removal through the settling of backwash water was minimal, and the use of polymers in the recovery water did not make a significant difference in the TOC concentration (Ashcroft et al. 1997). Hoehn et al. (1987) reported significant releases of TOC from sludges held in manually cleaned sedimentation basins. Sludges collected from a mechanically cleaned basin at the Lee Hall plant on three occasions (March, April, and June) represented the transition period from winter to summer conditions (when biological activity in the reservoir began to accelerate). The TOC concentrations in the water above the experimental jars containing sludges collected in March remained reasonably constant (4 to 6 mg/L) during the storage period, whereas the TOC concentrations increased markedly, to nearly double that range, in the water that overlay the sludges collected in June (8 to 11 mg/L).
January, 2001 5-89 P.28 Occurrence Assessment for the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Assimilable Organic Carbon
January, 2001 5-90 P.29 Occurrence Assessmentfor the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules the water treatment process. EE&T (1999) reviewed occurrence data for DBPs in water treatment process streams; these data are summarized in Table 5-18. Three treatment alternatives have been identified for controlling DBPs: removal of organic matter (TOC) prior to disinfection; use of alternative (nonchlorine) disinfectants; and removal of DBPs following their formation. Because THMs can be used as indicators of DBP presence in process or recycle streams, they are the focus ofthe discussion of DBPs. Table 5-18. Summary of Disinfection Byproduct Occurrence in Process Streams Total Concentration Range (mg/L) Number Samples Total Untreated spent trihalomethanes filter backwash (TTHM) O.002- 0.146 n>50 Treated spent filter backwash 0.029-0.118 Cornwell and Lee l-993bvand
AWWSC 1998 Untreated sedimentation basin sludge
AWWSC 1998 0.091-0.197 Sedimentation basin sludgetreated supernatant Cornwell and Lee 1993b and
AWWSC 1998 5-91 P.30 Occurrence Assessment for the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Disinfection Byproduct Total trihalomethane formation potential (TTHMFP)
January, 2001 Total Concentration Range (mg/L) Number Samples Mechanical dewatering device 0.128-0.276 Cornwell and Lee 1993b Pump packing water 0.030
AWWSC 1998 GAC transport waterfroma filter absorber 0.031-0.063
AWWSC 1998 Untreated spent filter backwash 0.135-0.465 Treated spent filter backwash 0.084-0.658 Cornwell and Lee 1993b and Ashcroft 1997 Untreated sedimentation basin sludge 0.209 - 2.032 Cornwell and Lee 1993b Sedimentation basin sludgetreated supernatant 0.270 - 0.686 Cornwell and Lee 1993b Thickener supernatant 0.170 - 0.259 Cornwell and Lee 1993b Lagoon decant Mechanical dewatering device 0.397-0.499 Process Stream Comments The upper end of the
TTHMFP levels were similar to those of source water. References Cornwell and Lee 1993b and Ashcroft et al. 1997 Cornwell and Lee 1993b Cornwell and Lee 1993b 5-92 P.31 Occurrence Assessmentfor the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Disinfection Byproduct Total Concentration Range (mg/L) Number Samples Untreated spent filter backwash <0.001-0.185 n>40 LeChevallier et al. 1998 and
AWWSC 1998 Treated spent filter backwash 0.20-0.67
AWWSC 1998 Untreated sedimentation basin sludge Sedimentation basin sludgetreated supernatant 0.059
AWWSC 1998 GAC transport water from a filter absorber 0.0024-0.053
AWWSC 1998 Process Stream Comments References
AWWSC 1998 ND = None detected or below detection level Source: EE&T 1999.
January, 2001 5-93 P.32 Occurrence Assessment for the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Total Trihalomethanes
TTHM in Process Streams Cornwell and Lee (1993b) evaluated TTHM and TTHMFP in several treatment facilities and on different types of process streams. In general, it was found that if the solids are removed from the recycle stream prior to recycling, TTHMFP in recycle is no higher than in the raw water. However, without solids removal, TTHMFP can increase in the recycle streams. The recycled streams can contain pre-formed THM, and consequently the THM concentration infinishedwater with recycle is sometimes higher than without recycle. This condition can impact a utility's distribution-system TTHM average. At the Mianus plant, raw water TTHMFP ranged from 150 to 195 pg/L. Filtered water values were between 120 and 150 pg/L without recycle and between 120 and 190 pg/L with recycle. TTHM precursor concentrations were greater than those of raw water orfinishedwater levels for pressate (400 to 450 pg/L), sludge thickener overflow (350 to 440 pg/L), clarifier sludge (480 to 575 pg/L), and spent filter backwash water (300 to 485 pg/L). Low solids concentrations were found in the thickener supernatant; thus, the
TTHMFP in the thickener tank was associated primarily with the liquid phase. Because the TTHMFP was higher in these streams than in the raw water, Cornwell and Lee (1993b) postulated a precursor release from the solids into the overlying water. Excess TTHMFP associated with clarifier flush and spent filter backwash appeared to be associated with the solids, with little release to the liquid phase. This result was attributed to the settling of these streams, which generated TTHMFP levels nearly equal to those in raw or filtered water. Recycling of settled backwash streams had very little, if any, impact onfilteredTTHMFP. Analysis of TTHMFP in the New Castle plant process streams showed similar results. The recycle streams with solids contained high TTHMFP, but settled streams had TTHMFP levels nearly as low as those in raw water; however, one round of sampling at the New Castle plant did show elevated levels of TTHMFP in the treated recycled stream (Cornwell and Lee 1993b).