Occurrence Assessment for the Long Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules EPA Document No. 815-R-00-019 [W-99-10-II-B-49]
Other documents for the same rulemaking (all, by stage)
References: 1,178 extracted, 0 linked to papers
SDWC 1980). Recent data on inactivation of health-related microbes by chloramines support the position that drinking water should not be disinfected exclusively with this agent unless other treatment processes are present to provide substantial microbial reductions or the source water is already of very good quality. Viruses such as hepatitis A virus and rotaviruses, for example, are extremely resistant to chloramines (Sobsey 1989). There is little information concerning the mode of action by which chlorine dioxide inactivates vimses. Viruses have rapid rates of reaction with chlorine dioxide; when chlorine and chlorine dioxide are combined, the inactivation appears to be synergistic. Inactivation of poliovirus type 3 by chlorine dioxide has been documented to occur at a rate that increases with increasing pH at pH values from 5.6 to 8.5 (SDWC 1980).
White (1986) concluded that ozone was a superior vimcide. Payment and Armon (1989) maintain that ozonation of viruses that were not eliminated by prechlorination-coagulation-sedimentation-filtration were relatively insensitive to the ozonation process. As with other oxidizing agents, the efficiency of ozonation is reduced when dissolved organic matter and reduced inorganic constituents are present (EPA 1999a). Vimses in water and on exposed surfaces can be inactivated with UV light (Cliver 1997). The factors that determine the amount of UV radiation needed to disinfect a body of water are turbidity, color, and dissolved iron salts, which prevent the UV energy from penetrating the water. UV light is generally not used
Research, Britain 1994 Cryptosporidium Giardia 1.5-2 1.5-2 Full-scale plant (operation considered not optimized) Kelley etal. 1995 Cryptosporidium Giardia 2.7-5.9 3.4-5.0 Pilot plants
Pataniaetal. 1995 Cryptosporidium Giardia 2.7-3.1 3.1-3.5 Pilot plants Ongerth and Pecoraro 1995 Cryptosporidium Giardia 1.3-3.8 Pilot plants 2.9-4.0 Pilot plants
Pataniaetal. 1995 Nieminski and Ongerth 1995 Cryptosporidium Pilot plants West etal. 1994 Cryptosporidium Giardia Pilot plant at 4.5 to 16.5°C Schuler and Ghosh 1991 Cryptosporidium Full-scale plant
NR = No marked reduction. Coagulation and flocculation do not themselves serve as mechanisms for virus removal. However, microorganisms may become trapped within the aggregated mass and be removed upon filtration or sedimentation. Payment and Armon (1989) evaluated the percent removal of indigenous viruses at operational water treatment plants for a combined flocculation and settling step. Results ranged from 0- to 74-percent removal of rotavims, enterovims, and bacteriophage during the dry and rainy seasons. Some states give coagulation and flocculation credit for vims removal (EPA 1999a). There is no specific information on the effectiveness ofwater treatment process for Cyclospora or Toxoplasma removal. However, since Cyclosporaand Toxoplasma oocysts are slightly larger than those of
5. OCCURRENCE OF PATHOGENS AND OTHER CONTAMINANTS OF CONCERN Evidence for the occurrence of Cryptosporidium parvum, Giardia lamblia-, and other microbial pathogens (microbiological contaminants) in drinking water supplies is available from national epidemiological surveillance summaries, and from a limited number of surveys and monitoring studies. Each of these lines of evidence is discussed in this chapter. First, an overview of national waterborne disease outbreak surveillancedata collected from 1971-1996 is presented in Section 5.1. These national surveillance data document the numbers of community and non-community surface water system outbreaks and the numbers of related illnesses attributed to waterbome pathogens. Recently compiled surveillance data on waterbome disease outbreaks in small drinking water systems from 1991 -1996 are discussed in greater detail. In Section 5.2, occurrence data for Cryptosporidium are discussed, including a presentation of available Cryptosporidium concentration data that were collected following disease outbreaks in small systems. This section also reviews general (i.e., non-outbreak) survey and monitoring data that document the occurrence of Cryptosporidium oocysts in raw and finished water supplies, including surface water and
Feb. 1997) Range of positive values arftrti-* Mean6 Unknown 33.3 Reference Fridirici 1997 12/L Sebald 1997 Infiltration gallery (Salem, OR, Jan. 1994 through Sept. 1996) 35.5 0.3 - 12.7/L Salis 1997 Ranney collector (St. Helens, OR, May 1993 <2.3 4.5/L Salis 1997 1 sample 0.77 Smith 1997 33.3 through Mar. 1997) Well (Marshfield, MA, June 1997)
Shallow, vertical well (Braymer Well #4, MO, May 1995) " These data are presented as they were reported in the referenced study. Geometric mean reported unless otherwise indicated. Number of sites sampled and percent of site's positive are reported rather than the number of samples from each site. Data compiled for 62 positive samples from all sources in the survey, with outlier data removed from analysis.
NR = Not reported. 0.3/100 L Ledbetter (undated) P.87 Occurrence Assessment for the Long-Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules In Oregon, Cryptosporidium oocysts were detected at three sites: Sebald (1997) has reported that Cryptosporidium oocysts were found in a well drilled into basalt at 12 oocysts/100 L. The well is located 80 feet from a river, is 55 feet deep, and is suspected of being linked to the river by a gravel conduit. Microscopic analyses were conducted after close correlations were observed between pH and turbidity values in the river and the well. Eleven presumptive Cryptosporidium oocyst occurrences have been reported at an infiltration gallery located 15 feet below a river (Salis 1997).
Missouri, and Florida. One presumptive oocyst has been reported in a well in Massachusetts (Smith 1997). In Missouri, one unconfirmed Cryptosporidium oocyst (0.3/100 L) was detected in a shallow alluvial well that may have been impacted by flooding [Ledbetter (undated)].
Okunetal. 1997 aIS3 Table 5-12. Summary of Surface Water Monitoring Data for Giardia Cysts (continued) Sample source Number of samples (n) River (polluted) Raw water (100 plants) Filter (100 plants) Surface water (8 locations in a creek, river, and sewage treatment plant effluent) 6-10 from each location Samples positive for Limit of Range of cyst Estimated Giardia detection" concentration recovery rate" (percent) (cysts/100 L) (cysts/100 L) (percent) Stable flow: 50-100 Storm flow: 60-100 Stable flow: 0.1-1 Storm flow: 0.1-10 ° These data are presented as reported in the referenced study. * All samples.
EPA (1994) reported Giardia concentrations of 1 cyst/100 gallons from an infiltration gallery, and 3 cysts/100 gallons in a gravel well that was flooded. Giardia cysts also were found at three sites in Oregon, including a 55-foot deep basalt well, an infiltration gallery, and a Ranney collector. In the basalt well, Giardia cysts were detected at 4 cysts per September 28, 2000 5-64 Occurrence Assessment for the Long-Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules 100 gallons (Sebald 1997). Two samples collected from the infiltration gallery were found to have presumptive Giardia cysts (2/100 L and 22.6/100 L), and the Ranney collector had an unconfirmed occurrence of 9.1 Giardia cysts per 100 gallons (Salis 1997). Hancock et al. (1998b) evaluated the occurrence oi Giardia in ground water at 199 sites using the
ICR method. Giardia cysts were detected in samples from 6 percent (12 of 199) ofthe sites, including 1 percent (2 of 149) ofthe vertical wells, 14 percent (5 of 35) ofthe springs, 25 percent (1 of 4) ofthe infiltration galleries, and 36 percent (4 of 11) ofthe horizontal wells. The range of cyst density detected was from <0.1 to 120 cysts/100 L, with a mean density of 8 cysts/100 L (std = 25) and a median density value of 2 cysts/100 L (Hancock et al. 1998b). As described in Section 5.2.2, Hancock et al. (1998a) have performed statistical analyses of an unpublisheddataset(383 ground water samples), and report a correlation ofthe detection oi Giardia in ground water with the depth ofthe source sampled. The presence of Giardia also correlated with the presence oi Cryptosporidium in this data set (Hancock et al. 1998a). September 28, 2000 5-65 Table 5-13. Summary of Ground Water Monitoring Data for Giardia Cysts" Number of samples Samples positive for Giardia (percent) Vertical well 149 sites' Hancock etal. 1998b Spring 35 sites' Hancock etal. 1998b Infiltration gallery 4 sites' Hancock etal. 1998b Horizontal well 11 sites' Hancock et al. 1998b Total ground water sources 199 sites Springs Hibler 1988 Wells Hibler 1988 Infiltration galleries Hibler 1988 Spring (East Haines Twp., Center Co.,
PA, May 1997) Vertical well (Lemont Well #4, Center Co., PA, Feb. 1991 - A u g . 1992) 1.6-2.9 Vertical well (Lemont Well #5, Center Co., PA, Feb./Mar. 1991) Springs (Defiance, PA, Apr. 1994) Fridirici 1997 Infiltration gallery (Huckleberry, PA, June 1991) Fridirici 1997 Sample source Limit of Range of detection" positive values Mean (cysts/100 L) (cysts/100 L) (cysts/100 L)A 0.1-120'' Reference Hancock etal. 1998b
PADEP 1997; Conrad 1997 Lee 1993; PADEP 1997; Conrad 1997 Lee 1993; PADEP 1997; Conrad 1997 Table 5-13. Summary of Ground Water Monitoring Data for Giardia Cysts" (continued) Range of cyst Mean concentratio (cysts/100 (cysts/100 L) Number samples Percent of sites positive for Giardia Springs (Topton Boro, Reading District,
PA, Jan. 1993) Fridirici 1997 Spring (Aaronsburg, Spring #2, Center Co., PA, June 1997) Diehl 1997 Spring (Aaronsburg, Spring #4, Center Co., PA, June 1997) Diehl 1997 Vertical well (Douglas Co., OR, Feb 1996, Feb. 1997) 33.3 Sebald 1997 Infiltration gallery (Salem, OR, Jan. 1994-Sept. 1996) 0.5-6 Salis 1997 Ranney collector (St. Helens, OR, May 1993-Mar. 1997) Rock well (Byfield, MA, May 1994) Sample source Detection limit (cysts/100 Reference <2.3 Sal is 1997 Smith 1997 Caisson well (North Attleboro, MA,
EE&T (1999) reported that only one study, by Wang et al. (1973), addressed the impacts of FBR on inorganic finished water quality. Cornwell and Lee (1993) studied the effects of filter backwash on the concentrations of inorganics in water treatment process streams. The ranges of-inorganics, including manganese, iron, aluminum, copper, and arsenic, in filter backwash and related process streams were reviewed by EE&T (1999) and are summarized in Table 5-16. Table 5-15. Summary of Cryptosporidium and Giardia Occurrence in Process Streams Pathogen Cryptosporidium Total Concentration Range (oocysts or cysts/lOOL) Number Samples Untreated spent filter backwash
ND-750 n>50 Cornwell and Lee 1993b; Karanis etal. 1995; Karanis etal. 1998 Untreated sediment basin sludge 2,642 Cornwell and Lee 1993b Thickener 82 - 420 Cornwell and Lee 1993b <210 Cornwell and Lee 1993b Process Stream supernatant Sludge drying bed decant and overflow September 28, 2000 Comments References Three of five studies reported oocysts > 15,000/ 100L Cornwell and Lee 1993b; LeChevallier etal. 199 Id; States et al. 1995; LeChevallier et al. 1998; Rose 1989, as cited in EE&T 1999 5-75 Occurrence Assessment for the Long-Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Pathogen Process Stream Untreated spent filter backwash Giardia Total Concentration Range (oocysts or cysts/1 OOL) Number Samples
ND-16,513 n>50 Comments References Two of five sources reported cysts > 10,000/ 100L Cornwell and Lee 1993b; LeChevallier etal. 199 Id; States et al. 1995; LeChevallier et al. 1998; Rose 1989, as cited in EE&T 1999 Treated spent filter backwash
ND - 374 n>50 Cornwell and Lee 1993b; Karanis etal. 1995 Untreated sediment basin sludge 5,284 n= 1 Cornwell and Lee 1993b Thickener supernatant
ND-71 Cornwell and Lee 1993b Cornwell and Lee 1993b Sludge drying bed decant and overflow
ND = None detected or below method detection Source: EE&T 1999. Manganese Concentrations of total manganese detected in untreated sedimentation basin sludge range from 0.34 to 865 mg/L; dissolved manganese ranges from 1.2 to 7.28 mg/L (EE&T 1999). Hoehn et al. (1987) collected sludge samples from a mechanicallycleaned basin at the Lee Hall plant on three occasions (March,
AWWSC 1998 Untreated spent filter backwash 0.001 0.85 n>50 LeChevallier et al. 1998 and
AWWSC 1998 Treated spent filter backwash AWWSC 1998 0.0045 15.44 n=234 Cornwell et al. 1992, Schmitt and Hall 1975, Cornwell 1986, Wortel and Koppers 1989, Koppers et al. 1985, and AWWSC 1998 Untreated sedimentation basin sludge Sedimentation basin sludgetreated supernatant
AWWSC 1998 Table 5-16. Summary Inorganic Contaminant Occurrence in Process Streams (continued) <-_. Inorganic Contaminant Arsenic (continued) Concentration Range (mg/L) Total Number Samples Thickener supernatant O.001
AWWSC 1998 Lagoon decant O.001 AWWSC 1998 Mechanical dewatering device O.05 - 0.70
AWWSC 1998 Process Stream Dissolved References Reverse osmosis
AWWSC 1998 Thickener supernatant O.Ol AWWSC 1998 Lagoon decant O.Ol
AWWSC 1998 Mechanical dewatering device concentrate O.Ol 0.340
AWWSC 1998 Sludge drying bed decant and underflow 0.11 — 48.2 n=13 Wortel and Koppers 1989 Pump packing water 0.045
AWWSC 1998 GAC transport water from a filter absorber O.Ol 0.130
AWWSC 1998 Untreated spent filter backwash O.l1000 n>40 Sa-1 Typical iron values were below 50 mg/L, although one reference reported a value of 1,000 mg/L. Cornwell and Lee 1993b, Grubb and Arnold 1997, Klezcewski 1997, Cornwell and Koppers 1990, and LeChevallier et al. 1998 Treated spent filter backwash 0.01216 Cornwell and Lee* 1993b, Wang and Yang 1975, Klezcewski 1997, and AWWSC 1998 Untreated sedimentation basin sludge 6.47 58.42,025 n=10 Cornwell and Lee 1993b, Cornwell 1986, Cornwell et al. 1981, Van Duijvenbode et al. 1985, and Such etal. 1998 Table 5-16. Summary Inorganic Contaminant Occurrence in Process Streams (continued) Inorganic Contaminant Iron (continued) Cone. Range (mg/L) Process Stream Thickener supernatant Manganese Comments References Dissolved Total O.05 0.100.13 Cornwell and Lee 1993b 0.08 Snoeyink et al. 1984 Reverse osmosis membrane concentrate Mechanical dewatering device concentrate Number Samples O.05 0.4165 n=ll Cornwell and Lee 1993b and Such et al. 1988 Vandermeyden and Cornwell 1998 and Wortel and Koppers 1989 0.068.45 Pump packing water <0.1
AWWSC 1998 GAC transport water 5.2 - 9.0 AWWSC 1998 O.Ol 17.9 n>50 Cornwell and Lee 1993b, Grubb and Arnold 1997, Klezcewski 1997, LeChevallier et al. 1998, and AWWSC 1998 Treated spent filter backwash Untreated sedimentation basin sludge Sa-1 Sludge drying bed decant and underflow Untreated spent filter backwash n=17 0.150.75 O.02 0.92 1.2-7.28 O.02 0.34 n=27 Cornwell and Lee 1993b, Wang and Yang 1975, Klezcewski 1997, and
AWWSC 1998 a«__ Table 5-16. Summary Inorganic Contaminant Occurrence in Process Streams (continued) <__> Inorganic Contaminant Manganese (continued) Cone. Range (mg/L) Process Stream Comments References "5a<. Dissolved Total Sedimentation basin sludge-treated supernatant 0.263.08 0.26186.0 Cornwell and Lee 1993b and
AWWSC 1998 0.01 Snoeyink et al. 1984 Reverse osmosis membrane concentrate Number Samples Lagoon decant 0.62 O.Ol 0.70 The upper ends of both total and dissolved manganese ranges are high. Cornwell and Lee 1993b and
AWWSC 1998 Sludge drying bed decant and underflow 0.0512.34 n=17 Vandermeyden and Cornwell 1998 and Wortel and Koppers 1989 Pump packing water O.Ol
AWWSC 1998, GAC transport water from a filter absorber 4.249.2
TOC in Process Streams EE & T (1999) reviewed occurrence data for TOC in water treatment process streams. These data are summarized in Table 5-17. Observed TOC concentrations in untreated spent filter backwash water ranged from 2.9 to 41.9 mg/L. TOC apparently concentrates in settled solids (untreated sedimentation basin sludge contains 8.7 to 245 mg/L TOC). Cornwell and Lee (1993b) sampled several plants for TOC in the waste streams and within the treatment process. Several streams showed elevated TOC levels; however, most ofthe TOC was associated with the solids and readily settled out. TOC levels in some streams were higher than 200 mg/L, which could impact the formation of DBP if the solids are not settled out prior to recycling. Filtered water TOC levels were not affected by recycling at the plants studied. September 28, 2000 5-87 Occurrence Assessment for Ihe Long-Term I Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Table 5-17. Summary of Total Organic Carbon Occurrence in Process Streams Total Concentration Range (mg/L) Number of Samples Untreated spent filter backwash 2.9-41.9 n>50 Cornwell and Lee 1993b, Ashcroft etal. 1997, Nieminski 1997, LeChevallier etal. 1998, and
AWWSC 1998 Treated spent filter backwash 2.1-9.9 Cornwell and Lee 1993b and Ashcroft etal. 1997 Untreated sedimentation basin sludge 8.7-245 Cornwell and Lee 1993b Sedimentation basin sludge-treated supernatant 5.1-15.1 Cornwell and Lee 1993b Thickener supernatant 2.1-4.4 Cornwell and Lee 1993b Reverse osmosis membrane concentration 27-33 Nelson and DiGiano 1996 5.8-14.3 Process Stream Lagoon decant Mechanical dewatering
ND - 0.700 n=22 Cornwell and Lee 1993 b, Koppers 1987, and
AWWSC 1998 Sedimentation basin sludgetreated supernatant 0.091-0.197 Cornwell and Lee 1993b and
AWWSC 1998 Thickener supernatant 0.011-0.127 Cornwell and Lee
AWWSC 1998 5-91 P.36 Occurrence Assessment for the Long-Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Disinfection Byproduct Total trihalomethane formation potential (TTHMFP) September 28,2000 Total Concentration Range (mg/L) Number Samples Mechanical dewatering device 0.128-0.276 Cornwell and Lee 1993b Pump packing water 0.030
AWWSC 1998 GAC transport water from a filter absorber 0.031-0.063
AWWSC 1998 Untreated spent filter backwash 0.135-0.465 The upper end of the Cornwell and Lee
TTHMFP 1993b and concentration range, Ashcroft et al. 0.465 mg/L, was 1997 higher than the average of 0.350 mg/L. Treated spent filter backwash 0.084-0.658 Cornwell and Lee 1993b and Ashcroft 1997 Untreated sedimentation basin sludge 0.209 - 2.032 Cornwell and Lee 1993b Sedimentation basin sludgetreated supernatant 0.270 - 0.686 Cornwell and Lee 1993b Thickener supernatant 0.170-0.259 Cornwell and Lee 1993b Lagoon decant Mechanical dewatering device 0.397 - 0.499 Process Stream Comments
TTHMFP levels were similar to those of source water. References Cornwell and Lee 1993b Cornwell and Lee 1993b 5-92 Occurrence Assessment for the Long-Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Disinfection Byproduct Total Concentration Range (mg/L) Number Samples Untreated spent filter backwash O.001-0.185 n>40 LeChevallier et al. 1998 and
AWWSC 1998 ND = None detected or below detection level Source: EE&T 1999. September 28, 2000 5-93 P.38 Occurrence Assessmentfor the Long-Term 1 Enhanced Surface Water Treatment and Filter Backwash Recycling Rules Total Trihalomethanes
TTHM in Process Streams Cornwell and Lee (1993b) evaluated TTHM and TTHMFP in several treatment facilities and on different types of process streams. In general, it was found that if the solids are removed from the recycle stream prior to recycling, TTHMFP in recycle is no higher than in the raw water. However, without solids removal, TTHMFP can increase in the recycle streams. The recycled streams can contain pre-formed THM, and consequently the THM concentration in finished water with recycle is sometimes higher than without recycle. This condition can impact a utility's distribution-system TTHM average. At the Mianus plant, raw water TTHMFP ranged from 150 to 195 /_g/L. Filtered water values were between 120 and 150 /ig/L without recycle and between 120 and 190 /ig/L with recycle. TTHM precursor concentrations were greater than those of raw water or finished water levels for pressate (400 to 450 //g/L), sludge thickeneroverflow(350 to 440 /ig/L), clarifier sludge (480 to 575 /ig/L), and spent filter backwash water (300 to 485 /ig/L). Low solids concentrations were found in the thickener supernatant; thus, the