Mousavi ES, Kananizadeh N, Martinello RA, Sherman JD. (2020). COVID-19 Outbreak and Hospital Air Quality: A Systematic Review of Evidence on Air Filtration and Recirculation. Environ Sci Technol. acs.est.0c03247. https://doi.org/10.1021/acs.est.0c03247.
Other documents for the same rulemaking (all, by stage)
References: 38 extracted, 0 linked to papers
HEPA filter. Hahn et al. (2002) also showed that HEPA filters made a significant reduction in the number of HAIs in highly immunocompromised patients.77 The incident of nosocomial Aspergillus infection was 10 times lower when the BMT patient was placed in a room with HEPA filtration and laminar airflow.78 Passweg et al. (1998) also found that HEPA filters reduced contamination and increased the survival of BMT and leukemia patients.54 During a four-year period, in two hematology wards and a
ACH, removing particles, and reducing the risk of transmission in general wards when there are not enough isolation wards as is the case with the COVID-19 pandemic8,39,89,93−95 (Table 5). Miller et al. (1996) investigated the effectiveness of portable air filters (PAFs) and ceiling mounted air filters (CMAFs) for controlling TB exposure. CMAFs were shown to be more advantageous over PAFs due to their elevated inlet and the buoyant nature of the droplet nuclei.62 Qian and colleagues tested the performance of portable HEPA filters, such as their effect on the airflow pattern, using both smoke visualization and computer simulation. They found that having portable
Al-waked (2010) investigated the steady state operation of a laminar flow system (LAF) using HEPA filters that was centrally located in the OR ceiling, using computational fluid dynamics (CFD), and results indicated their effectiveness in minimizing the spread of contaminants and providing thermal comfort.68 One major difference between the OR design and that for the AIIR is the use of laminar airflow systems. The laminar flow system provides a unidirectional flow,36 and it must not be confused with cleaned air.69 The HEPA filtration plays an outstanding role in the efficiency of laminar flow systems, as it assures the cleanliness of the supply air prior to pouring it on the OR bed.70−72 The laminar air flow combined with HEPA filters can bring the contamination level down and is recommended for ORs and immunocompromised patient rooms.37,73−78 It must be noted that a true laminar flow system is not achievable, as hospital personnel and equipment movements often disturb airflow patterns.7 In a study by Sheretz et al. (1987), the use of whole-wall
OR + pediatric hematology room acute tertiary-care Qian et al. (2007)93 Article
Technol. 2012, 46 (2), 138−147. (27) Bemer, D.; Calle, S. Evolution of the Efficiency and Pressure Drop of a Filter Media with Loading. Aerosol Sci. Technol. 2000, 33 (5), 427−439. (28) Furtaw, E. J., Jr.; Pandian, M. D.; Nelson, D. R.; Behar, J. V. Modeling Indoor Air Concentrations Near Emission Sources in Imperfectly Mixed Rooms. J. Air Waste Manage. Assoc. 1996, 46 (9), 861−868. (29) Stephens, B.; Novoselac, A.; Siegel, J. A. The Effects of Filtration on Pressure Drop and Energy Consumption in Residential
HVAC Systems (RP-1299). HVACR Res. 2010, 16 (3), 273−294. (30) Kadam, V.; Truong, Y. B.; Easton, C.; Mukherjee, S.; Wang, L.;
Padhye, R.; Kyratzis, I. L. Electrospun Polyacrylonitrile/β-Cyclodextrin Composite Membranes for Simultaneous Air Filtration and Adsorption of Volatile Organic Compounds. ACS Appl. Nano Mater. 2018, 1 (8), 4268−4277. (31) Moher, D.; Liberati, A.; Tetzlaff, J.; Altman, D. G.; Altman, D.;
Shekelle, P. G.; Tovey, D.; Tugwell, P. Preferred Reporting Items for Systematic Reviews and Meta-Analyses: The PRISMA Statement. PLoS Medicine. 2009, 6, e1000100. (32) ASHRAE Standard 170. Ventilation of Health Care Facilities; 2013. (33) Facility Guidelines Institute. Guidelines for Design and Construction of Hospitals; AHA Data & Insight, 2018. (34) ASHRAE Standard 52.2−2017-Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size (ANSI/ASHRAE Approved), 2017. (35) Ninomura, P.; Rousseau, C.; Bartley, J. Guidelines for Design and Construction of Hospital and Health Care Facilities; AIA: Washington,
DC, 2001; Vol. 48. (36) Laufman, H. Current Status of Special Air-Handling Systems in Operating Rooms. Med. Instrum. 1973, 7 (1), 7−15. (37) Ulrich, R. S.; Zimring, C.; Zhu, X.; DuBose, J.; Seo, H.-B.;
Choi, Y.-S.; Quan, X.; Joseph, A. A Review of the Research Literature on Evidence-Based Healthcare Design (Part I). HERD Heal. Environ. Res. Des. J. 2008, 1 (3), 61−125. (38) Yau, Y. H.; Chandrasegaran, D.; Badarudin, A. The Ventilation of Multiple-Bed Hospital Wards in the Tropics: A Review. Build.
Environ. 2011, 46 (5), 1125−1132. (39) Rebmann, T. Management of Patients Infected with AirborneSpread Diseases: An Algorithm for Infection Control Professionals. Am. J. Infect. Control 2005, 33 (10), 571−579. (40) Curry International Tuberculosis Center. Tuberculosis Infection Control A Practical Manual for Preventing TB; University of California
San Francisco, 2011; pp 1−171. (41) Isolation Rooms: Design, Assessment and Upgrade; https://www. abatement.com/media/pdf/isolation-rooms-design-assessmentupgrade.pdf. (42) Victorian Advisory Committee on Infection Control. Guidelines for the Classification and Design of Isolation Rooms in Health Care Facilities; Department of Human Services: Melbourne, Victoria,
Bone Marrow Transplant. 1998, 21 (12), 1231−1238. (55) Shirani, K. Z.; McManus, A. T.; Vaughan, G. M.; McManus, W. F.; Pruitt, B. A.; Mason, A. D. Effects of Environment on Infection in Burn Patients. Arch. Surg. 1986, 121 (1), 31−36. (56) Oren, I.; Haddad, N.; Finkelstein, R.; Rowe, J. M. Invasive Pulmonary Aspergillosis in Neutropenic Patients during Hospital Construction: Before and after Chemoprophylaxis and Institution of
HEPA Filters. Am. J. Hematol. 2001, 66 (4), 257−262. (57) Abraham, G.; Smith, P. M. L. B.; McCabe, P. Hepa Filter Replacement Experience in a Biological Laboratory. J. Am. Biol. Saf.
Surg. 2015, 13 (1), 52−58. (72) Schonholtz, G. J. Maintenance of Aseptic Barriers in the Conventional Operating Room: General Principles. J. Bone Jt. Surg. 1976, 58-A (4), 139−115. (73) Alberti, C.; Bouakline, A.; Ribaud, P.; Lacroix, C.; Rousselot, P.;
Leblanc, T.; Derouin, F. Relationship between Environmental Fungal Contamination and the Incidence of Invasive Aspergillosis in Hematology Patients. J. Hosp. Infect. 2001, 48 (3), 198−206. (74) Arlet, G.; Gluckman, E.; Gerber, F.; Perol, Y.; Hirsch, A. Measurement of Bacterial and Fungal Air Counts in Two BoneMarrow Transplant Units. J. Hosp. Infect. 1989, 13 (1), 63−69. (75) Dharan, S.; Pittet, D. Environmental Controls in Operating Theatres. J. Hosp. Infect. 2002, 51 (2), 79−84. (76) Friberg, S.; Ardnor, B.; Lundholm, R.; Friberg, B. The Addition of a Mobile Ultra-Clean Exponential Laminar Airflow Screen to Conventional Operating Room Ventilation Reduces Bacterial Contamination to Operating Box Levels. J. Hosp. Infect. 2003, 55 (2), 92−97. (77) Hahn, T.; Cummings, K. M.; Michalek, A. M.; Lipman, B. J.;
Epidemiol. 2002, 23 (9), 525−531. (78) Sheretz, R. J.; Belani, A.; Kramer, B. S.; Elfenbein, G. J.; Weiner, R. S.; Sullivan, M. L.; Thomas, R. G.; Samsa, G. P. Impact of Air Filtration on Nosocomial Aspergillus Infections. Am. J. Med. 1987, 83 (4), 709−718. (79) Sadrizadeh, S.; Holmberg, S.; Tammelin, A. A Numerical Investigation of Vertical and Horizontal Laminar Air Flow Ventilation in an Operating Room. Build. Environ. 2014, 82, 517−525. (80) Heffernan, D. S.; Evans, H. L.; Huston, J. M.; Claridge, J. A.;
Blake, D. P.; May, A. K.; Beilman, G. S.; Barie, P. S.; Kaplan, L. J. Surgical Infection Society Guidance for Operative and Peri-Operative Care of Adult Patients Infected by the Severe Acute Respiratory Syndrome Coronavirus-2 (SARS-CoV-2). Surg. Infect. (Larchmt). 2020, 21 (4), 301−308. (81) Johnson, D. L.; Lynch, R. A.; Mead, K. R. Containment Effectiveness of Expedient Patient Isolation Units. Am. J. Infect. Control 2009, 37 (2), 94−100. (82) Marier, R. L.; Nelson, T. A Ventilation-Filtration Unit for Respiratory Isolation. Infect. Control Hosp. Epidemiol. 1993, 14 (12), 700−705. (83) Streifel, A.; Rhamme, F. Hospital Building Design for Particle Management. In Healthy Buildings; Chicago, IL, 1995; pp 72−75. (84) Barnes, R. A.; Rogers, T. R. Control of an Outbreak of Nosocomial Aspergillosis by Laminar Air-Flow Isolation. J. Hosp.
Infect. 1989, 14, 89−94. (85) Cornet, M.; Levy, V.; Fleury, L.; Lortholary, J.; Barquins, S.;
Coureul, M. H.; Deliere, E.; Zittoun, R.; Brücker, G.; Bouvet, A. Efficacy of Prevention by High Efficiency Particulate Air Filtration of Laminar Airflow against Aspergillus Airborne Contamination during Hospital Renovation. Infect Control Hosp Epidemiol 1999, 20, 508− 513. (86) Richardson, M. D.; Rennie, S.; Marshall, I.; Morgan, M. G.;
Murphy, J. A.; Shankland, G. S.; Watson, W. H.; Soutar, R. L. Fungal Article Survelliance of an Open Haematology Ward. J. Hosp. Infect. 2000, 45 (4), 288−292. (87) Araujo, R.; Carneiro, A.; Costa-Oliveira, S.; Pinavaz, C.;
Rodrigues, A. G.; Guimaraes, J. E. Fungal Infections after Haematology Unit Renovation: Evidence of Clinical, Environmental and Economical Impact. Eur. J. Haematol. 2008, 80, 436−443. (88) Abdul Salam, Z. H.; Karlin, R. B.; Ling, M. L.; Yang, K. S. The Impact of Portable High-Efficiency Particulate Air Filters on the Incidence of Invasive Aspergillosis in a Large Acute Tertiary-Care Hospital. Am. J. Infect. Control 2010, 38 (4), e1−e7. (89) Rutala, W. A.; Jones, S. M. N.; Worthington, J. M.; Reist, P. C.;
Biotechnol. 2005, 32 (7), 319−321. (101) Gilbert, Y.; Duchaine, C. Bioaerosols in Industrial Environments: A Review. Can. J. Civ. Eng. 2009, 36 (12), 1873−1886. (102) Muñoz, P.; Guinea, J.; Peláez, T.; Durán, C.; Blanco, J. L. L.;
Bouza, E.; Munoz, P.; Guinea, J.; Pelaez, T.; Duran, C.; Blanco, J. L. L.; Bouza, E. Nosocomial Invasive Aspergillosis in a Heart Transplant Patient Acquired during a Break in the HEPA Air Filtration System. Transplant Infect. Dis. 2004, 6 (1), 50−54. (103) Lutz, B. D.; Jin, J.; Rinaldi, M. G.; Wickes, B. L.; Huycke, M. Outbreak of Invasive Aspergillus Infection in Surgical Patients, Associated with a Contaminated Air-Handling System. Clin. Infect.
Dis. 2003, 37 (6), 786−793. (104) Kumari, D. N. P.; Haji, T. C.; Keer, V.; Hawkey, P. M.;
Duncanson, V.; Flower, E. Ventilation Grilles as a Potential Source of Methicillin-Resistant Staphylococcus Aureus Causing an Outbreak in an Orthopaedic Ward at a District General Hospital. J. Hosp. Infect. 1998, 39 (2), 127−133. (105) Mcdonald, L. C.; Walker, M.; Carson, L.; Arduino, M.;
Aguero, S. M.; Gomez, P.; Mcneil, P.; Jarvis, W. R. Outbreak of https://dx.doi.org/10.1021/acs.est.0c03247 Environ. Sci. Technol. XXXX, XXX, XXX−XXX Environmental Science & Technology pubs.acs.org/est Acinetobacter Spp. Bloodstream Infections in a Nursery Associated with Contaminated Aerosols and Air Conditioners. Pediatr. Infect. Dis. J. 1998, 17 (8), 716−722. (106) Uduman, S. A.; Farrukh, A. S.; Nath, K. N. R.; Zuhair, M. Y. H.; Ifrah, A.; Khawla, A. D.; Sunita, P. An Outbreak of Serratia Marcescens Infection in a Special-Care Baby Unit of a Community Hospital in United Arab Emirates: The Importance of the Air Conditioner Duct as a Nosocomial Reservoir. J. Hosp. Infect. 2002, 52 (3), 175−180. (107) Bergeron, V.; Reboux, G.; Poirot, J. L.; Laudinet, N. Decreasing Airborne Contamination Levels in High-Risk Hospital Areas Using a Novel Mobile Air-Treatment Unit. Infect. Control Hosp.
Epidemiol. 2007, 28 (10), 1181−1186. (108) Foarde, K. K.; Van Osdell, D. W.; Menetrez, M. Y. Investigation of the Potential Antimicrobial Efficacy of Sealants Used in HVAC Systems. J. Air Waste Manage. Assoc. 2001, 51, 1219− 1226. (109) Cecchini, C.; Verdenelli, M. C.; Orpianesi, C.; Dadea, G. M.;
Cresci, A. Effects of Antimicrobial Treatment on Fiberglass-acrylic Filters. J. Appl. Microbiol. 2004, 97 (2), 371−377. (110) Foarde, K. K.; Hanley, J. T. Determine the Efficacy of Antimicrobial Treatments of Fibrous Air Filters. ASHRAE Trans. 2001, 107, 156−170. (111) Griffiths, W. D.; Bennett, A.; Speight, S.; Parks, S. Determining the Performance of a Commercial Air Purification System for Reducing Airborne Contamination Using Model MicroOrganisms: A New Test Methodology. J. Hosp. Infect. 2005, 61 (3), 242−247. (112) Verdenelli, M. C.; Cecchini, C.; Orpianesi, C.; Dadea, G. M.;
Cresci, A. Efficacy of Antimicrobial Filter Treatments on Microbial Colonization of Air Panel Filters. J. Appl. Microbiol. 2003, 94 (1), 9− (113) Xia, T.; Kleinheksel, A.; Lee, E. M.; Qiao, Z.; Wigginton, K. R.; Clack, H. L. Inactivation of Airborne Viruses Using a Packed Bed Non-Thermal Plasma Reactor. J. Phys. D: Appl. Phys. 2019, 52 (25), 255201. (114) Centers for Disease Control and Prevention.. Environmental Control for Tuberculosis: Basic Upper-Room Ultraviolet Germicidal Irradiation Guidelines for Healthcare Settings. DHHS Natl. Inst. Occup. Saf. Heal. Publ. 2009, 87. (115) Jacob, J. T.; Kasali, A.; Steinberg, J. P.; Zimring, C.; Denham, M. E. The Role of the Hospital Environment in Preventing Healthcare-Associated Infections Caused by Pathogens Transmitted through the Air. Heal. Environ. Res. Des. J. 2013, 7, 74−98. (116) Ryan, R. M.; Wilding, G. E.; Wynn, R. J.; Welliver, R. C.;
Holm, B. A.; Leach, C. L. Effect of Enhanced Ultraviolet Germicidal Irradiation in the Heating Ventilation and Air Conditioning System on Ventilator-Associated Pneumonia in a Neonatal Intensive Care Unit. J. Perinatol. 2011, 31 (9), 607. (117) Yang, Y.; Zhang, H.; Nunayon, S. S.; Chan, V.; Lai, A. C. K. Disinfection Efficacy of Ultraviolet Germicidal Irradiation on Airborne Bacteria in Ventilation Ducts. Indoor Air 2018, 28 (6), 806−817. (118) Memarzadeh, F.; Olmsted, R. N.; Bartley, J. M. Applications of Ultraviolet Germicidal Irradiation Disinfection in Health Care Facilities: Effective Adjunct, but Not Stand-Alone Technology. Am. J. Infect. Control 2010, 38, S13−S24. (119) Marshall, J. W.; Vincent, J. H.; Kuehn, T. H.; Brosseau, L. M. Studies of Ventilation Efficiency in a Protective Isolation Room by the Use of a Scale Model. Infect. Control Hosp. Epidemiol. 1996, 17 (1), 5−10. (120) Mousavi, E. S.; Grosskopf, K. R. Internal Contaminant Source Dilution and Filtration in Dedicated Outdoor Air Systems. Procedia
Eng. 2015, 118, 12−18. (121) Kameel, R. Energy Efficient and Hygienic Operating Theatres’
HVAC Airside Design Architectural and Engineering Consideration. In International Energy Conversion Engineering Conference; 2003. Article (122) Lidwell, O. M. Design and Ventilation of Operating Room Suites for Control of Infection and for Comfort. Inst. Heat. Vent. Eng. 1962, 30, 320−328. (123) Streifel, A. J. Design and Maintenance of Hospital Ventilation Systems and Prevention of Airborne Nosocomial Infections; Lippincott Williams & Wilkins: Philadelphia, PA, 1999. (124) Ulrich, J. A. Recirculation of Air in Operating Rooms.
ASHRAE J. 1974. (125) Woods, J. E.; Brayman, D. T.; Rasmussen, R. W.; Reynolds, G. L.; Montag, G. M. Ventilation Requirements in Hospital Operating Rooms - Part I: Control of Airborne Particles. ASHRAE Trans. 1986, 92, 396−426. (126) Pereira, M. L. Modeling and Measurement of Air Contaminant Distribution in an Operating Room Ventilated with Split System, Part II: The Impact on Airborne Particles. ASHRAE 2011. (127) Mousavi, E. S.; Grosskopf, K. R. Ventilation Rates and Airflow Pathways in Patient Rooms: A Case Study of Bioaerosol Containment and Removal. Ann. Occup. Hyg. 2015, 59 (9), 1190−1199. (128) Kang, Y.; Wang, Y.; Zhong, K. Effects of Supply Air Temperature and Inlet Location on Particle Dispersion in Displacement Ventilation Rooms. Particuology 2011, 9 (6), 619−625. (129) Cayer, M.; Veillette, M.; Pageau, P.; Hamelin, R.; Bergeron, M.; Mériaux, A.; Cormier, Y.; Duchaine, C. Identification of Mycobacteria in Peat Moss Processing Plants: Application of Molecular Biology Approaches. Can. J. Microbiol. 2007, 53 (1), 92− (130) Nehme, B.; Létourneau, V.; Forster, R. J.; Veillette, M.;
Duchaine, C. Culture-independent Approach of the Bacterial Bioaerosol Diversity in the Standard Swine Confinement Buildings, and Assessment of the Seasonal Effect. Environ. Microbiol. 2008, 10 (3), 665−675. (131) Lowen, A. C.; Mubareka, S.; Tumpey, T. M.; Garcıa-Sastre, A.; Palese, P. The Guinea Pig as a Transmission Model for Human Influenza Viruses. Proc. Natl. Acad. Sci. U. S. A. 2006, 103 (26), 9988−9992. (132) Shakoor, S.; Mir, F.; Zaidi, A. K. M.; Zafar, A. Hospital Preparedness in Community Measles Outbreaks-Challenges and Recommendations for Low-Resource Settings. Emerging Health
Threats Journal. 2015, 8, 24173. (133) Li, Y.; Huang, X.; Yu, I. T. S. S.; Wong, T. W.; Qian, H. Role of Air Distribution in SARS Transmission during the Largest Nosocomial Outbreak in Hong Kong. Indoor Air 2005, 15 (2), 83− (134) Correia, G.; Rodrigues, L.; Gameiro da Silva, M.; Gonçalves, T. Airborne Route and Bad Use of Ventilation Systems as NonNegligible Factors in SARS-CoV-2 Transmission. Med. Hypotheses 2020, 141 (April), 109781. (135) Joubert, A.; Laborde, J. C.; Bouilloux, L.; Chazelet, S.;
Thomas, D. Modelling the Pressure Drop across HEPA Filters during Cake Filtration in the Presence of Humidity. Chem. Eng. J. 2011, 166 (2), 616−623. https://dx.doi.org/10.1021/acs.est.0c03247 Environ. Sci. Technol. XXXX, XXX, XXX−XXX
Pandemic: Built Environment Considerations To Reduce Transmission. mSystems 2020, 5 (2), 1 DOI: 10.1128/mSystems.00245-20.