Innovative Nutrient Removal Technologies EPA 830-R-01-001 - DCN MP00892
Other documents for the same rulemaking (all, by stage)
References: 70 extracted, 0 linked to papers
WERF. 2015. “Towards a Renewable Future: Assessing Resource Recovery as a Viable Treatment Alternative. Case Studies of Facilities Employing Extractive Nutrient Recovery Technologies”. NTRY1R12b. Water Environment Research Foundation (WERF). Alexandria, 5-18
Zeng, R., van Loosdrecht, M., Yuan, Z., Keller, J. (2003). “Metabolic Model for Glycogen Accumulating Organisms in Anaerobic/Aerobic Activated Sludge Systems”. Biotechnol. Bioeng., 81(1), 92. 5-19
Currently, the facility operates under an annual average total nitrogen (TN) load limit of 334,705 lb/yr, which translates to an equivalent TN discharge limit of approximately 5.5 mg/l at design flow. The TN loading limit may be reduced to 185,345 lb/yr in the near future to comply with the total maximum daily load limits in the Jordan Lake Watershed. This translates to a mass equivalent TN discharge limit of approximately 3.0 mg/l TN at design flow. In 2011, the city completed a wastewater master planning effort that evaluated different treatment alternatives for meeting a total nitrogen (TN) limit of 3 mg/l and a total phosphorus (TP) limit of 0.23 mg/l at its design flow expected in the near future to comply with total maximum daily load limits in the Jordan Lake Watershed which serves as a source of drinking water in the region.
UV disinfection and is post-aerated prior to discharge. Figure 6-1. Liquid and Solids Treatment Process Train at SDWRF (Bilyk et al., 2017) Waste activated sludge (WAS) is thickened through gravity thickeners and then through gravity belt thickener. It is then mixed with primary sludge before entering the anaerobic digesters. Digested sludge is dewatered with belt filter presses, and the dewatered cake is placed in a sludge storage pad prior to transportation to land application sites. Sand drying beds are available but are not in service. Biogas produced in the anaerobic digesters is utilized to run two engine-driven blowers. The dewatering filtrate is fed to a sidestream ANITA Mox® deammonification facility for ammonia and total nitrogen load reduction, and the effluent from the deammonification facility is returned to the head of the plant. Table 6-1. Design and Average Raw Influent Concentrations and Percent of Design Loads for the SDWRF from January 2015 to December 2017 Parameter Raw Influent Design Average Raw Influent Percent of Design1 10.602 68.8 Flow (MGD) 15.4 (Maximum Month)
TKN (lbs/d) TP (lbs/d) 30,182 3,622 43,411 4,739 1,130 26,716 2,431 3,359 88.52 92.74 49.36 (Annual Average) Temperature (oC) Note: 1- Percent of design values, except for flow, are based on average annual values for the analysis period for influent design loads (lbs./day) and actual influent loads (lbs./day). 1- N/A: Data not available or applicable. 2- Raw influent flow data available from 1/1/2015 through 8/1/2016 only
Bilyk, K., Khunjar, W., Pace, G., Worley-Morse, T, Cocker, C., Lobdell, S., Taylor, R., Gasper, B., Pitt, P. (2017). “Lessons Learned about Deammonification from Design, Startup and Operation of an ANITA™ Mox System”. Proceedings of the Water Environment Federation Nutrient Symposium 2017, 253-263.
Bilyk, K. (2017). “Nutrient Removal Optimization”. Presentation at the 2017 Annual Conference of the North Carolina Section of the American Water Works Association & The North Carolina Member Association of the Water Environment Federation, October 5, 2017.
EPRI (Electric Power Research Institute). 2013. “Electricity Use and Management in the Municipal Water Supply and Wastewater Industries”. Technical Report 3002001433. Palo Alto, Calif.
Farina, T., 2012. “An Overview of Sidestream Treatment Alternatives Used to Increase Nutrient Removal”. Presentation at Ohio Water Environment Association Annual Conference. Aurora,
OH, June 20, 2012. Hollowed, M., Thesing, G., Liang, S. (2018). “Tale of Two Cities: Operation of Sidestream Anita MoxTM”. Proceedings of the Water Environment Federation Nutrient Symposium 2018, 747-759.
Mulder, A., Van de Graff, A.A., Robertson, L.A., and Kuenen, J.G. 1995. “Anaerobic Ammonium Oxidation Discovered in a Denitrifying Fluidized Bed Reactor”. FEMS Microbiol Ecology 16, 177-184.
Plaza, E., Trela, J., and Hultman, B. 2009. “Swedish Experience with Deammonification Process in Biofilm System”. Joint Polish-Swedish-Ukrainian Reports, Report no. 14, Proceedings of Research and application of new technologies in wastewater treatment and municipal solid waste disposal in Ukraine, Sweden and Poland.
Twomey, Kelly M., and Michael E. Webber. 2011. “Evaluating the Energy Intensity of the U.S. Public Water Supply.” Proceedings of the ASME 2011 5th International Conference on Energy
Sustainability, ES2011- 54165. 1735–48. U.S. EPA. 2009. “Clean Energy Lead by Example Guide: Strategies, Resources, and Action Steps for State Program”. Washington, DC: US Environmental Protection Agency.
WEF (1997). “Energy Conservation in Wastewater Treatment Facilities”. Manual of Practice No. MFD-2. Alexandria, VA. 6-17
CHAPTER 7.0 Town of Hillsborough Wastewater Treatment Plant – Hillsborough, North Carolina – Modification and Enhancement of 5-Stage BNR – Case Study Background The Hillsborough Wastewater Treatment Plant (HWWTP) is a 3.0 MGD wastewater treatment facility located in the Town of Hillsborough, North Carolina. As of January 2016, HWWTP’s
HWWTP before upgrading the biological process to the five-stage BNR configuration (shown in Figure 7-4 below). Since the upgraded BNR system was constructed by modifying two previously existing stages of aeration and secondary clarification, the last two stages (anoxic, reaeration) of the current 5-stage BNR system are physically separated from the previous three stages. The system is equipped with methanol addition capability in the second anoxic zone and alum addition capability to the secondary clarifiers to be used if needed. Denitrification filters with alum addition are also available but are only used to remove residual suspended solids and total phosphorus. No external carbon is added. The effluent is then disinfected by chlorination prior to dechlorination and post aeration, and then discharged to the Eno River. Solids processing includes aerobic digestion of waste activated sludge, digested sludge storage, gravity belt thickening of digested sludge, storage of thickened sludge, and dewatering prior to hauling the sludge offsite. Figure 7-1. Solids and Liquid Treatment Process Trains at HWWTP Before BNR Upgrades (Adapted from Mahagan and Bilyk, 2016 – With Permission) Table 7-1. Design and Average Raw Influent Concentrations and Percent of Design Loads for the HWWTP from January 2015 to December 2017 Parameter Raw Influent Design Average Influent Percent Design1 1.04 Flow (MGD) (Annual Average) (Maximum Month) BOD5 (lbs/d) 4,441 6,000 1941
TSS (lbs/d) 4,421 5,400 2055 TKN (lbs/d) TP (lbs/d) Temperature (oC) 19.13 Note: 1- Percent of design values, except for flow, are based on average annual values for the analysis period for influent design loads (lbs./day) and actual influent loads (lbs./day). N/A: Data not available or applicable. Table 7-2. NPDES Limits - January 2015 – December 2017 at HWWTP Parameter Monthly Average (mg/l) Flow (MGD) Ammonia
Mahagan, J., Bilyk, K. (2016). “How I’ve Kept Effluent TN Below 1.5 mg/L Without Supplemental Carbon for 500 Days and Counting”. Proceedings of the 2016 Water Environment Federation's Technical Exhibition and Conference (WEFTEC), pp 3317-3328. Metcalf and Eddy, Inc. (2003). “Wastewater Engineering Treatment and Reuse”, 4th ed.;
McGraw-Hill, Inc.: New York. U.S. EPA, 2008. “Municipal Nutrient Removal Technologies Reference Document – Volume I – Technical Report”. EPA 832-R-08-006. Washington, DC. U.S. EPA, 2010. “Nutrient Control Design Manual”. EPA EPA/600/R-10/100. Cincinnati, OH. 7-16