New York State Reliability Council, L.L.C. ( NYSRC) Reliability Rules for Planning and Operations
Other documents for the same rulemaking
References
NYSRC Reliability Rules January 7, 2011 NYSRC Reliability Rules
NYSRC Reliability Rules January 7, 2011 NYISO CONTROL CENTER COMMUNICATIONS (CONT’D.) c. Continued operations from the NYISO Alternate Control Center. The procedures shall identify how various systems are monitored for availability and include methods of tracking performance measures of system availability. Measurements J-M1. The NYISO shall develop the necessary procedures and other required documentation in compliance with J-R1 and J-R2, which shall be provided to the NYSRC on request. J-M2. The NYISO shall prepare reports summarizing performance data of control center communication interfaces. These reports shall be provided to the NYSRC on request or when significant changes are made, and shall include a tracking basis of historical performance of voice and data communication equipment. (J-R2) J-M3. The NYISO shall provide to the NYSRC within one month a report summarizing any loss of critical voice and/or data systems. The report shall describe the problem and its relationship to the control of the NYS Bulk Power System, the cause of the problem, the corrective action,
NYSRC Reliability Rules January 7, 2011 EXCEPTIONS TO RELIABILITY RULES (CONT’D.) Exception Reference
AT-1 bank is in-service. Approved NYPP Operating Committee November 20, 1986.
NYPA Special Protection System Post Contingency Flow on Plattsburgh-Vermont PV20 Line E-R1* The post-contingency flow on the Plattsburgh-Vermont PV20 tie-line is allowed to reach its STE rating so long as NYPA can ensure that the Overload Mitigation system is available on a manual or automatic basis to reduce the flow to below the LTE rating immediately following the actual occurrence of the contingency. Approved NYPP Operating Committee February 15, 1995.
NYPA Monitoring Post Contingency Flow on Marcy Transformer T2 E-R1 The post-contingency flow on the Marcy Transformer T2 is allowed to exceed its LTE rating up to its STE rating following the loss of Marcy Transformer T1. Approved NYPP Operating Committee July 23, 1987.
NYSRC Reliability Rules January 7, 2011 EXCEPTIONS TO RELIABILITY RULES (CONT’D.) Exception Reference Rescinded 1/31/10
NYSRC Reliability Rule E-R1 The following feeders on the Consolidated Edison System have STE ratings which are limited by disconnect or wavetrap restrictions and not by conductor sagging limitations. These feeders will be operated above Normal ratings and up to LTE ratings (for 4 hours) without changing their STE ratings: F30 Pleasant Valley-Wood St. W80 Wood St.-Millwood West F31 Pleasant Valley-Wood St. W81 Wood St.-Millwood West F36 Pleasant Valley-East Fishkill W82 Millwood West-Eastview F37 Pleasant Valley-East Fishkill W85 Millwood West-SprainBrook W64 Eastview-SprainBrook Y86 Wood St.-Pleasantville W65 Eastview-SprainBrook Y87 Wood St.-Pleasantville 69 Ramapo-South Mahwah Y88 Ladentown-Buchanan South 70 Ramapo-South Mahwah W89 Pleasantville-Dunwoodie W72 Ramapo-Ladentown W90 Pleasantville-Dunwoodie W79 Eastview-SprainBrook W99 Millwood West-Eastview W93 Buchanan North-Eastview Y94 Ramapo-Buchanan NorthW75 SprainBrook-Dunwoodie (Winter Rating Period Only) Approved NYRSC Executive Committee September 10, 1999 Applicable Rating W97 and W98 Above Normal Rating Operation E-R1 The following feeders on the Consolidated Edison System have overload relay protection. These feeders will be operated above Normal rating and up to LTE rating (for 4 hours) without changing their STE ratings: W97 Buchanan South-Millwood West W98 Buchanan South-Millwood West Approved NYRSC Executive Committee September 10, 1999
NYSRC Reliability Rules January 7, 2011 EXCEPTIONS TO RELIABILITY RULES (CONT’D.) Exception